3. Room temperature
control with min/max
limiting
4. Room temperature
control
5. Room/supply air
temperature control
Room-temperature control with min-/max limitation of supply-air temperature
The room temperature sensor (AI7) controls the sequences so that the setpoint is
reached.
The supply-air temperature at the sensor (AI6) is kept within the set minimum and
maximum limits.
Room temperature control without supply air sensor
The temperature sensor Room (AI7) controls the sequences so that the setpoint is
reached.
Supply air temperature control with outdoor temperature compensation or
room control with min/max limiting. Outdoor temperature dependent switch-
over
The outdoor temperature sensor controls the change-over between supply air
control (winter) and room control (summer).
1) The supply air sensor (AI6) controls the sequences to reach setpoint. The
setpoint is outdoor temperature compensated by means of the outdoor tempera-
ture sensor (AI5). Parameters are set under the menu ”Temp. control”.
2) The room sensor (AI7) controls the sequences to reach setpoint. The supply air
temperature (AI6)can be min/max limited. Cooling is prevented from starting
when the outdoor temperature is low. Parameters are set under ”Settings”.
Frost protection
sensor
Frost protection
sensor
Frost protection
sensor
Supply-air sensor
Supply-air sensor
Room sensor
Room sensor
Room sensor
Outdoor sensor