Regin Corrigo C10-LON Скачать руководство пользователя страница 5

2418C JAN 00  1.5.5

CORRIGO C10-LON

INSTRUCTION

Diode

Text

Function yellow

Function red

1

SF

Supply fan on

SF error

2

EF

Exhaust fan on

EF error

3

Pump

Pump on

Pump error

4

Y1

Output Y1

Over temp limit

Heating

or frost protection

5

Y2

Output Y2

        Alarm

Exch

Blinks on defrost

Heat exchanger

6

Y3 Cool Output Y3

Alarm chiller

7

Filter

---

Filter alarm

Alarm

--

---

Alarm active

Running mode

In this menu the running mode for the system can be
checked and also set to manual control.
To the left the display shows Auto/Manual and to the right
the present running mode.
The modes AUTO/ON/OFF can be set.
In AUTO the running mode is set by the scheduler
program or by signals on DI7/DI8.
If the controller is configured for two-speed fans the
modes AUTO/LOW/HIGH/OFF can be set.
The menu is available from level 1 and up.

AI Analogue inputs

Displays current values for AI1...AI8.
The displayed sensor temperature can be adjusted
by ±2K. Available for level 3.
Maximum and minimum temperatures since last reset can
be shown. Activated in menu ”Settings”.

DI Digital inputs

Displays current values for inputs DI1...DI8.

AO Analogue outputs

Shows current values for AO1...AO3.
The outputs can be manually set. From level 1 and up.
If an output is not reset to AOTO within 15 seconds an
alarm is activated.

DO Digital outputs

Shows current values for DO1...DO7.
The outputs can be manually set. From level 1 and up.
If an output is not reset to AUTO within 15 seconds an
alarm is activated.

Scheduler

The Corrigo has a year-base clock. This means that a
week-schedule, individual holidays and holiday periods
for a full year can be set.
The clock has at least 24 hours running reserve.

1. Clock

Here weekday, date and time are set. Level 1 and up.

2. Scheduler period 1, 2, 3.

Setting of running periods. Level 2 and up.
Corrigo has 3 scheduler periods so that separate
running times can be set for, for example, weekdays,
Saturdays and Sundays/holidays. In each period, mark
the days and time interval in which the system should
be in normal running mode. Use the arrow keys to
select/deselect days in the period. End each selection
with 

OK

.

The day H is used if the system is to have running time
during holidays or holiday periods.

3. Reduced 1, 2, 3.

3 periods for running with reduced airflow.
Should not overlap periods set for normal running.
Should periods overlap Corrigo will choose normal
running before reduced.

4. Dates for holidays. Level 2 and up.

A total of 10 individual holidays can be set. Running
time during a holiday is set by programming the day
H into one of the three scheduler periods. If none of
the periods contains the day H the system will be shut
down on holidays.

5. Holiday periods. Level 2 and up.

2 periods comprising any number of days may be
programmed. Running time during a holiday is set by
programming the day H into one of the three
scheduler periods. If none of the periods contains the
day H the system will be shut down on holidays.

Alarm settings

Here all settings for the alarm system are set.

1. Sensor alarm

Should the actual temperature differ from the setpoint
by more than the set value an alarm will be activated
after a set time.

2 Outdoor temperature range within which sensor alarm

is permitted.
To prevent alarms when the outdoor temperature
leads to conditions beyond the system capacity. (For
example at temperatures higher than the setpoint in
systems without cooling).

3 Alarm delay for the supply air fan.

Startup alarm supression time.

4 Alarm delay for the exhaust air fan.

Startup alarm supression time.

5 Blocking of the alarm output relay.

The alarm output relay can be blocked so that alarms
only will be forwarded during the set time. Outside the
set period only frost alarm, high temperature limit
alarm and fire alarm will activate the alarm relay.
Other alarms will be blocked. All alarms will however,
at all times be registered in the internal alarm list and
indicated by the red flashing alarm diod. The alarm
list menues function as normal.

Settings 

Only shown to levels 2 and 3

A number of settings that generally only are set at
commissioning.
1

Setpoint frost protection system

2

Setpoint Shutdown control

3

Pump stop. Minimum outdoor temp and delay time

4

Supply fan run on time for cooling electric heater

5

100% on startup

6

Extension of running time when using pushbutton

7

P-band for Y2, Y3. Factor of P-band for Y1

8

Min fresh air when using mixing damper on Y2

9

Free cooling. Min outdoor temp and min temperature
difference indoor/outdoor

10 Free cooling. Room temperature setpoint.
11 Cooling recovery. Differential outdoor/return temp
12 DX cooling. Minimum on and off times
13 Lowered minimum limit by DX cooling
14 Time for fire damper exercise
15 Exchanger min.temp and P-band for liquid connected

exchanger

16 Force low speed on fans on low outdoor temerature
17 Show Minimum/Maximum values for AI3...AI8

LED’s

The LEDs are connected to the functions of certain in-
and outputs. Normal running indication is yellow. A red
LED signifies an error. The text strip can easily be
changed to reflect various configurations

INSTRUCTION

5

ð

6. Stop unit on alarm from rotating exchanger

A rotating heat exchanger alarm on input DI4 will stop
the whole unit.
This in order to prevent uneconomic running and
running att too low a temperature.
Is only displayed if rotating exchanger has been
configured.

