2418C JAN 00  1.5.5

CORRIGO C10-LON

INSTRUCTION

Corrigo C10-LON is a controller primarily intended
for controlling air handling units. It can easily be
adapted to suit different types of units.
Corrigo C10-LON has built-in capability for LON
communication. See separate LON interface manual.

Corrigo C10-LON has three 0...10 V DC control outputs
in sequence for controlling for example heating / heat
exchanger / cooling.
It has a number of functions and possibilities, such as
DX-cooling in one or two steps, outdoor temperature
compensation, fire damper exercise, control and
monitoring of fans and circulation pump, free cooling,
heat-exhanger efficiency calculation etc.
Corrigo C10-LON can also receive and handle a number
of alarms such as fan and filter alarm, smoke alarm,
chiller alarm, heat-exchanger alarm and has a free relay
output for total alarm.
Corrigo C10-LON has a year-base real-time clock,
week-scheduler , holiday calendar, holiday periods and
automatic normal time/daylight saving time change-over.

Installation

Mount the unit on a DIN rail in a cabinet or separate
enclosure.
For mounting in the cabinet front, use mounting kit FMC.
Degree of protection

IP20

Ambient temperature

0...50°C

Wiring

Supply voltage

Terminals 42 and 43: 24 V AC, ±15%, 50/60 Hz.

Sensors AI3...AI8

Use PT1000 sensors. (See data sheet 4-150).
The choice of which sensors to connect is determined by
the choice of functions. The table, fig 3 can be used as
an aid in determining which sensors to install.
Connect the sensors according to the terminal schema-
tics on page 6.

N.B.

 All AI-inputs must refer to the signal neutral termin-

als for AI-inputs (terminals 24, 27, 30, 33).

AI4

 has different functions depending on settings.

1. Efficiency calculation - exhaust air sensor.
2. Liquid-connected heat exchanger - limiting sensor in

the exchanger circulation system.

3. External setpoint. Input for setpoint signal.
These functions are mutually exclusive.
Only one of them may be chosen.

AI8 

is, depending on setting, used for:

1. Frost protection sensor for applications with water

heated heater.

2. High temperature limiting switch for applications with

electrical heater.

When used for high temperature limiting switch it must be
connected to a free contact closing on alarm.

Fan supervision,
supply air fan, exhaust air fan AI1, AI2

Connect AI1 and AI2 to free contacts that open when the
fans stop.
Either in form of  pressure switches monitoring the
pressure over each fan or as free contacts in the fan
motor relays.

N.B. 

Since these signals control vital functions they must

be connected for the unit to work as intended.

Digital inputs DI1...DI8

The digital inputs DI1...DI8 must refer to terminal 22.

N.B. 

Terminal 22 must 

not 

be connected to any other

terminals but should only be used as reference for units
connected to DI1...DI8.
The inputs may only be connected to potential free
contacts.
Closed contact activates alarm or function.
Unused inputs are to be left open.

DI1

Input for filter guards

DI2

Input for circulation pump indication.
Must be connected for systems with water heating.

DI3

Input for chiller alarm

DI4

Input for rotation sentinel or ice build-up sentinel for
heat exchanger.

DI5

Input for smoke alarm.

DI6

Input for fire damper end-position indication, external
alarm or external switches ”not in Auto position”.
(See textblock on DO6/DI6 on page 6).

DI7

Input for start of extended running time for single
speed fan systems or high speed for two speed fan
systems.

DI8

Input for start of extended running time at low speed
for two speed fan systems

DI7 and DI8 should, depending on settings, either be
wired to a momentarily closing pushbutton or to, for
example, a timer.
If DI7 and DI8 are both closed at the same time the unit is
shut down.
If a separate handswitch for setting the running mode is
installed it should be wired according to figure 1 or 2.

!

IMPORTANT: Read these
instructions before installation
and wiring of the product.

