Temperature control
In this menu you can look at and set most control values for the temperature
control. See also menu branch ”Settings”.
The control function that has been chosen and the selected login level will
determine which of the following menus can be seen and which parameters can be
set.
The table shows all the menus and the control functions with which they are shown.
Table of control functions
0.
Supply air control
1.
Supply air control with outdoor temperature compensation
2.
Room temperature control with cascade function of supply air temperature
3.
Room temperature control with minimum/maximum limiting of supply air
temperature
4.
Room temperature control without supply air sensor
5.
Supply air control with outdoor compensation or room temperature control.
Change-over point is outdoor temperature dependent.
6.
Room temperature control with minimum/maximum limiting of supply air
temperature.
1. Setpoint/Actual temp. Control function 0,2,3,4.
2. Calculated setpoint/Actual temp. Control function 1,5,6.
3. Output % for Y1,Y2,Y3. Control function 0,1,2,3,4,5,6.
If the output is not used this will be shown as —.
4. Setpoint Supply air/Compensation. Control function 1,5.
5. Setpoint/Actual value of supply air. Control function 2.
6. Setpoint Room/Change-over temp. Control function 5.
7. Minimum/Maximum limiting. Control function 2,3,5,6.
8. P-band/I-time/Neutral zone. Control function 0,1,2,3,4,5,6.
9. Room P-band/I-factor. Control function 5
These factors set the P-band and I-time for the room temperature controller
in control function 5. They are multiplication factors applied to the
equivalent parameters set for supply air control in menu 8 above.
10. Cascade factor/I-time. Control function 2.
11. Outdoor temperature compensation. Breakpoint 1. Control function 1,5.
12. Outdoor temperature compensation. Breakpoint 2. Control function 1,5.
13. Outdoor temperature compensation. Breakpoint 3. Control function 1,5.
14. Outdoor temperature compensation. Breakpoint 4. Control function 1,5.
The breakpoints must be placed with 1 lowest and
4 highest.
For each point both the temperature and
compensation in degrees has to be set.
For temperatures lower than point 1 and higher
than point 4 the compensation is constant and
equal to the value set for these points.
Setpoint/Actual
á
20.0°C/20.0°C
â
1
2
3
4
Setpoint
Outdoor temp