ð

Содержание Corrigo C10-LON

Страница 1: ...osen AI8 is depending on setting used for 1 Frost protection sensor for applications with water heated heater 2 High temperature limiting switch for applications with electrical heater When used for high temperature limiting switch it must be connected to a free contact closing on alarm Fan supervision supply air fan exhaust air fan AI1 AI2 Connect AI1 and AI2 to free contacts that open when the f...

Страница 2: ...he Trunk of the menu tree contains the following menues Logon Configuration Only shown in level 3 Control temp ï Starting point Running mode AI Analogue in DI Digital in AO Analogue out DO Digital out Scheduler Alarm settings Not shown in level 0 Settings Only shown in level 2 and 3 During normal running when the buttons are not in use a series of menu pages is shown The display alternates between...

Страница 3: ...with outdoor tempera ture compensation 2 Room temperature control with cascade control of the supply air temperature 3 Room temperature control with minimum maximum limiting of the supply air temperature 4 Room temperature control without supply air tempera ture sensor 5 Outdoor temperature controlled change over between constant supply air temperature control with outdoor temperature compensation...

Страница 4: ...ng engineer When the configuration is terminated by leaving the configuration branch by pressin Esc an automatic restart with the new parameters will take place The login level will be reset to 0 Configuration quick method The top two menu pages on the configuration branch show two configuration codes Configuration code 1 and Configuration code 2 Each position in the code represents in order the v...

Страница 5: ... none of the periods contains the day H the system will be shut down on holidays 5 Holiday periods Level 2 and up 2 periods comprising any number of days may be programmed Running time during a holiday is set by programming the day H into one of the three scheduler periods If none of the periods contains the day H the system will be shut down on holidays Alarm settings Here all settings for the al...

Страница 6: ...cating that the dampers have reached the other end point When DI6 is activated the output DO6 is deactivated and the dampers begin to return to the start position To avoid an alarm output DI6 must once again be deactivated within 5 minutes and then activated again within 5 minutes indicating that the dampers are back in their original position Factory settings Configuration Factory settins Config ...

Страница 7: ...Y1 0 Not active 0 1 Heating 1 2 Damper 2 3 Cooling 3 D Output Y2 0 Not active 0 1 Plate heat exchanger 1 2 Rotating heat exchanger 2 3 Liquid connected heat exchanger 3 4 Damper 4 5 Heating 5 6 Cooling 6 E Output Y3 0 Not active 0 1 Cooling 1 2 Heating 2 F Frost protection Water heating only 0 Not active 0 1 Active on Y1 1 2 Active on Y2 2 3 Active on Y1 with automatic alarm reset 3 4 Active on Y2...

Страница 8: ...rm only 0 1 Alarm supply air and exhaust air fans stop 1 2 Alarm supply air fan stops 2 3 Alarm exhaust air fan stops 3 O Function DI7 DI8 0 Not active 0 1 Pushbutton 1 2 Timer 2 P 2 speed fans Can not be combined with DX cooling 0 No 0 1 Yes 1 Q External setpoint 0 No 0 1 Yes 1 R Daylight saving time 0 No 0 1 Yes 1 S This function is not available for Corrigo C10 The code must always be set to 0 ...

Страница 9: ...egrenzungsfühler im Wärmetauscherkreis 3 Externer Sollwert Eingang für Sollwertsignal verwendet Fühler Diese Funktion sind deshalb gegenseitig auszu schließen Nur eine der Funktionen kann gewählt werden AI8 wird in Abhängigkeit von der Einstellung entweder für Frostschutz in Applikationen mit Wasserbatterie Überhitzungsschutz in Applikationen mit Elektroheizung Wenn er als Eingang für den Überhitz...

Страница 10: ...nd Corrigo an die Spannung angeschlossen wird ermöglicht Um die Sprache zu ändern nochmals auf die Taste drücken Ein Anzeige wird neben der aktuellen Sprache angezeigt Zum Ändern é oder ê drücken Wenn die gewünschte Sprache gewählt ist OK drücken Nochmals OK drücken um wieder in das normale System zu gelangen Jede Information die im Fenster angezeigt werden kann ist in Abschnitten in einen Eingabe...

Отзывы: