INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

1

CO2RT-R / CO2RT-R-D

CO

2

-sensors for wall mounting

CO2RT-R / CO2RT-R-D are sensors for measuring carbon  
dioxide (CO

2

) concentration in indoor environments. Measuring range 

0...2000 ppm and relay output.

Technical data

Measuring principle 

NDIR (Non-Dispersive Infrared  

 

 

 

 Technology)

Measuring range   

0...2000 ppm

Inaccuracy at 20°C 

< ±(50 ppm + 2% of the measured value)

Temp. influence   

typ. 2 pp

m / K

Long term stability  

typ. 20 ppm / year

Time constant 

 

< 90 seconds

Warm-up time 

 

< 5 minutes 

Ambient temperature 

-5...55°C

Humidity 

 

0...90 % RH non condensating

Protection class   

IP30 

Switching output 
   Max. switching voltage   50 V AC / 60 V DC 
   Max. switching load  

1 A at 50 V AC, 1 A at 30 V DC 

   Min. switching load  

1 mA at 5 V DC 

   Contact material   

Ag+Au clad

30

100

85

Mounting

CO2RT-R / CO2RT-R-D should be mounted in a location with good air 
circulation where they can be expected to give a representative reading.
Mount the sensor on a wall-box or directly on the wall. Remove the front 
cover by depressing the locking tounge in the lower part of the casing 

using a 3 mm flat-blade screwdriver (see arrow in figure). Press and twist 

the screwdriver at the same time as you pull the bottom part of the front 
outwards. When the bottom end of the front is free from the casing bottom 
part, slide the cover towards the top of the casing to free the hooks hold-
ing the upper edge of the front cover.

Wiring

Supply voltage 

24 V AC ±15%, 50...60 Hz or 15...35 V DC.

Consumption 3 W.

1

Supply voltage 24 V AC

2

System neutral 24 V AC

3

Common

4

Normally open

5

Normally closed

Hysteresis and level

switching 

of

f

ppm

2000

1000

500

relay 

st

atus

switchin

g

on

ON

OFF

Hysteresis [% of the set measuring range]

Level [% of measuring range]

25% of 

measuring 

range

Start-up

After applying power to the sensor, it will take a few minutes before it 
shows correct values.

Calibration

CO2RT-R / CO2RT-R-D are factory calibrated before delivery and do 
not need to be calibrated at installation.
CO2RT-R / CO2RT-R-D are calibrated automatically, which means 
that manual recalibration is not required during the lifetime of the 
sensors.

 

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Direc-
tive 2004/108/EC through product standards EN 61000-6-1 and 
EN 61000-6-3.

RoHS

This product conforms to the Directive 2011/65/EU of the European 
Parliament and of the Council.