1-speed fans

2-speed

INSTRUCTION

1

ð

Fig 3

Fig 1

High
Low
0
Auto

DI7

DI8

H
0
Auto

DI8

DI7

Fig 2

Tel:+46 (0)31 795 44 60    Fax:+46 (0)31 795 38 50

Box 116   428 22  KÅLLERED, SWEDEN

Содержание Corrigo C10-LON

Страница 1: ...osen AI8 is depending on setting used for 1 Frost protection sensor for applications with water heated heater 2 High temperature limiting switch for applications with electrical heater When used for high temperature limiting switch it must be connected to a free contact closing on alarm Fan supervision supply air fan exhaust air fan AI1 AI2 Connect AI1 and AI2 to free contacts that open when the f...

Страница 2: ...he Trunk of the menu tree contains the following menues Logon Configuration Only shown in level 3 Control temp ï Starting point Running mode AI Analogue in DI Digital in AO Analogue out DO Digital out Scheduler Alarm settings Not shown in level 0 Settings Only shown in level 2 and 3 During normal running when the buttons are not in use a series of menu pages is shown The display alternates between...

Страница 3: ...with outdoor tempera ture compensation 2 Room temperature control with cascade control of the supply air temperature 3 Room temperature control with minimum maximum limiting of the supply air temperature 4 Room temperature control without supply air tempera ture sensor 5 Outdoor temperature controlled change over between constant supply air temperature control with outdoor temperature compensation...

Страница 4: ...ng engineer When the configuration is terminated by leaving the configuration branch by pressin Esc an automatic restart with the new parameters will take place The login level will be reset to 0 Configuration quick method The top two menu pages on the configuration branch show two configuration codes Configuration code 1 and Configuration code 2 Each position in the code represents in order the v...

Страница 5: ... none of the periods contains the day H the system will be shut down on holidays 5 Holiday periods Level 2 and up 2 periods comprising any number of days may be programmed Running time during a holiday is set by programming the day H into one of the three scheduler periods If none of the periods contains the day H the system will be shut down on holidays Alarm settings Here all settings for the al...

Страница 6: ...cating that the dampers have reached the other end point When DI6 is activated the output DO6 is deactivated and the dampers begin to return to the start position To avoid an alarm output DI6 must once again be deactivated within 5 minutes and then activated again within 5 minutes indicating that the dampers are back in their original position Factory settings Configuration Factory settins Config ...

Страница 7: ...Y1 0 Not active 0 1 Heating 1 2 Damper 2 3 Cooling 3 D Output Y2 0 Not active 0 1 Plate heat exchanger 1 2 Rotating heat exchanger 2 3 Liquid connected heat exchanger 3 4 Damper 4 5 Heating 5 6 Cooling 6 E Output Y3 0 Not active 0 1 Cooling 1 2 Heating 2 F Frost protection Water heating only 0 Not active 0 1 Active on Y1 1 2 Active on Y2 2 3 Active on Y1 with automatic alarm reset 3 4 Active on Y2...

Страница 8: ...rm only 0 1 Alarm supply air and exhaust air fans stop 1 2 Alarm supply air fan stops 2 3 Alarm exhaust air fan stops 3 O Function DI7 DI8 0 Not active 0 1 Pushbutton 1 2 Timer 2 P 2 speed fans Can not be combined with DX cooling 0 No 0 1 Yes 1 Q External setpoint 0 No 0 1 Yes 1 R Daylight saving time 0 No 0 1 Yes 1 S This function is not available for Corrigo C10 The code must always be set to 0 ...

Страница 9: ...egrenzungsfühler im Wärmetauscherkreis 3 Externer Sollwert Eingang für Sollwertsignal verwendet Fühler Diese Funktion sind deshalb gegenseitig auszu schließen Nur eine der Funktionen kann gewählt werden AI8 wird in Abhängigkeit von der Einstellung entweder für Frostschutz in Applikationen mit Wasserbatterie Überhitzungsschutz in Applikationen mit Elektroheizung Wenn er als Eingang für den Überhitz...

Страница 10: ...nd Corrigo an die Spannung angeschlossen wird ermöglicht Um die Sprache zu ändern nochmals auf die Taste drücken Ein Anzeige wird neben der aktuellen Sprache angezeigt Zum Ändern é oder ê drücken Wenn die gewünschte Sprache gewählt ist OK drücken Nochmals OK drücken um wieder in das normale System zu gelangen Jede Information die im Fenster angezeigt werden kann ist in Abschnitten in einen Eingabe...

Отзывы: