Exchanger de-icing 

 

This menu is shown if exchanger de-icing has been 
configured. If the temperature at the de-icing sensor 
drops below the setpoint value, the de-icing function is 
started. It is stopped when the temperature has risen 
above the setpoint plus the set differential. 

 

Heat exchanger efficiency monitoring 

 

The function calculates the heat exchanger temperature efficiency in % when the output 
signal to the exchanger is higher than 5 % and the outdoor temperature is lower than 10°C. 
The function requires an extract air sensor, an exhaust air sensor and an outdoor sensor or an 
efficiency sensor, extract air sensor and outdoor sensor. 

When the control signal is lower than 5% or the outdoor temperature is higher than 10°C the 
display will show 0%.  

Recirculation 

The first of the three below menus can be found under 

Configuration

 in the controller. The 

fourth menu is located under 

Temperature

 

Recirculation is a function for mixing the air in the room using 
the supply air fan. The function can be used even when there is 
no heating or cooling demand. When using recirculation control, 
the extract air fan stops and a recirculation damper opens which 
allows the air to circulate through the unit. 

 

 

 

 

 

It is selectable whether or not the extract air fan should 
run during recirculation. 

Deicing exchanger 
    Actual: 11.2°C 
      Setp: -3.0°C 
Hysteresis:  1.0°C 

Efficiency exch 
Actual: 93% 
Output exchanger 
Actual: 100% 

Enable temp  
control when 
recirculation 

Heat and cooling 

 

Constant or 
setpoint offset 
when recirculation: 
Constant 

EAF running during 
recirculation: No 
 

 

Offset SAF when 
frequency control 
and recirculation: 
 0.0 Pa 

Содержание Corrigo

Страница 1: ...Corrigo user guide Ventilation application Copyright AB Regin Sweden 2014...

Страница 2: ...ventilation application available in Swedish English German and French Manual E tool Manual on how to configure the controllers using the PC software E tool available in Swedish English German and Fr...

Страница 3: ...e controller is based on a supply air PI controller for heating control with a pre programmed set of control modes A number of different control functions as well as analogue and digital input and out...

Страница 4: ...endent or flow dependent Humidity control Either humidification or dehumidification or both humidification and dehumidification can be used Timer control For starting and stopping the unit Up to 5 tim...

Страница 5: ...in order to return the cool extract air Recirculation control Recirculation of air using a supply air fan and optionally extract air fan and a recirculation damper with or without temperature control...

Страница 6: ...ns and LEDs ARROW UP Move up a row in the menu Increase parameter value ALARM Press to view the alarm list ARROW DOWN Move down a row in the menu Decrease parameter value CLEAR Reset Abort a parameter...

Страница 7: ...Corrigo ventilation user guide revision FFel Anv nd fliken Start om du vill till mpa heading 1 f r texten som ska visas h r 7...

Страница 8: ...mber of menus and submenus Running mode Here you can view and set the unit s running mode as well as view selected control functions and alarm events Temperature Air control and Humidity control Here...

Страница 9: ...In numbers containing several digits you can move between the digits using the ARROW LEFT RIGHT buttons When the desired value is displayed press OK If there are further settable values displayed the...

Страница 10: ...cooling demand in the room the unit will start and the temperature will be adjusted The fire function determines the settings for the fire dampers and the unit s running mode when a fire alarm is acti...

Страница 11: ...inputs and outputs These are read only menus No changes can be made here Universal inputs can be configured as either analogue or digital inputs Analogue inputs and digital outputs are shown here as e...

Страница 12: ...emperature if a outdoor sensor has been configured This is a read only menu No settings can be made here Submenus Setpoint In control modes Supply air control Room control and Supply air control Extra...

Страница 13: ...uses the average temperature of the two sensors Setpoint Cascaded extract air temperature control In control mode Supply air control Extract air control the setpoint is used when cascaded extract air...

Страница 14: ...oling will run if support control is configured the running mode is Off timer control OFF and not in extended running and if conditions call for support control Minimum run time is settable 0 to 720 m...

Страница 15: ...When the control signal is lower than 5 or the outdoor temperature is higher than 10 C the display will show 0 Recirculation The first of the three below menus can be found under Configuration in the...

Страница 16: ...ge this offset value here Extra controller unit An independent temperature control circuit for control of for example after heaters The circuit can be configured to either heating or cooling Enthalpy...

Страница 17: ...u extra compensation A temperature dependent compensation similar to the one above but with selectable temperature source Flow control SAF there are also corresponding menus for EAF Setpoint Flow cont...

Страница 18: ...or compensation An outdoor temperature dependent compensation of the pressure setpoint value can be added The compensation can be set for either the supply air fan alone or for both fans Submenu extra...

Страница 19: ...e SAF or EAF is operated as a slave This function is also available featuring flow control 25 C 0 Controller output comp if cooling 0 at R U S 0 100 at R U S 0 Controller output comp if heating 0 at R...

Страница 20: ...the air quality as measured by a CO2 sensor CO2 can be set to function either on Y2 Y4 or both Act comp 0 Pa Comp sens Roomtp 1 15 C 0 Pa 20 C 0 Pa 25 C 0 Pa Controller output comp if cooling 0 at R...

Страница 21: ...to 365 days Holiday schedules take precedence over other schedules Each day has up to two individual running periods For two speed fans and pressure controlled fans there are daily individual schedul...

Страница 22: ...n be used to force the unit to start although the timer says the running mode should be Off For 2 speed fans and pressure flow controlled fans inputs for normal speed and reduced speed can normally be...

Страница 23: ...bmenus Configuration In and Outputs and Configuration System Admin level gives full read write access to all settings and parameters in all menus Repeatedly press down arrow when the start up display...

Страница 24: ...e basic no log on level Automatic logoff If the access level is Operator Service or Admin the user will automatically be logged off to Normal after a settable time of inactivity The time is settable C...

Страница 25: ...are then given the choice of acknowledging the alarm or blocking the alarm Acknowledged alarms will remain on the alarm list until the alarm input signal resets Blocked alarms remain on the alarm lis...

Страница 26: ...an internal battery to ensure the operation of the memory and real time clock in the event of a power failure When the alarm Internal Battery is activated and the battery LED lights up red the batter...

Страница 27: ...w 3 H Holidays 22 Humidity control 20 Setpoint 20 I Indicators 25 Information screen 24 Inputs Outputs 10 L Language change 25 LEDs 25 Log off 23 Log on 22 M Menus 7 N Navigating the menus 7 O Other f...

Страница 28: ......

Отзывы: