P36E-10 Zero Clearance Direct Vent Gas Fireplace
|
31
31
|
installation
Diagram 3
Diagram 5
Diagram 1
Diagram 2
plumber's
tape
connected
to wall strap
Ruban de
plombier
relié à
l’attache
murale
wall
strap
Attache
murale
45
o
Elbows
Coudes de 45
o
Firestop
Spacer
Espaceur
coupe-feu
walstrp.eps
walstrpf.eps
french
NOTE:
For best results and optimum perfor-
mance with each approved venting system,
it is highly recommended to apply “Mill-Pac”
sealant (supplied) to every inner pipe connec
-
tion. Failure to do so may result in drafting
or performance issues not covered under
warranty.
Diagram 5
Diagram 6
DURA-VENT VERTICAL
TERMINATIONS
1) Maintain the 1-1/4" clearances
(air spaces) to combustibles
when passing through ceilings,
walls, roofs, enclosures,
attic rafter, or other nearby
combustible surfaces. Do not
pack air spaces with insulation.
Check for the maximum vertical
rise of the venting system and
the maximum horizontal offset
limitations.
2) Set the gas appliance in
its desired location. Drop
a plumb bob down from
the ceiling to the position
of the appliance flue exit,
and mark the location
where the vent will penetrate the ceiling. Drill
a small hole at his point. Next, drop a plumb
bob from the roof to the hole previously drilled
in the ceiling, and mark the spot where the
vent will penetrate the roof. Determine if
ceiling joists, roof rafters or other framing
will obstr uct
t h e v e n t i n g
system. You
may wish
to relocate the
appliance or to
offset, as shown
in Diagram 2
to avoid cutting
load bearing
members.
3) A Firestop spac-
Diagram 7
Note: If installing termination on a siding
covered wall, a vinyl siding standoff or
furring strips must be used to ensure
that the termination is not recessed
into the siding.
7) Before connecting the horizontal run of vent
pipe to the vent termination, slide the Wall
Thimble over the vent pipe.
8) Slide the appliance and vent assembly
towards the wall carefully inserting the
vent pipe into the vent cap assembly. It is
important that the vent pipe extends into
the vent cap sufficient distance so as to
result in a minimum pipe overlap of 1-1/4
inches. Secure the connection between the
vent pipe and the vent cap by attaching the
two sheet metal strips extending from the
vent cap assembly into the outer wall of the
vent pipe. Use the two sheet metal screws
provided to connect the strips to the pipe
section. See Diagram 6.
9) Install wall thimble in the center of the 10"
square and attach with wood screws
(Diagram 7).
er must be installed in the floor or ceiling of
every level. To install the Firestop spacer in a
flat ceiling or wall, cut a 10 inch square hole.
Frame the hole as shown in Diagram 3 and
install the firestop.
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow con-
nections are in the fully twist-locked position
and sealed.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The hole
should be of sufficient size to meet the minimum
requirements for clearance to combustibles
of 1-1/2". Slip the flashing under the shingles
(shingles should overlap half the flashing) as
per Diagram 4.
Diagram 4: The upper half of the flashing is
installed under the roofing material and not
nailed down until the chimney is installed.
This allows for small adjustments.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic to
avoid obstructions, it is important to
support the vent pipe every 3 feet, to
avoid excessive stress on the elbows,
and possible separation. Wall straps are
available for this purpose (Diagram 2).
Galvanized pipe is desirable above the roof line
due to its higher corrosion resistance. Continue
to add pipe sections through the flashing until
the height of the vent cap meets the minimum
Roof Pitch
Minimum Vent Height
Feet
Meters
flat to 7/12
2
0.61
over 7/12 to 8/12
2
0.61
over 8/12 to 9/12
2
0.61
over 9/12 to 10/12
2.5
0.76
over 10/12 to 11/12
3.25
0.99
over 11/12 to 12/12
4
1.22
over 12/12 to 14/12
5
1.52
over 14/12 to 16/12
6
1.83
over 16/12 to 18/12
7
2.13
over 18/12 to 20/12
7.5
2.29
over 20/12 to 21/12
8
2.44
Содержание P36E-LP10
Страница 59: ...P36E 10 Zero Clearance Direct Vent Gas Fireplace 59 59 parts list ...
Страница 63: ...P36E 10 Zero Clearance Direct Vent Gas Fireplace 63 63 notes ...
Страница 68: ......
Страница 69: ...P36E 10 Zero Clearance Direct Vent Gas Fireplace 69 69 notes ...
Страница 70: ...70 P36E 10 Zero Clearance Direct Vent Gas Fireplace 70 notes ...
Страница 71: ......