FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.  6988 Venture St., Delta, BC  Canada, V4G 1H4

919-372

Regency Horizon® HZ54E

Gas Fireplace

09.16.15

Owners & 

Installation Manual

www.regency-fire.com

Tested by:

Installer

: Please complete the details on the back cover 

and leave this manual with the homeowner.

Homeowner:

 Please keep these instructions for future reference.

 MODELS: HZ54E-NG10 Natural Gas
                  HZ54E-LP10  Propane

Horizon HZ54E Product Video

 

-  Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other 

appliance. 

- WHAT TO DO IF YOU SMELL GAS
 • 

Do not try to light any appliance.

 

•  Do not touch any electrical switch: do not use any phone in your building.

 

  Leave the building immediately.

 

•  Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's  

instructions.

 

• If you cannot reach your gas supplier, call the fire department.

 

 

 

- Installation and service must be performed by a qualified installer, service agency or the gas supplier.

     WARNING
FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in serious
injury, death, or property damage. 

Содержание HZ54E-LP10

Страница 1: ...oline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call t...

Страница 2: ...armth and charm of a wood fireplace at the flick of a switch The model HZ54E has been approved by Warnock Hersey Intertek for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace ...

Страница 3: ...s Direct Vent System Appliance must be installed in accordance with the manufacturer s installation instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or the current Standard of Fire Safety Criteria for Manufactured Home Installations Sites and Communities ANSI NFPA 501A and with CAN CSA Z240 MH Mobile Home Standard in Canada This appliance installation ...

Страница 4: ...ntal Terminations for HZ54E lp 24 Venting Arrangements 27 Allowable Vertical Terminations for HZ54E ng 27 Venting Arrangements 28 Allowable Vertical Terminations for HZ54E lp 28 Unit Installation with Horizontal Termination 29 Unit Installation with Vertical Termination 30 Unit Installation 31 Horizontal Termination with Flex Vent System 31 High Elevation 32 Gas Line Installation 32 Pilot Adjustme...

Страница 5: ...vidual manual shut off must be a t handle type valve The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA720 and a CO alarm withbatterybackupinthesameroomwhere the gas appliance is installed This is a copy of the label that accompanies each HZ54E NG10 HZ54E LP10 Direct Vent Gas Fireplace We have printed a copy of the contents here for your review ...

Страница 6: ...ectly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspec...

Страница 7: ...Regency Horizon HZ54E 10 Gas Fireplace 7 7 dimensions FACEPLATE DOOR FRAME OVERLAY DIMENSIONS UNIT DIMENSIONS The Verona Glass Surround Not Shown Dimensions 58 9 16 W x 27 1 8 H ...

Страница 8: ...equirescommonsense however wearerequired by the Canadian Safety Standards and ANSI Standards to make you aware of the following GENERAL SAFETY INFORMATION 1 Theapplianceinstallationmustconformwithlo cal codes or in the absence of local codes with the current Canadian or National Gas Codes CAN1 B149orANSIZ223 1InstallationCodes 2 The appliance when installed must be electri cally grounded in accord...

Страница 9: ...control instructions for operation of this device 8 Test the pilot Refer to Pilot Adjustment section 9 TestGasPressure Referto GasPipePressure Testing section 10 Install standard and optional features Refer to the following sections a Optional Log Set Installation b Glass Crystals Optional Ceramic Stones c Optional Firebox Base Pebbles d Optional Reflective Panels e Faceplate Door Frame Overlay 11...

Страница 10: ...Measured From A Mantel Height min 20 508mm Top of Fireplace Opening B Sidewall on one side 4 102mm Side of Fireplace Opening C Ceiling room and or alcove 40 7 8 1038mm Top of Fireplace Opening D Mantel Depth max 13 330mm 30 Above Fireplace Opening E Alcove Width 83 2108mm Sidewall to Sidewall Minimum F Alcove Depth 36 914mm Front to Back Wall Maximum G To Floor 28 7 8 733mm Top of Fireplace Openin...

