background image

INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

1

CO2DT-R

CO

2

-transmitter for duct mounting

CO2DT-R is a transmitter for measuring 

carbon dioxide (CO

2

) concen-

tration in exhaust air. Measuring range 0...2000ppm and relay output.
CO2DT-R is intended for duct mounting.

Technical data

Measuring principle 

NDIR (Non-Dispersive Infrared  

 

 

 

 Technology)

Measuring range   

0...2000 ppm

Inaccuracy at 20°C 

< ±(50 ppm + 2% of the measured value)

Temp. influence   

typ. 2 ppm / K

Long term stability  

typ. 20 ppm / year

Time constant 

 

< 120 seconds

Warm-up time 

 

< 5 minutes 

Ambient temperature 

-5...55°C

Humidity 

 

0...90 % RH non condensating

Protection class   

IP65 with probe downwards, otherwise   

 

 

 IP20

Mounting

CO2DT-R should be mounted at a place in the duct where it can be  
expected to give a representative reading. The transmitter should be 
placed at least 4 duct diameters after a bend for minimal turbulence.
Open the front cover by removing the screws on the cover with a screw-
driver.

CO

2

 sensing element

air flow direction

Wiring

Supply voltage 

24 V AC ±20%, 50...60 Hz or 15...35 V DC

Consumption 3 W.

1

Supply voltage 24 V AC/DC or 15...35 V DC

2

System neutral

3

Common

4

Normally open

5

Normally closed

Hysteresis and level

switching 

of

f

ppm

2000

1000

500

relay 

st

atus

switchin

g

on

ON

OFF

Hysteresis [% of the set measuring range]

Level [% of measuring range]

25% of 

measuring 

range

Start-up

After applying power to CO2DT-R, it will take a few minutes before it 
shows correct values.

Calibration

CO2DT-R is factory calibrated before delivery and does not need to 
be calibrated at installation.
CO2DT-R is calibrated automatically, which means that manual recali-
bration is not required during the lifetime of the sensor.

 

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Direc-

tive 2004/108/EC through product standards EN 61000-6-1 and 

EN 61000-6-3.

RoHS

This product conforms to the Directive 2011/65/EU of the European 

Parliament and of the Council.

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden

 

Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 
www.regincontrols.com, [email protected]

 

 
 

6742G

 

JUL

Y 19

EN