INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

OPTIGO OP5U

Consult documentation in all cases where this symbol 

is used, in order to find out the nature of the potential 

hazards and any actions to be taken

1

OPTIGO OP5U

Controller with display

 

Optigo OP5U is a pre-programmed, configurable controller. It has 5 
inputs/outputs and can be configured to control temperature, CO

2

humidity or pressure. All configuration and normal handling is done 
using the display and the knob on the front. From revision R18, it is 
possible to connect an external PT1000 setpoint device.

Technical data

Supply voltage 

 

24 V AC ±15%, 50/60 Hz

Power consumption 

3 VA

Ambient temperature 

0...50°C

 

Ambient humidity   

Max. 90% RH

Storage temperature 

-20...70°C

Display 

 

Numeric / graphic. Background 

 

 

 

illumination.

Inputs/outputs 

 

Refer to connection illustrations and 

 

 

 

table below

Terminal blocks   

Disconnectable, so-called lift type for    

 

 

cable cross-section max 2.5 mm

2

Protection class   

IP20

Material, casing   

Polycarbonate, PC

Weight 

 

215 g incl. terminal blocks

 

Dimensions 

 

122 x 120 x 64 mm (WxHxD incl. terminals,  

 

 

fixed installation)

 

Pollution degree   

2

Temperature settings

Temperature, supply air  

-20..+60, 20...100, 60...140°C

 

Setpoints 

 

-18...+60, 22...100, 62...140°C

External setpoint   

0...40°C

 

Neutral zone  

 

0...10°C

 

P-band 

 

0…99°C

 

I-time 

 

0…990 s

 

Min. limit damper   

0…99

Other settings

Setpoint values

 

   CO

2

 

 

0...100% of max set value on UI1

 

   General (GEN)   

0...100% of max set value on UI1

 

   Pressure (Pa)   

0...100% of max set value on UI1

Scaling of UI1

 

 

0...10 V DC in

 

   CO

2

 

 

10...9900 ppm

   General 

 

0...100%

   Pressure 

 

100 Pa...2500 kPa   

 

 

Neutral zone

 

 

12.5% of max

P-band

  

 

   CO

2

 

 

0...100% of UI1

 

   General (RH) 

 

0...100% of UI1

 

   Pressure (Pa)   

0...300% of UI1

 

I-time

 

 

0…990 s

Control setting 5 

Outdoor compens. start 

-20…+60°C

Setpoint pressure at

 

-20°C outdoor temp. 

0 Pa...2500 kPa

Installation

OP5U must be mounted in a DIN-standard casing (minimum 7 
modules) or in a cabinet, either on a DIN-rail or, using the two screw-
pockets provided, by being screwed to any suitable flat surface in the 
cabinet. The controller can also be mounted in a cabinet door or other 
control panel, using a suitable front-mounting kit.
The controller must be connected to a 24 V AC safety insulating 
transformer providing mains insulation.

Follow table 1 below for connection. 

Table 1. I/O connection terminals. Terminals 2, 20 and 50 are internally con-
nected.

Terminal Designation Operation

1

G

Supply voltage 24 V AC

2

G0

3

20

AGnd

Ref. for AO1 and AO2

21

AO1

0...10 V DC Output

22

AO2

0...10 V DC Output

41

DI+

Reference for DI1

42

DI1

Digital input

43

UI+

Reference for UI1 digital mode

44

UI1

0...10 V DC or Digital input

50

AGnd

Ref. for AI1 and UI1 analogue

51

AI1

PT1000 temp. sensor input

52

SPI

Input PT1000 setpoint device

 

Digital inputs DI and UI are only intended to be used with 

a potential-free contact or switch.

 

If the Optigo OP5U and active 

sensors and actuators connected to it share transformer, it is 
essential that the same transformer-pole is used as reference for 
all the equipment. Failure to do so will prevent the equipment from 
functioning as intended and may also lead to damages.
For best protection against disturbances, a shielded twisted-pair cable 
should be used for wiring the sensors. Ground the shield at one end.
The protection provided by the equipment may be impaired by im

-

proper use.

6732I

 

SEPT

 12

EN

Содержание Optigo OP5U

Страница 1: ...100 Pa 2500 kPa Neutral zone 12 5 of max P band CO2 0 100 of UI1 General RH 0 100 of UI1 Pressure Pa 0 300 of UI1 I time 0 990 s Control setting 5 Outdoor compens start 20 60 C Setpoint pressure at 20...

Страница 2: ...trolling the output signals on AO1 and AO2 AO1 is used for positive control AO2 for negative control A single PI control loop is used If you want to max limit the humidity connect a HMH humidistat in...

Страница 3: ...nfirm the change by clicking on the knob To exit the 10 second level go to menu level 12 Menu OK and click on the encoder knob You will be returned to the basic level see below There is also a time ou...

Страница 4: ...den Tel 46 31 720 02 00 Fax 46 31 720 02 50 www regin se info regin se i Gelieve deze instructie te lezen alvorens over te gaan tot installatie en aansluiting van het toestel NL INSTRUCTIE OPTIGO OP5U...

Страница 5: ...voor de bekabeling van de sondes Sluit de aarding aan De bescherming van het materiaal kan worden tenietgedaan door een verkeerd gebruik Regelingsmodi 1 De temperatuur ter hoogte van de sonde wordt o...

Страница 6: ...onfiguratieniveau Configuratieniveau 10 seconden Er zijn 2 toegangsniveaus het configuratieniveau 10 seconden en het basisniveau Druk op de knop gedurende 10 seconden vanaf het beginscherm om toegang...

Страница 7: ...ut AO2 voor configuratie op AO2 enkel regelingsmodus 1 Symbool voor configuratie op AO1 enkel regelingsmodus 1 Input 0 10 V actief Temperatuurregeling Externe compensatie actief Het menu bevat paramet...

Страница 8: ...option Le r gulateur doit tre connect un transformateur d isolation de s cu rit 24 V AC qui assure l isolation principale Voir le tableau 1 pour les raccordements Table 1 Borniers de raccordement des...

Страница 9: ...sortie AO1 Une seule boucle PI est utili s e Le signal AO1 invers est re u de AO2 24 V AC Signal de d marrage transmetteur de pression Variateur de fr quence Pa G G0 DI DI1 UI UI1 AGND AI1 SPI 1 2 3 4...

Страница 10: ...ements dans la m moire flash coupez l alimentation de l Optigo alors que vous trouvez toujours dans le mode configuration Le r gulateur revient alors automatiquement aux derni res valeurs sauvegard es...

Страница 11: ...Ein Ausg nge und kann so konfiguriert werden dass er Temperatur CO2 relative Feuchte oder Druck regelt S mtliche Einstel lungen und Konfigurationen werden ber das Display und den Dr ck drehknopf direk...

Страница 12: ...rt wird durch die Ansteuerung des Ausgangssignals AO1 auf dem Sollwert gehalten Ein PI Regelkreis wird verwendet Eine min max Begrenzung des Ausgangs ist m glich 24 V AC Klappe Frequenz umrichter CO2...

Страница 13: ...der Regelmodus ausgew hlt und das Symbol Men mit ver nder baren Werten blinkt nicht mehr kann durch Drehen des Knopfes zwischen den Men ebenen gewechselt werden In einigen F llen werden durch bestimmt...

Страница 14: ...Uhrzeigersinn angezeigt Displaysymbole Konfigurationsmen Men nummer S ulendiagramm Ausgangsleistung AO1 S ulendiagramm Ausgangsleistung AO2 Graphisches Ausgangssignal AO2 nur Regelmodus 1 Graphisches...

Отзывы: