CONFIGUR
ATION -
Corrigo L10
A
B
C
D
.
E
F
G
H
.
I
J
K
Configuration code
.
.
A Control function
0. Supply air control
0
1. Supply air control with outdoor temperature compensation
1
2. Room control with cascaded supply air temperature control
2
3. Room control with min/max limiting of supply air temp.
3
4. Room control, single sensor
4
5. Supply air control/Room control. Outdoor temp dependent
5
B
Outpus sequences Y1, Y2, Y3
0. Heating / - / -
0
1. Heating / Cooling / -
1
2. Heating / Dampers / -
2
3. Heating / Dampers / Cooling
3
4. Heating / Plate exchanger / -
4
5. Heating / Plate exchanger / Cooling
5
6. Heating / Rotating exchanger / -
6
7. Heating / Rotating exchanger / Cooling
7
8. Cooling
8
C Heater type
0. Water heater
0
1. Electric heater
1
D Frost protection
0. Not active
0
1. Active
on Y1
1
2. Active on Y1 with automatic alarm reset
2
EShutdown mode
0. No
0
1.
Yes
1
F Pump stop
0. No
0
1.
Yes
1
G Function AI1
0. Outdoor temperature sensor
0
1. External setpoint device
1
H Function DI1
0. Fan alarm
0
1. Fan indication
1
I Function DI3
0.Not active
0
1. Timer
1
2. Pushbutton
2
3. Alarm,
smoke detector
3
4. External alarm
4
J Function DI4
0. Not active
0
1. Freeze-up protection plate-exchanger
1
2. Alarm,
rotating exchanger
2
3. Alarm,
chiller
3
4. Alarm,
smoke detector
4
5. External alarm
5
K Function DO1, DO2
0. -- / --
0
1. DX1 / --
1
2. -- / Frost interlock
2
3. DX1 / Frost interlock
3
4. DX1 / DX2 in sequence
4
5. DX1 / DX2 binary
5
Numbers in bold indicate factory settings