Clearance:

Dimension

Measured From:

A: Rise

1” minimum

Finished Floor

B: Sidewall

7-1/2”

Side of Unit

C: Ceiling

30”

Top of Unit

D: Alcove Width

48”

Sidewall to Sidewall (Minimum)

E: Alcove Depth

36”

Front to back wall (Maximum)

Clearance Requirements

Regency P33 Sunrise Gas Fireplace

Model

P33S-NG4

P33S-LP4

Fuel Type

Natural Gas

Propane

Minimum Supply Pressure

5” W.C. (1.25 kPa)

11” W.C. (2.73 kPa)

Manifold Pressure - High

3.5” W.C. (0.87 kPa)

10” W.C. (2.49 kPa)

Manifold Pressure - Low

1.6” W.C. (0.39 kPa)

6.4” W.C. (1.59 kPa)

Maximum Input

Altitude 0-4500 ft. (0-1372m)

17,000 BTU/h

(4.98 kW)

15,500 BTU/h

(4.54 kW)

Vent Sizing

4” Inner / 6 5/8” Outer

4” Inner / 6 5/8” Outer

Unit Dimensions

Description

P33S

A

Front Face Width

33-5/8” (846mm)

B

Rear Firebox Width

23” (584mm)

C

Front Face Height

29” (737mm)

D

Height w/ Standoff

31 1/2” (800mm)

E

Unit Depth

12-3/4” (324mm)

F

Firebox Height

29” (737mm)

Framing Dimensions Description

P33S

G

Framing Width

33-1/4” (845mm)

H

**

Framing Height

**

31-3/4” (806mm)

**

I

*

Framing Rise from Floor

1” (25mm) minimum

*

J

Framing 
Depth

Vertical

19 -1/2” (495mm) 

Vertical Rise

16 1/2” (419mm) 

Rigid

 12-3/4” 

(324mm) 

Flex

Horizontal

K

Corner Wall Length

37 -1/2” (953mm)

L

Corner Facing Wall Width

53-1/4” (1353mm)

M***

Framed Chase Ceiling***

36” (914mm) 

Rigid***

32” (813mm) 

Flex***

N

Vent Centerline Height

30” (762mm) 

Rigid

26” (660mm) 

Flex

Dimension

Description

P33S

O

Gas Connection Height

1-1/2” (38mm)

P

Gas Connection Inset

4” (102mm)

Q

Gas Connection Width

3” (76mm) 

 R

Minimum Framing Depth

16 1/2” (419mm) 

Rigid  /  

12-3/4” (324mm) 

Flex

 S

Maximum Framing Depth 
(including wall thickness)

40 1/2” (1028mm) 

Rigid  /  

36-3/4” (933mm) 

Flex

P33 Sunrise Gas Fireplace

Approved Venting Systems

Flex Vent Systems:

FPI AstroCap™ Flex Vent

Rigid Pipe Vent Systems:

Simpson Direct Vent Pro®
American Metal Products® Amerivent Direct
Security Secure Vent® 
Selkirk Direct-Temp™
Metal-Fab® Sure Seal

* The unit must be raised a minimum of 1” above the 

fi

 nished 

fl

 oor.

** Dimension H = H + I (minimum)
*** Dimension M = M + I (minimum)

This manual is intended to be a Sales Reference Guide only.
Do NOT use for actual framing and installation of any unit. 
Some speci

fi

 cations may change without notice.

You must use the actual manual for exact installation speci

fi

 cations.

WARNING

Failure to maintain required clearances is a major cause of chimney related 

fi

 res.  

Installation of this 

fi

 replace must comply with these clearances

Please note:

 Due to ongoing product development, product appearance and speci

fi

 cations 

are subject to change without notice.