Read this instruction before installation 

and wiring of the product

ED-TCV

1

ED-TCV

Graphic touch display

ED-TCV is an external display for connection to a Corrigo ventilation 
with two ports. ED-TCV permits starting and stopping an air handling 
unit, setting extended running time, adjusting setpoints and viewing 
alarms. The display is connected to port 2 on the Corrigo and can be 
used in combination with expansion units.

Technical data

Protection class   

IP30

Power supply 

 

24 V DC via terminal 4 (+C) and G0 on   

 

 

 

the Corrigo. 

Power consumption 

50 mA

Connection cable   

Twisted-pair, 0.25 mm

2

Display  

 

TFT-LCD (resistive)

Backlight 

 

LED (backlit)

Language 

 

Swedish or English, set automatically  

 

 

 

depending on the language used in the   

     Corrigo
Aspect ratio 

 

4:3

Resolution 

 

320 x 240

Dimensions (WxHxD) 

120 x 90 x 27 mm

Communication  

EXOline

Corrigo software version 

3.2 or later

Installation

ED-TCV is mounted on a wall using the supplied wall bracket. It can also 
be mounted on a device box (cc 60 mm). The display can be removed 
from the bracket if necessary.

Wiring

ED-TCV is connected to the A and B terminals on the communication port 

configured for an external display. Power is supplied from +C (terminal 4) 
and G0 (terminal 2) on the Corrigo. See the figure below.

(4) +C
(2) G0

A

B

    Figure 1. Wiring

Configuration via E tool

©

(The following settings can not be made in the display, only via  

E tool

©

.)

E tool

©

 is used to select what to show on the start page of the touch dis-

play.  It is possible to select one of the following alternatives:

•  The clock
•  Room temperature connected to the Corrigo
•  Room temperature from the temperature sensor of the display
•  Extract air temperature
•  Current supply air setpoint
•  Current room setpoint
•  Current extract air setpoint

E tool

©

 is also used to make the following settings:

•  Whether setpoint adjustment via the ED-TCV should be permit-

ted (Yes/No)

•  Permitted max./min. adjustment
•  The current setpoint adjustment

Operation

The following information is displayed on the ED-TCV start page:

The main menu

Service number

AHU  
status

Ventilation

Setpoint 
increase and 
decrease

What to 
display here 
is selected 
using E tool

©

Figure 2. The start page

The main menu permits setting and reading different values:

Alarms

System info

Temperature

Ventilation

Settings

Figure 3. The main menu