background image

INSTRUCTION

 

i

i

Read this instruction before installation 

and wiring of the product

Display/button-function repeater

E0R-3 and E0R230K-3 are display/button-function repeaters. They 
can be used when there is need for a remote display and the distance 
between controller and display/buttons is so great that it prevents  
direct connection of the display unit. E3-DSP can be used as a dis-
play unit. 
Using the RS485 port it can address up to 6 connected Corrigo units.  
The repeater can also be used in a network with EXOcompact.

Technical data

The maximum total length for the communication line is 1200 m.

Wiring

Communication line

G G0

1 2 3

E0R-3 / E0R230K-3

B A N E

50 51 52

53

*24 V AC (E0R-3) 

230 V AC (E0R230K-3)

External display

Supply voltage*

E3-DSP

Wiring of the RS485 communication line

Use shielded twisted pair cable. Connect A to A and B to B. Connect the 
shield to N.

Communication line (max. 1200 m)

B A N E

50 51 52 53

B A N E

B A N E

Corrigo controller

Corrigo controller

E0R-3 / E0R230K-3

50 51 52 53

50 51 52 53

Configuration

On power-up, E0R...-3 will display the Base Display.
 

E0R-3

07:04:17   14:38

Select Controller

with down arrow

To set the date and time, click on the OK button to log in. Next, press OK 
again. The default access code is 1111. Use the up and down arrow to 

set the relevant number. Press the right arrow to switch fields. Once the 

setting has been changed, press OK.
Click the down button to access the controller selection list where you 
choose which of the connected controllers you wish to communicate with, 
the Settings menu where you set the addresses to the connected control-
lers and the Access rights menu where you can administer access rights.

Controller 1

Controller 2

Controller 3

Controller 4

Controller 5

Controller 6

Settings

Access rights 

Settings

Click down-button until you reach the menu Settings.
Click right-button.

Controller 1

PLA: 254

ELA: 30 

Here you can change the text that is displayed in the controller selec-
tion list and set the addresses for the connected controllers. 
The text in the top line can be changed to any suitable text to identify 
the controller. Use up-button and down-button to scroll through the 
available characters. Use right-button and left-button to move side-
ways in the text. To store the revised text, click OK. The revised text 
will be displayed in the controller selection list. 

The connected controllers are identified by their ELA and PLA add

-

resses. Each connected unit must be set to a unique address. See 
the Corrigo manual for information on how to change the controller 
address.
If less than 6 units are connected leave the unused controller addres-

ses at PLA: 0 and ELA: 0. You can however still change the text if you 

wish, for example to Not used.

For instance, if you have three controllers that you wish to monitor, 
called Riverside Building Heating 1, Riverside Building Heating 2 and 

Riverside Building Ventilation, the menu list could look like this:

Riverside Bd Heat 1

Riverside Bd Heat 2

Riverside Bd Vent

Not used

Not used

Not used

Settings

Access rights

E0R-3 / E0R230K-3

11

184B

 

FEB 20

EN

1