Страница 11: ... manufacturer s recommendations 6 Prime wall for a second time for proper adhesion of paint 7 Paint walls using a high quality paint which will withstand the high temperatures being emitted from this appliance IMPORTANT Regency Fireplace Products are designed produced tested and certified to the highest industry standards The finishing of the walls surrounding your Regency Horizon Fireplace is as ...

Страница 12: ...EL LEG CLEARANCES Combustible mantel leg clearances as per diagram 4 Allowable mantel leg projection 5 1 2 140mm 8 203mm 11 279mm 1 5 38mm MANTEL LEG 4 102mm Non Combustible 7 Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Drywall 2 0 12 6 4 8 10 Top of Fireplace Opening 13 330mm 3 89mm Standoff Metal Stud...

Страница 13: ...tion Combustible materials can be laid against the side and back standoffs and the stove base 4 When finishing around the faceplate if material such as brick stone etc extend past the faceplate depth due to the finished material exceeding 3 1 8 the minimum opening dimensions noted below must be adhered to this is to ensure removal of the faceplate For material such as brick stone etc that extends ...

Страница 14: ...CTION The HZ54E uses the balanced flue technology Co Axial system The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney Note These flue pipes must not be connected to any other appliance The gas appliance and...

Страница 15: ...ming depth measurement is noted with the side nailing strips set as far forward on the firebox as possible The side nailing strips can be adjusted back up to 3 1 8 to allow for varying thicknesses in non combustible material wall finishes Important The minimum framing dimensions given for height width and depth must be maintained even if using non combustible materials Dangerous operating conditio...

Страница 16: ...by loosening 2 screws on each nailing strip adjust and retighten the screws 4 Attach both vertical studs 478 015 and secure using 6 screws 2 at bottom 2 at top and 2 on the sides as shown NOTE Ensure the flat side of the steel stud is facing the wood framing 5 Secure horizontal steel header with 2 screws per diagram 6 Slide the unit in position Hook up gas venting and electrical and fan if purchas...

Страница 17: ...ox to the framing at desired location within 10 ft from fireplace 2 Feed the 12 pin connector through the opening at back of junction box 3 Connect the 12 pin connector to the back of the receiver 4 Install the Receiver in the Low Voltage Junction box 5 Insert the 4 AA type batteries in the battery compartment with the correct polarity 6 Place the slider into the cover plate 7 Put the Receiver swi...

Страница 18: ...he vent restrictor plate is in the required position secure with screws VENT RESTRICTOR POSITION Vent Restrictor Settings for HZ54E NG Vent Restrictor Settings for HZ54E LP 4 25 3 2 Vent Restrictor Set 1 Factory Set Vent Restrictor No adjustment required Vent Restrictor Set 2 Vent Restrictor Set 4 SET 2 THIS HOLE SETS THE VENTR ESTRICTOR AT 3 SET 1 THIS HOLE SETS THE VENTR ESTRICTOR factory settin...

Страница 19: ... side of center line extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located on public property 84 2 1m ...

Страница 20: ...ner sections should be continuous without any joints or seams 2 Only Flex pipe purchased from FPI may be used for Flex installations 3 Horizontal vent must be supported every 3 feet 4 Awallthimbleismandatoryforallhorizontalterminations due to high temperatures FPI Kit Length Contains 946 615 4 Feet 1 8 flexible liner Kit length 2 5 flexible liner Kit length 3 spring spacers 4 thimble 5 AstroCap te...

Страница 21: ...retooutsidesurface of wall without siding and add 2 inches When using Rigid Vent other than Simpson Dura Vent 3 screws must be used to secure rigid pipe to adaptor The FPI AstroCap XLTM is certified for installations using FPI venting systems as well as Simpson Dura Vent Direct Vent Pro ICC Excel and Selkirk Direct Temp AstroCap XLTM is a proprietary trademark of FPI Fireplace Products Internation...

