27
Manual C
ORRIGO
C-
SERIES
2000.09
Exhaust air temperature control with minimum/maximum limiting of the
supply air temperature
The exhaust-air temperature sensor (AI3) controls the sequences to reach setpoint.
The temperature at the supply-air sensor (AI6) is kept within the minimum/maxi-
mum temperatures set.
B. Setting of heater type
0.
Water heating.
1.
Electric heating.
When electric heating has been selected input A18 is set for closing
contact from high temperature limit. The configuration parameters
applicable to water heated circuits: frost protection sensor, shutdown
mode, pump stop, are not shown when electric heating is selected.
Wiring suggestion when
using electric heating.
High limit thermostat contacts
drawn unactivated
Frost- protection
sensor
Exhaust-air sensor
Supply-air sensor
6. Exhaust air temp
control with min/max
limiting of the supply
air temperature
Heater type
á
0 Water heating
â
High limit
thermostat
Control
relay
Relay
electric heating
Control voltage
Control voltage
33
34 CORRIGO AI8
N.B.
Not available for C30 and
C40.
This since AI3 is then
used as humidity input.
N.B. It is important that the high temperature limit switch is wired to dissconnect the power
to the heater via a relay to ensure that the heating is properly disconnected when the limit
switch is tripped.