INSTRUCTION

DTB...

IN20009 REV. G, 2021-05-17

C

Caauuttiioonn!! Read and understand the instruction before using the product.

C

Caauuttiioonn!! Ensure that the installation complies with local safety

regulations.

C

Caauuttiioonn!! Before installation or maintenance, the power supply should first

be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.

Technical Data

Supply voltage

24 V AC/DC (18…30 V AC/DC)

Output signal

0…10 V / 4…20 mA

Display

Yes

Display type

LED, 4 digits

Sensor element, pressure

Piezo-resistive pressure sensor

Accuracy, pressure

±1 % full scale, min. ±1 Pa

Power consumption

< 6 W

Load impedance, 4...20 mA

20…500 Ω

Load impedance, 0...10 V

≥ 1 kΩ

Protection class

IP54

Ambient humidity

0…95 % RH (non-condensing)

Ambient temperature

-10…+50 °C

Response time

100 ms / 1 s

Storage temperature

-10…+50 °C

Media

Air and non-corrosive gases

Zero-point adjustment

Automatic

Cable connection

Screw terminals max. 1.5 mm²

Cable gland

M16

Pressure connection

Connection pipes for 6 mm tube

Mounting

Wall

Accessories, included

Two pressure outlets (cut 60°) and 2 m
plastic tube. Art. no.: ANS-1

Dimensions, external (WxHxD)

85 x 85 x 58 mm

Models

Article

Measuring range,
pressure

Max. overload pressure

DTB5/5

-50…+50 Pa

60 kPa

DTB10/10

-100…+100 Pa

60 kPa

DTB125

0…100 Pa / 0…250 Pa

60 kPa

DTB510

0…500 Pa / 0…1000 Pa

75 kPa

Installation

The unit can be mounted in any position as the automatic calibration
eliminates any position error.

Wiring

Figure 1 Terminal assignments (L= Load)

Terminal

Description

4

Not used

3

Ground GND

2

Output signal

1

Supply voltage

Settings

Jumpers are available for changing the output signal and its response
time as well as selecting the pressure range (on models where this is
possible).

Number

Function

Jumper on

Jumper off

1

Pressure range

Low

High

2

Response time

Slow

Fast

3

Not used

-

-

4

Output signal

0...10 V

4...20 mA

Handling

The transmitter regularly performs automatic zero-point adjustments,
which means that no manual calibration is needed.

1

4

3

2

L

1

2

3

4

DTB...

1