Страница 22: ... Offset Support 58DVA ES N A from FPI 5DT OS N A N A Wall Thimble Black 58DVA WT 5DT WT 5DWT TE 5DE90 Wall Thimble Support Ceiling Support 58DVA DC N A from FPI N A N A TE 5DE90B Firestop Spacer 58DVA FS 5DT FS 5DFS N A Trim Plate Black 58DAV WFS 5DT TP 5DCP N A 5 X 8 RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed Not all rigid pipe components are availab...

Страница 23: ...ional 946 606 Starter collar reducer 5 x 8 to 4 x 6 5 8 946 625 Vinyl Siding Standoff AstroCap XL Note When using Metal Fab Sure Seal Rigid Piping please note that the Adaptor 4DDA must be used in conjunction with FPI Rigid Pipe Adaptor 510 994 Offset Pipe Selection Use this table to determine offset pipe lengths Pipe Length L 5 x 8 Venting For specific instructions on venting components visit the...

Страница 24: ...t Firestops are required at each floor level and whenever passing through a wall A wall thimble is mandatory for all horizontal terminations due to high temperatures VENT RESTRICTOR SETTING Vent restrictor factory set no adjustment required unless otherwise indicated Refer to the Vent Restrictor Position section for details on how to change the vent restrictor from the factory setting of Set 1 to ...

Страница 25: ...al pipe length is 30 feet with min of 11 feet total vertical and max 9 feet total horizontal Please note min 1 foot between 90o elbows is required VENT RESTRICTOR SETTING Vent restrictor factory set at Set 1 no adjustment required One 90o elbow Two 45o elbows Option V H H1 With these options maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 10feettotalhorizonta...

Страница 26: ...in 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 8 Max 9 Min One 90o elbow Two 45o elbows Withtheseoptions max total pipelengthis30feetwithmin of9feettotalverticalandmax 8 feet total horizontal Please note min 1 foot between 90o elbows is required VENT RESTRICTOR SETTING Vent restrictor factory set at Set 1 no adjustment required V H1 H V1 ...

Страница 27: ...m Min 44 1118mm Max 10 3m centerline to centerline Minimum length of pipe between elbows 12 305mm Maximum 27 ft 8 2m 0 2 4 6 40 8 10 12 14 16 18 20 22 24 26 28 30 Vertical Height Feet 32 34 36 38 6 8 Horizontal Feet 2 0 4 10 12 16 18 14 Vent Restrictor on Set 2 Vent Restrictor on Set 4 Vent Restrictor on Set 1 factory setting VENTING ARRANGEMENTS ALLOWABLE VERTICAL TERMINATIONS FOR HZ54E NG The sh...

Страница 28: ...m Min 44 1118mm Max 10 3m centerline to centerline Maximum 27 ft 8 2m 0 2 4 6 40 8 10 12 14 16 18 20 22 24 26 28 30 Vertical Height Feet 32 34 36 38 6 8 Horizontal Feet 2 0 4 10 12 16 18 14 20 Vent Restrictor on Set 4 Vent Restrictor on Set 5 Vent Restrictor on Set 1 factory setting Minimum length of pipe between elbows 12 305mm VENTING ARRANGEMENTS ALLOWABLE VERTICAL TERMINATIONS FOR HZ54E LP The...

Страница 29: ...ight side of the unit 2 Direct Vent pipe and fittings are designed with special twist lock connections to connect the venting system to the appliance flue outlet A twist lock appliance adaptor is required 3 InconjunctionwiththeSimpsonDirectVentPro system install the adaptor after the unit is set in its desired location Put a bead of Mill Pac inside the outer section of the adapter and on theinnerc...

Страница 30: ...m the ceiling to the position of the appliance flue exit andmarkthelocation where the vent will penetrate the ceiling Drill a small hole at his point Next drop a plumb bob from the roof to the hole previously drilled in the ceiling and mark the spot where the vent will penetrate the roof Determine if ceiling joists roof rafters or other framing will obstruct the venting system You may wish to relo...

