46
Manual C
ORRIGO
C-
SERIES
2000.09
Commissioning protocol
Configuration
Factory setting Commissioning setting
Config.code 1
0011.1110.0000
____._____._____
Config.code 2
0100.010
____._____
A. CONTROL FUNCT.
0 Supply air control
_______________
B. HEATER TYPE
0 Water heater
_______________
C. SEQUENCE Y1
1 Heating
_______________
D. SEQUENCE Y2
1 Plate-exchanger
_______________
E. SEQUENCE Y3
1 Cooling
_______________
F. FROST PROTECTION
1 Y1
_______________
G. SHUTDOWN MODE
1 Yes
_______________
H. PUMP STOP
0 No
_______________
I. EFF MONITORING
0 No
_______________
J. DX-COOLING
0 No
_______________
K. COOLING RECOVERY
0 No
_______________
L. FREE COOLING
0 No
_______________
M. FUNCT. DI6/DU6
0 Ext.alarm+frost prot.
_______________
N. FIRE ALARM
1 SF+EF Stop
_______________
O. FUNCTION DI7/DI8
0 ---
_______________
P. 2-SPEED FANS
0 No
_______________
Q. EXTERNAL SETPOINT
0 No
_______________
R. DAYLIGHT SAVING
1 Yes
_______________
S. HUMIDITY CONTROL
0 Humidif/Dehumidification
_______________
BASIC SETTING
No
Used to reset to factory settings
Control Temp
Setpoint / Actual
20.0
_______________
Min.limit / Max.limit
10.0°C / 30.0°C
________ / _____
PBand / Itime / Nz
20K / 60s / 2K
_____/_____/____
Room P/I Factor
0.5 / 2.0
_______________
Casc.f / Itime
2.0 / ---
_______________
Setp.Room/ Outdoor temp
22.0 / 12.0
_______________
Outdoor comp. point 1
-20°C / 0.0°C
_______________
Outdoor comp. point 2
20°C / 0.0°C
_______________
Outdoor comp. point 3
25°C / 0.0°C
_______________
Outdoor comp. point 4
30°C / 0.0°C
_______________
Control Pressure
Setpoint SF/EF
300 / 300Pa
________ / _____
Reduced SF/EF
200 / 200Pa
________ / _____
SF P / I / D
200Pa / 60s / 0.0
_____/_____/____
EF P / I / D
200Pa / 60s / 0.0
_____/_____/____
Outdoor comp. point 1
-20°C / 0Pa
_______________
Outdoor comp. point 2
20°C / 0Pa
_______________
Outdoor comp. point 3
25°C / 0Pa
_______________
Outdoor comp. point 4
30°C / 0Pa
_______________
Control Humidity
Setpoint / Actual
---
________/______
Max.limit / Actual
80%RH / ---
_______ / ______
PBand / Itime
40%RH / 60s
_______/_______
Installation
System
Commiss. date
Commiss. by
Page 1
C10 and C20 only
C10 and C30 only
C10 and C20 only
C30 and C40 only
C20 and C40 only
C30 and C40 only