Regin Corrigo C10-LON Скачать руководство пользователя страница 6

2418C JAN 00  1.5.5

CORRIGO C10-LON

INSTRUCTION

Damper 1

90°

DI6

Terminal 22

Damper 2

Damper 3

Damper ..

DO6

DI6

High

High

Low

Low

max 5

minutes

max 5

minutes

DO6/DI6

The output/input pair DO6/DI6 can be configured for
different functions.
When Corrigo is used with relay unit RM6H-24/D or if
external switches for manual fan control are used, fire
damper exercising cannot be done through the Corrigo.
DO6/DI6 are then used for other purposes

0. Frost alarm / External alarm

DO6 is used to stop the fans in the event of frost risk.
DO6 is normally closed but will open on a frost alarm on
AI8. DI6 is used as input for external alarm signals.

1. Frost alarm / Auto position

DO6 is used to stop the fans in the event of frost risk.
DO6 is normally closed but will open on a frost alarm on
AI8. DI6 is used to activate an alarm if any of the manual
switches on RM6H-24/D is left in other position than
”Auto” for longer than 15 seconds.

2. Fire damper exercising

Wire all the damper end-position switches to DI6
according to the figure above. The contacts must close
when the actuator is at either end position.
At a preset time DO6 will activate all the dampers. DI6
must then be deactivated within 5 minutes, indicating
thet the dampers have left their normal end position , or
an alarm will be activated. When DI6 has been
deactivated it must be activated again within 5 minutes
indicating that the dampers have reached the other end
point. When DI6 is activated the output DO6 is
deactivated and the dampers begin to return to the start
position. To avoid an alarm output DI6 must once again
be deactivated within 5 minutes and then activated
again within 5 minutes indicating that the dampers are
back in their original position.

Factory settings

Configuration

Factory settins

Config.code 1

0011.1110.0000

Config.code 2

0100.010

A. CONTROL FUNCTION

0 Supply air temp control

B. HEATER TYPE

0 Water heater

C. SEQUENCE Y1

1 Heating

D. SEQUENCE Y2

1 Plate exchanger

E. SEQUENCE Y3

1 Cooling

F. FROST PROTECTION

1 Y1

G. SHUTDOWN CONTROL

1 Yes

H. PUMP STOP

0 No

I. EFFICIENCY MONITORING.

0 No

J. DX-COOLING

0 No

K. COOLING RECOVERY

0 No

L. FREE COOLING

0 No

M. FUNCT. DI6/DO6

0 Ext. alarm+frost prot.

N. FIRE ALARM

1 SF + EF Stop

O. FUNCTION DI7/8

0 ---

P. TWO-SPEED FANS

0 No

Q. EXTERNAL SETPOINT

0 No

R. DAYLIGHT SAVING TIME

1 Yes

S. FUNCTION NOT AVAILABLE 0
T. FACTORY SETTING

No

Control Temp

Setpoint

20.0°C

P-Band / I-time / Neutral zone

20K / 60s / 2K

INSTRUCTION

6

Storage of programmed parameters

All settings are stored in non-volatile memory so the unit
does not need reprogramming after a long power
failiure.
The clock has a power reserve of at least 24 hours.
After longer power failiures the clock will need resetting
but not the programmed scheduler parameters.
The alarm list will be erased at a power failiure.

EMC emissions & immunity standards:

This product conforms with the requirements of Euro-
pean EMC standards CENELEC EN 50081-1 and EN
50082-1 and carries the CE mark.

Содержание Corrigo C10-LON

Страница 1: ...osen AI8 is depending on setting used for 1 Frost protection sensor for applications with water heated heater 2 High temperature limiting switch for applications with electrical heater When used for high temperature limiting switch it must be connected to a free contact closing on alarm Fan supervision supply air fan exhaust air fan AI1 AI2 Connect AI1 and AI2 to free contacts that open when the f...

Страница 2: ...he Trunk of the menu tree contains the following menues Logon Configuration Only shown in level 3 Control temp ï Starting point Running mode AI Analogue in DI Digital in AO Analogue out DO Digital out Scheduler Alarm settings Not shown in level 0 Settings Only shown in level 2 and 3 During normal running when the buttons are not in use a series of menu pages is shown The display alternates between...

Страница 3: ...with outdoor tempera ture compensation 2 Room temperature control with cascade control of the supply air temperature 3 Room temperature control with minimum maximum limiting of the supply air temperature 4 Room temperature control without supply air tempera ture sensor 5 Outdoor temperature controlled change over between constant supply air temperature control with outdoor temperature compensation...

Страница 4: ...ng engineer When the configuration is terminated by leaving the configuration branch by pressin Esc an automatic restart with the new parameters will take place The login level will be reset to 0 Configuration quick method The top two menu pages on the configuration branch show two configuration codes Configuration code 1 and Configuration code 2 Each position in the code represents in order the v...

Страница 5: ... none of the periods contains the day H the system will be shut down on holidays 5 Holiday periods Level 2 and up 2 periods comprising any number of days may be programmed Running time during a holiday is set by programming the day H into one of the three scheduler periods If none of the periods contains the day H the system will be shut down on holidays Alarm settings Here all settings for the al...

Страница 6: ...cating that the dampers have reached the other end point When DI6 is activated the output DO6 is deactivated and the dampers begin to return to the start position To avoid an alarm output DI6 must once again be deactivated within 5 minutes and then activated again within 5 minutes indicating that the dampers are back in their original position Factory settings Configuration Factory settins Config ...

Страница 7: ...Y1 0 Not active 0 1 Heating 1 2 Damper 2 3 Cooling 3 D Output Y2 0 Not active 0 1 Plate heat exchanger 1 2 Rotating heat exchanger 2 3 Liquid connected heat exchanger 3 4 Damper 4 5 Heating 5 6 Cooling 6 E Output Y3 0 Not active 0 1 Cooling 1 2 Heating 2 F Frost protection Water heating only 0 Not active 0 1 Active on Y1 1 2 Active on Y2 2 3 Active on Y1 with automatic alarm reset 3 4 Active on Y2...

Страница 8: ...rm only 0 1 Alarm supply air and exhaust air fans stop 1 2 Alarm supply air fan stops 2 3 Alarm exhaust air fan stops 3 O Function DI7 DI8 0 Not active 0 1 Pushbutton 1 2 Timer 2 P 2 speed fans Can not be combined with DX cooling 0 No 0 1 Yes 1 Q External setpoint 0 No 0 1 Yes 1 R Daylight saving time 0 No 0 1 Yes 1 S This function is not available for Corrigo C10 The code must always be set to 0 ...

Страница 9: ...egrenzungsfühler im Wärmetauscherkreis 3 Externer Sollwert Eingang für Sollwertsignal verwendet Fühler Diese Funktion sind deshalb gegenseitig auszu schließen Nur eine der Funktionen kann gewählt werden AI8 wird in Abhängigkeit von der Einstellung entweder für Frostschutz in Applikationen mit Wasserbatterie Überhitzungsschutz in Applikationen mit Elektroheizung Wenn er als Eingang für den Überhitz...

Страница 10: ...nd Corrigo an die Spannung angeschlossen wird ermöglicht Um die Sprache zu ändern nochmals auf die Taste drücken Ein Anzeige wird neben der aktuellen Sprache angezeigt Zum Ändern é oder ê drücken Wenn die gewünschte Sprache gewählt ist OK drücken Nochmals OK drücken um wieder in das normale System zu gelangen Jede Information die im Fenster angezeigt werden kann ist in Abschnitten in einen Eingabe...

Отзывы: