Regin HTRT5W Скачать руководство пользователя страница 1

EN

INSTRUCTION

HTRT5W

IN20016 REV. A, 2019-05-28

C

Caauuttiioonn!! Read and understand the instruction before using the product.

Technical data

Power supply

AA 1.5 V L91 battery x 2

Battery life

10 years

1

Frequency

868 MHz

Protection class

IP30

Measuring range, temperature

-10…+50 °C

Measuring range, humidity

0…100 % RH

Accuracy, temperature

±0.2 K

Accuracy, humidity

±2 %

Dimensions (WxHxD)

86 x 86 x 30 mm

1. Battery life is calculated with 720 wake-ups and 120 value updates per day.

Installation

1. Open the cover by pressing the locking tab carefully with a

screwdriver.

2. Insert two 1.5 V L91 lithium batteries in the battery compartments.

3. Pair the receiver and sensor if necessary. See description in the

variable list for the receiver RCW-M32.

4. Ensure that the receiver and sensor are paired by pressing the

Test

button

while studying the LED indications. See

Handling

.

5. Make a signal strength test as described under

Handling

.

6. Mount the sensor on a wall using the mounting holes. For optimal

monitoring, the sensor should be mounted in an open space with
good air circulation, and at a height of 1.2 to 1.4 meters.

7. Snap on the cover.

Number

Description

1

Battery compartments

2

Mounting holes

3

Test button

4

LED light

5

DIP switches

Wiring

DIP switch

Description

1

Frequency
OFF = 868.6375 MHz (used in Europe)
ON = 868.2375 MHz (used in China)

2

Not used

Settings

The temperature and humidity are measured at an adjustable time
interval called

wake up time

. If a measured value changes more than the

specified limit it will send a signal to the receiver. The sensor will always
send a signal to the receiver every 95 - 110 minutes. If the receiver does
not receive a signal from the sensor within a specified time interval it will
indicate

out of signal

.

For default time values, limits and how to modify them see the variable
list for the receiver.

N

No

ottee!! Changing the time intervals will influence the battery life time.

Handling

Signal strength test

Test the signal strength to optimise the installation:

1. Push the

Test button

(approx. 7 s) on a paired sensor until the LED

first shines with a solid light. After that the LED behaviour will
depend on the connection quality.

– Long flash with short pause = Very good connection

(-20…-50 dB)

– Short flash with short pause = Good connection (-50…-90 dB)

– Flash with long pause (1 s) = Bad connection (< -90 dB)

– No LED = Out of range or time-out for test sequence

2. Test in different locations to optimise the connection before

installing the unit.

The test sequence lasts for 1 minute.

LED indications

– 3 flashes (when

Test button

is pressed): The sensor is not paired with

the receiver.

– Flashing (when

Test button

is pressed): The sensor is paired with the

receiver.

– Flash every 4 seconds: Batteries need to be replaced.

Function

The temperature and humidity sensor is designed to work together with
Regin's wireless receiver RCW-M32 with Modbus communication.

This product carries the CE-mark. More information is available at
www.regincontrols.com.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]

2

3

4

1

+

-

+

-

2

5

ON

1

2

HTRT5W

1

Отзывы: