7.
Stop on alarm from rotating heat exchanger
An alarm from a rotating heat exchanger can initiate a complete stop of the
unit.
This to prevent running at too low a temperature. Heat exchanger
malfunction can also lead to unneccessarily high running costs which is
avoided by stopping the unit when an alarm is indicated on input DI4.
The function is only available if rotating heat exchanger has been configured.
Alarms -Overview
Operational failure Supply air fan
AI1
Operational failure Exhaust air fan
AI2
Operational failure, pump
DI2
With water heater
Frost protection
AI8
With water heater
High temperature limit
AI8
With electric heater
Fire alarm
DI5
Fire damper
DI6
Rotation sentinel, heat exchanger
DI4
Chiller
DI3
External alarm
DI6
When DI6 is configured
for external alarm
Sensor failure
AI3-AI8
Temperature deviation
Pressure deviation
Output in manual mode
Manual running mode
Switch not in Auto mode
DI6
When DI6 is configured
for this, external switch.
Stop Exch alarm
á
No