43
Manual C
ORRIGO
C-
SERIES
2000.09
Diode
Text
Function yellow
Function red
1
SF
Supply fan on
SF error
2
EF
Exhaust fan on
EF error
3
Pump
Pump on
Pump error
4
Y1
Output Y1
Over temp limit
Heating
or frost protection
5
Y2
Output Y2
Alarm
Exch
Blinks on defrost
Heat exchanger
6
Y3 Cool
Output Y3
Alarm chiller
7
Filter
---
Filter alarm
Alarm
--
---
Alarm active
LED’s
The LEDs are connected to the functions of certain in- and outputs. Normal running
indication is yellow. A red LED signifies an error. From the text strip, cut out a part
that suits the programmed configuration. Insert the strip through the rectangular slot
above the text windows to the left of the LEDs.
12.DX cooling. Minimum on and off times. See page 30.
Factory setting 5 min. and 5 min.
Range 0...90 min and 0...90 min.
13.Lowered minimum limit by DX cooling. See page 30.
For control configurations with minimum limiting of the supply-air temperature
(control functions 2, 3, 5 and 6) the minimum limit temperature will be lowered
by the set number of degrees when the cooling is activated. This is to reduce
the risk of the minimum limit causing a premature stopping of the cooling.
Factory setting 5 K.
Range 0...15K.
14.DX cooling.Minimum outdoor temperature.
Control function 5 only. At outdoor temperature lower than the set value the DX-
cooling outputs will not be activated.
Factory setting 12 K.
Range 0...30°C.
15.Time for fire damper exercise.
Factory setting 12 midnight. Can be set at any given time during the day or
night.
16.Min. temp and P-band for liquid connected exchanger
Factory setting 2°C and 5K
Range 0...10°C and 0...5K
17.Force low speed on fans when outdoor temp. is lower than set value.
Factory setting Yes / -10 °C.
Range Yes/No and -30...+10°C
18.Range SF/EF. Pressure range for SF and EF pressure transmitters
Factory setting 500/500 Pa.
Range 0....1000Pa
19.Damping factor, Analogue inputs AI1...AI8
Factory setting 1.
Range 1...10
20.Inversion of function for digital inputs DI1...DI8
Factory s. (Closed contact activates function/alarm)
21.Show Min/Max-temperatures for AI3...AI8. The lowest and highest values
encountered since the last activation of the function are stored and will be
displayed for each input under the menu Analogue in.
Factory setting No.
Range Yes or No