Страница 31: ...pt when passing through a wall ceiling or at the termination where the use of a firestop or wall thimble reduces the required clearance to 1 1 2 38mm We recommend framing a 11 279mm x 11 279mm inside dimensions hole to give structural rigidity for mounting the termination 1 Locate the unit in the framing rough in the gas preferably on the right side of the unit Locate the centerline of the termina...

Страница 32: ...installations follow local codes and or the current National Fuel Gas Code ANSI Z223 1 When using copper or flex connectors use only approved fittings Always provide a union so that gas lines can be easily disconnected for servicing Flare nuts for copper lines and flex connectors are usually considered to meet this requirement NOTE A shutoff dante valve should be supplied in or near the unit or as...

Страница 33: ...ess the DBFC see Battery ON OFF switch installation 1 Remove Faceplate and glass door if installed 2 The valve cover is located on the right side underneath the glass door loosen 2 screws securing the valve cover see Diagram 1 below Valve cover Diagram 1 Diagram 2 Diagram 3 3 Slide the valve cover upward 4 Lift the cover up off the screws and out of the unit 5 To install reverse steps ...

Страница 34: ...ellow flame For instructions to remove the burner for access to the ventury cap see pages 46 47 in this manual Minimum Air Shutter Opening NG 1 2 NG with Logs Full open NG with Stones Full open LP 1 2 LP with Logs Full open LP with Stones Full open CAUTION Carbon will be produced if air shutter is tightly closed Note Any damage due to carboning resulting from improperly setting the aeration contro...

Страница 35: ...nded bringing power to the receptacle box provided with the unit in case the fan is installed at a later date The AC adaptor is included with this appliance CAUTION Labelallwirespriortodisconnection when servicing controls Wiring errors can cause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges Note Either 4 AA batteries or ...

Страница 36: ...res will be located near the gas valve Disconnect greenTH wire Green Wires White Connector 3 Connect one thermostat lead to female connector using male spade con nector see picture below CAUTION Do not wire Thermostat wires to 120V wire 4 Connect the other thermostat lead to male connector disconnected from Step1using a female spade connector see picture below When complete turn remote receiver to...

Страница 37: ...allation will not receive consideration Black Enamel panels must be inspected for scratches and dimples prior to installation All claims to be recorded at this time Claims for damage after installation will not receive consideration Use a hair dryer to remove the protective coating from the panels Toprotectthefinishduringinstallationandhandling cottongloves MUST be worn at all times while handling...

Страница 38: ...amic Stones or 2 lb Glass 40 Volcanic Stones 3 lb Beads 2 packages 140 Spa Stones 3 lb Beads 40 Volcanic Stones NOTE Glass Crystals are not supplied with the unit Must purchase separately see quantities above OPTIONAL PEBBLES GLASS CRYSTAL INSTALLATION FOR FIREBOX BASE AROUND BURNER Firebox Around Burner Packages Unit Glass Crystals Fire Beads Pebbles HZ54E 6 lbs 9lbs 2 packages 6 x bags pebbles T...

Страница 39: ...rature 2 Remove flush glass door see manual 3 Carefully remove the logs from the packaging and unwrap them The logs are fragile handle with care never force into position 4 Ensure glass crystals are installed on the burner HZ54E 2lbs HZ40E 1 5lbs 5 HZ54E only Remove existing pilot hood replace with pilot hood provided with log set HZ54E existing Pilot Hood HZ54E new Pilot Hood HZ40E log placement ...

Страница 40: ...og piece on firebox floor as shown 16 Place Right Log piece on firebox floor as shown 17 If desired install additional crystals on firebox floor in and around installed logs 18 Install lava embers spread evenly over glass HZ54E shown Left Log 2 positioned to match template profile HZ54E shown Completed Install HZ40E shown Completed Install HZ54E shown Left Cross Log 4 positioned to match template p...

