Humidity and temperature transmitters

HTRT10A-420 and HTRT10AD-420 are room transmitters for  

measurement of humidity and temperature.

Installation

The transmitter should be mounted in a location with good air circula-
tion where it can be expected to give a representative reading. It may 
be mounted on a wall-box or directly on the wall. 

To remove the front cover, press the locking tounge in the lower part 

of the casing using a 3 mm flat-blade screwdriver (see arrow in the 
figure below). Press and twist the screwdriver and at the same time 

pull the bottom part of the front outwards. When the bottom end of 
the front is free from the bottom part of the casing, slide the cover to-
wards the top of the casing to free the hooks holding the upper edge 
of the front cover.
To select the temperature scale °C or °F, set dip-switch 4 as shown in 

the figure below.

Wiring

power supply

28 V > U

v

 > 11 + 0.02 x R

L

R

L

 ≤ 500 Ohm

Wiring for HTRT10A(D)-420

Technical data

Output signal

4...20 mA (T=0…50°C, RH= 0…100% r.h.)

Supply voltage

Max. 28 V DC, min. 11+(0.02xR

L

) V DC

Power consumption

1.2 W

DC power supply

Min. 2W

Temperature range

0...50°C

Accuracy, temperature

±0.5°C at 20 °C

Humidity, working range

10...90 % RH

Accuracy, humidity

±3 % RH at 20 °C

Protection class

IP30

Dimensions

100 x 85 x 30.5 mm

This product carries the CE mark.  
For more information, see www.regincontrols.com.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden 

Tel: +46 31 720 02 00, Fax: +46 31 720 02 50

 

www.regincontrols.com, [email protected]