Страница 41: ...rame 1 to be removed and installed into outer door frame 3 as shown 4 Hook the outer door frame 3 and mesh screen assembly 2 over the inner door frame 1 1 5 Bend the center tab up and secure with a screw to attach the outer frame mesh assembly to the inner door frame 5 Attach the completed assembly to the glass frame on the unit 6 Proceed to Faceplate installation 2 3 2 Remove screws from inner si...

Страница 42: ... is a top and bottom the top of the faceplate has a full 1 return whereas the bottom only has a 1 2 return as shown in the diagram below 2 Install the faceplate to the unit by hooking the left and right side mounting brackets into the mounting slots at the side of the firebox as shown below It is recommended that you use the first mounting slot the one closest to the door frame overlay out of the ...

Страница 43: ...nd the faceplate are equal from side to side you may need to slide the faceplate slightly to the left or right accordingly Also if necessary the faceplate may be adjusted up and down by loosening the top screw as shown in the diagram below and sliding the plate up or down as required Faceplate Mounting Slots Completed Faceplate Installation ...

Страница 44: ...ng the door out 45o from the bottom and lift up and out Important 120 Volt AC power is needed for the blower The receptacle box is installed on the left hand side of the unit and must be wired by a qualified electrician prior to fan assembly being installed The neutral wider slot of the polarized receptacle should be at the top 7 Remove bottom cover by undoing 3 screws securing it to the firebox b...

Страница 45: ...sary Ground Lug 2 HZ54EPV FAN INSTALLATION 12 Remove 8 screws to remove the fan access panel cover located on the left hand side floor of the firebox 13 Manoeuvre the fan into position on the floor of the unit Tilt the fan to get through the fan access panel and into position Fan Access Panel 10 After extenders have been removed Remove the 2 screws that secure the burner tray at the base of the fi...

Страница 46: ...stall the fan air deflector it hooks to 2 brackets on to the bottom lip the unit to the right of the receiver Air deflector TO REMOVE THE FAN 1 Turn the power off 2 Reverse the above instructions Maintenance The sealed bearings are lubricated there is no need to lu bricate them further Extra lubricant will cause more lint and dust buildup causing the bearings to prematurely fail Regular cleaning a...

Страница 47: ...White Black Black Ground Fan Fan Proflame System Configuration 886 GTMF Wire Diagram SureFire Switch 885 CAUTION Labelallwirespriortodisconnection whenservicingcontrols Wiringerrorscancause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges WIRING DIAGRAM WITH OPTIONAL FAN ...

Страница 48: ...y cause condensation and fog the glass This condensation is normal and will disappear in a few minutes as the glass heats up DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS STILL HOT DO NOT BURN THE UNIT WITHOUT THE GLASS DOOR IN PLACE FIRST FIRE NORMAL OPERATING SOUNDS OF GAS APPLIANCES It is possible that you will hear some sounds from yourgasappliance Thisisperfectlynormaldueto the fact that ther...

Страница 49: ...ately 60 seconds If there is no flame ignition rectification the board will stop sparking for approximately 35 seconds After wait time the board will start second try for ignition by sparking for approximately 60 seconds If there is still no positive ignition the board will go into lock out The system will need to be reset as follows a Turn the system off using ON OFF switch or press ON OFF button...

Страница 50: ...r service agency or gas supplier AVERTISSEMENT Quiconque ne respecte pas à la lettre les instructions dans la présente notice risquede déclencher un incendie ou une explosion entraînant des dommages des blessures ou la mort Une installation d ajustement de modification de service ou d entretien peut provoquer des blessures ou des dommages matériels Reportez vous au manuel du propriétaire de l info...

Страница 51: ... ChecktheVentingSystemforcorrosioninareas that are exposed to the elements These will appear as rust spots or streaks and in extreme cases holes These components should be replaced immediately 2 RemovetheCap andshineaflashlightdownthe Vent Remove any bird nests or other foreign material 3 Checkforevidencesofexcessivecondensation such as water droplets forming in the inner liner and subsequently dr...

Страница 52: ... Remove the door frame overlay by swinging out 45o from the bottom and lift up and out b Remove the 3 screws shown below at the bottom of the glass door c Swing the door out 45o from the bottom and lift up and out GLASS DOOR REMOVAL 6 Remove valve cover see valve cover removal section in this manual 5 Remove the glass door Diagram 4 Magnet Cover Plate a Remove cover plates from over each screw by ...

Страница 53: ...l screen into inner door trim 3 Secure screen by bending down the 6 tabs as shown 4 Hook the outer door frame 3 and mesh screen 2 assembly over the inner door frame 1 5 Bend the center tab up and secure with a screw to attach the outer frame mesh assembly to the inner door frame 6 Attach the completed assembly to the glass frame on the fireplace 7 Secure the assembly with screws on each side as sh...

Страница 54: ... firebox 4 Remove the door frame overlay by swinging out 45o from the bottom and lift up and out 5 Remove the glass door a Remove the 3 screws shown below at the bottom of the glass door b Swing the door out 45o from the bottom and lift up and out VALVE TRAY REPLACEMENT Note See next pages for specific instructions for NG LP units Prior to removing burner remove the following if installed crystals...

Страница 55: ... 3 Disconnect the green and orange wires from the valve 7 Remove the valve tray by undoing 12 screws 8 Partially lift out valve tray 9 Disconnect the inlet gas line 10 Replace valve and reverse steps 2 Remove bottom cover by undoing 3 screws securing it to the firebox base lift up and out Aerial View of the inside of the unit shown 4 Disconnect the green ground wire from the valve bracket 5 Lift o...

Страница 56: ... base of the firebox 5 Slide the burner to the left and lift it out 6 With burner removed lift out burner tray Burner tray extenders Burner tray extenders Burner tray Gas Inlet Line Burner Bracket Location of screws securing burner 10 Partially lift out valve tray 11 Disconnect the inlet gas line 12 Replace valve and reverse steps 9 Remove the valve tray by undoing 12 screws Green Wire Orange Wire...

Страница 57: ...ailing Strips 910 572 Wall switch Receiver 911 032 Wire harness 911 013 Valve wiring w IPI CPI switch 910 576 Wall Switch Receiver cover white 911 012 Ignition Board 946 721 AC Adaptor 910 592 GTMF Hand held transmitter 911 030 Fan Control Module Part Description 8 478 915 Optional Fan 476 540 Flush Door w Glass 478 013 Mesh Barrier 476 023 Plate Relief Gasket 476 055 Valve Tray Gasket 946 556 Hea...

Страница 58: ...58 Regency Horizon HZ54E 10 Gas Fireplace 58 parts list ...

Страница 59: ...Starfire Crystals 946 672 Natural River Pebbles 946 674 Ceramic Spa Stones 946 710 Volcanic Stones Slate Grey 946 711 Volcanic Stones Ivory Tan 946 556 Heat Wave Duct Kit 946 570 Heat Release Kit 476 936 Non Combustible Board 4 Pieces 1 pound bag of glass crystals Part Description 946 675 Black Reflective Crystals 946 676 Copper Crystals 946 677 Starfire Crystals 5 pound bag of Firebeads Part Desc...

Страница 60: ...60 Regency Horizon HZ54E 10 Gas Fireplace 60 notes ...

Страница 61: ...Regency Horizon HZ54E 10 Gas Fireplace 61 61 notes ...

Страница 62: ...62 Regency Horizon HZ54E 10 Gas Fireplace 62 notes ...

Страница 63: ...ment parts and issue credit once the replaced component has been returned to Regency and evalu ated for manufacturer defect The authorized selling dealer is responsible for all in field service work carried out on your Regency product Regency will not be liable for results or costs of workmanship from unauthorized service persons or dealers At all times Regency reserves the right to inspect produc...

Страница 64: ..._____________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No ___________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of all you...

Отзывы: