background image

 

Regency Horizon® HZ40E-10 Gas Fireplace

  |     

21

 

 

|

 

21

installation

Description

Simpson

Direct Vent Pro

®

Selkirk

Direct Temp™

American Metal

Products®

Amerivent Direct

Metal-Fab™

Sure Seal

Security

Secure- Vent®

ICC Excel 

Direct

Attic Insulation Shield 12”

46DVA-IS 

N/A@ FPI

N/A

4DAIS12

N/A

SV4RSA

N/A

Attic Insulation Shield - 

Cold Climates

 36”

N/A

N/A

4DAIS12

N/A

N/A

TM-4AS

High Wind Vertical Cap

46DVA-VCH

N/A

N/A

N/A

N/A

TM-4VT

High Wind Horizontal Cap

46DVA-HC

N/A

N/A

N/A

N/A

TM-4DHT

Horizontal Square Termination Cap

See

 

46DVA-HC

4DT-HHC

4DHC

4DHT

SV4CHC-1

TM-4HT

Vertical Termination Cap

46DVA-VC

4DT-HVC

4DVC

4DVT

SV4CGV-1

N/A

Storm Collar

46DVA-08A

4DT-SC

4DSC

4DSC

SV4FC

TM-SC

Restrictor Disk

N/A

N/A

N/A

N/A

N/A

TM-4DS

Extended Vertical Termination Cap

N/A

N/A

N/A

N/A

N/A

N/A

Chimney Conversion Kit  A  (USA only)

46DVA-KCA

N/A

N/A

N/A

N/A

TM-4CA6

Chimney Conversion Kit  B  (USA only)

46DVA-KCB

N/A

N/A

N/A

N/A

TM-4CA7

Chimney Conversion Kit  C  (USA only)

46DVA-KCC

N/A

N/A

N/A

N/A

TM-4CA8

Chimney Conversion Kit Masonry 
(USA only)

46DVA-KMC

N/A

N/A

N/A

N/A

N/A

Wall Firestop

46DVA-WFS

N/A

N/A

N/A

N/A

TM-4TR

Colinear Flex Connectors

46DVA-ADF

N/A

N/A

N/A

N/A

N/A

Adjustable Flashing 0/12-6/12

46DVA-F12

4DT-ST14

4D12S

4DST14

SV4STC14

TF-4FA

Adjustable Flashing 6/12-12/12

46DVA-F12

4DT-ST36

4D36S

4DST36

SV4STC36

TF-4FB

Vinyl Siding Standoff

46DVA-VSS

4DT-VS

N/A

4DVS

SV4VS

TM-VSS

Vinyl Siding Shield Plate

N/A

4DT-VSP

N/A

N/A

SV4VS

N/A

Snorkel Termination 14”

46DVA-SNKL

N/A

N/A

N/A

N/A

TM-4ST14

Snorkel Termination 36”

N/A

N/A

N/A

N/A

N/A

TM-4ST36

Basic Horizontal Termination Kit (A)

Disc.

4DT-HKA

4DHTK2

4DHTKA

SV-SHK

TM4-HTK

Horizontal Termination Kit (B)

46DVA-KHA

(Changed Components)

4DT-HKB

4DHTK1

4DHTKB

SV-HK

TM4-HTK

Vertical Termination Kit

Disc.

4DT-VKC

4DHTK

4DHTK

SV-FK

N/A

FPI

946-506/P

Vent Guard (Optional) for AstroCap

946-205

Vinyl Siding Shield for Riser Vent Terminal

510-994

Rigid Pipe Adaptor (Must use with all rigid piping)

946-208/P

Vent Guard (Optional) for Riser Vent Terminal

640-530/P

Riser Vent Terminal

946-523/P

AstroCap Horizontal Cap

946-206

Vinyl Siding Standoff for AstroCap

Note:

   When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).

Note:

   Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination.  

            Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.

Offset Pipe Selection:

 Use this table to determine offset pipe lengths.

Pipe Length

(L)

4” x 6-5/8” Venting

For specifi c instructions on venting components - visit the 
manufacturers website listed below.

Run (X)

Rise (Y)

0” (0mm)

4-7/8” (124mm)

13-7/8” (340mm)

Simpson Direct Vent Pro:  www.duravent.com

6” (152mm)

8” (203mm)

16-1/2” (419mm)

Selkirk Direct-Temp: www.selkirkcorp.com

9” (229mm)

10-1/8” (257mm)

18-5/8” (473mm)

American Metal Products: www.americanmetalproducts.com

12” (305mm)

12-1/4” (311mm)

20-3/4” (527mm)

Metal-Fab Sure Seal: www.mtlfab.com

24” (610mm)

20-5/8” (524mm)

29-1/8” (740mm)

Security Secure Vent:  www.securitychimneys.com

36” (914mm)

29” (737mm)

37-1/2” (953mm)

Industrial Chimney Company: www.icc-rsf.com

48” (1219mm)

37-7/16” (951mm)

45-15/16” (1167mm)

Содержание Horizon HZ40E

Страница 1: ...ELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach you gas supplier call the ire department Installation and service must be performed by a qualiied installer service agency or the gas s...

Страница 2: ...by local codes This Direct Vent System Appliance must be installed in accordance with the manufacturer s installation instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 or the current Standard of Fire Safety Criteria for Manufactured Home Installations Sites and Communities ANSI NFPA 501A and with CAN CSA Z240 MH Mobile Home Standard in Canada This appli...

Страница 3: ...the warmth and charm of a ireplace at the lick of a switch The model HZ40E has been approved by Warnock Hersey Intertek for both safety and eiciency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace ...

Страница 4: ...ts Vertical Terminations 34 Unit Installation with Horizontal Termination 35 4 x 6 5 8 venting 35 Unit Installation with Horizontal Termination 36 Dura Vent Horizontal terminations 37 Unit installation with Vertical Termination 38 4 x 6 5 8 venting 38 Vertical Termination 39 4 x 6 5 8 venting 39 Flex vent components 40 High Elevation 41 Gas Line Installation 41 Pilot Adjustment 41 Gas Pipe Pressur...

Страница 5: ...ppliance must be installed in accordance with local codes if any if none follow the National Fuel Gas Code ANSI Z223 1 or Natural Gas and Propane Installation Code CSA B149 1 This appliance must be installed in accordance with the Standard CAN CSAZ240 MH Mobile Housing in Canada or with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or when such ...

Страница 6: ...ectly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspec...

Страница 7: ...Regency Horizon HZ40E 10 Gas Fireplace 7 7 dimensions 1092mm 972mm 522mm 902mm 318mm 388mm 15 1 4 Inner Outer Faceplate 4 Piece Faceplate Verona Surround ...

Страница 8: ...we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES ESPE CIALLY THE FIREPLACE GLASS AND SHOULD STAY AWAYTO AVOID BURNS OR CLOTHING IGNITION GENERAL SAFETY INFORMATION 1 The appliance i...

Страница 9: ...ectly and operation fully explained to customer LOCATING YOUR GAS FIREPLACE 1 When selecting a location for your ireplace ensure that the clearances are met 2 The appliance must be installed on a lat solid continuous surface For example a wood metal or concrete loor or in a raised on the wall ap plication The appliance must be installed on a metal or wood panel extending the full width and depth o...

Страница 10: ...e and vent system be installed only in accordance with these instructions Clearance Dimension Measured From A Mantel Height min 17 330mm Top of Fireplace Opening B Sidewall on one side 8 203mm Side of Fireplace Opening C Ceiling room and or alcove 22 559mm Top of Fireplace Opening D Mantel Depth max 13 330mm 22 Above Fireplace Opening E Alcove Width 84 2134mm Sidewall to Sidewall Minimum F Alcove ...

Страница 11: ...nsure the paint that is used on the mantel and the facing is high quality or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Combustible Material 2 12 6 4 8 10 13 330mm Standoff Metal Stud On Edge 0 14 Non combustible Facing To Unit Base 1 25mm 22 17 27 10 20 26 Top of Fireplace Opening 559mm 4 Allowable mantel 7 1 8 181mm 10 203mm 13 279mm 1 5 38mm M...

Страница 12: ... as possible The nailing strips can be adjusted back up to 3 1 4 to allow for varying thicknesses in non combustible material wall inishes Nailing Strips INSTALLATION ACCESS PANEL Theunitisequippedwitharemovableaccesspanelforpre inishinstallation of optional components this panel is located on the lower front face 1 Remove 8 screws to remove access panel 2 Easier access to gas connection with pane...

Страница 13: ...t 36 1 4 921mm H Non combustible facing height 17 432mm I Gas Connection Opening Height 2 51mm J Gas Connection Height 4 3 16 106mm K Gas Connection Inset 8 5 16 211mm L Gas Connection Opening Width 3 1 2 89mm Framing depth measurement is noted with the nailing strips set as far forward on the irebox as possible The nailing strips can be adjusted back up to 3 1 4 to allow for varying thicknesses i...

Страница 14: ...th vertical studs and secure using 6 screws 2 at bottom 2 at top and 2 on sides as shown NOTE Ensure the lat side of the steel stud is facing the wood framing 258 025 Flat side out 5 Secure horizontal steel header stud with 2 screws per side as per diagram 6 Slide the unit into position Hook up gas venting electrical and fan if purchased prior to installing the remaining steel studs 7 Secure the l...

Страница 15: ...tion box to the framing at desired location within 10 ft from fireplace 2 Feed the 12 pin connector through the opening at back of junction box 3 Connect the 12 pin connector to the back of the receiver 4 Install the Receiver in the Low Voltage Junction box 5 Insert the 4 AA type batteries in the battery compartment with the correct polarity 6 Place the slider into the cover plate 7 Put the Receiv...

Страница 16: ...high strength compound for the irst coat This product can be found at any hardware store Mud must be cured as per manufacturer s recommendations 6 Prime wall for a second time for proper adhesion of paint 7 Paint walls using a high quality paint which will withstand the high temperatures being emitted from this appliance NON COMBUSTIBLE REQUIREMENTS Installation of the Receiver must be completed b...

Страница 17: ...ase 4 Non combustible material ie tile slate etc may be brought up to and overlap the unit top and bottom ensuring that the maximum thickness does not go beyond the 3 1 4 as shown in the diagram below The faceplate will not be able to be mounted if inished material is beyond 3 1 4 1 Frame in the enclosure for the unit with framing material IMPORTANT The framed opening must be of non combustible ma...

Страница 18: ...required acceptable for a combustible material To obtain the best most durable inish around your ireplace this calls for a high level of care and attention to the preparation and inish around this appliance using only the highest quality materials able to withstand the temperatures produced By following the installation instructions in the manual exactly you will increase your chances of a damage ...

Страница 19: ...tended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 3 91cm above if within 10 3m horizontally 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located on publi...

Страница 20: ... Adjustable Length 3 10 Galvanized N A N A N A 4DAL N A TC 4DLT Adjustable Length 3 10 Black N A N A N A 4DALB N A TC 4DLTB Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A Extension Pipe 8 1 2 Black 46DVA 08AB N A N A N A N A N A Adjustable Length 12 Galvanized N A N A 4D12A N ...

Страница 21: ...4ST14 Snorkel Termination 36 N A N A N A N A N A TM 4ST36 Basic Horizontal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK TM4 HTK Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK TM4 HTK Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK SV FK N A FPI 946 506 P Vent Guard Optional for AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigi...

Страница 22: ...ndicated in the venting arrangements diagrams refer to the following instructions 1 Remove the glass door see instructions in this manual 2 Remove the screws that hold the vent restrictor plate in place 3 Adjust the vent restrictor plate to the required vent restrictor position as per the diagrams shown 4 Once the vent restrictor plate is in the required position secure with screws VENT RESTRICTOR...

Страница 23: ...ow at the lue collar when using rigid venting Note Must use optional rigid pipe adapter Part 510 994 when using Rigid Pipe Venting Systems Maintain clearances to combustibles as listed in Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each loor level and whenever passing through a wall A vent guard should be used whenever the termination is lower than t...

Страница 24: ...T 4 X 6 7 8 These venting systems in combination with the HZ40E Direct Vent Gas Fireplace has been tested and listed as a direct vent heater system by Warnock Hersey Intertek The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in Exterior Vent Termination Locations section Regency Direct Vent Flex System Termination Kits includes all the part...

Страница 25: ...gid Pipe Adaptor in conjunction withDuraventDirect Vent SelkirkDirect Temp Ameri Vent Direct Venting ICC Excel Direct and Security Secure Vent systems Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not afect the Intertek WHI listing of components WARNING Do not combine venting components from diferent venting systems However use of the the AstroCapTM and FPI Riser i...

Страница 26: ...ing the starting 45o elbow at the lue collar when using rigid venting 2 Minimum distance between elbows is 1 ft 305mm Maintain clearances to combustibles as listed in the Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each loor level and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems ...

Страница 27: ...feet with minimum of 11 feet total vertical and maximum 9 feet total horizontal P l e a s e n o t e minimum 1 foot between90o elbows is required A 1 Max 1 Min 3 Max B 2 Max 3 Min 5 Max C 3 Max 5 Min 6 Max D 4 Max 7 Min 7 Max E 5 Max 9 Min 8 Max F 6 Max 11 Min 9 Max H1 H V Horizontal Venting with Two 2 90o Elbows One 90o elbow Two 45o elbows Option H V H H1 With these options maximum total pipe len...

Страница 28: ...s maximum total pipe length is 28 feet with minimum of 12 feet total vertical and maximum 9 feet total horizontal P l e a s e n o t e minimum 1 foot between 90o elbows is required A 2 Min 1 Max 3 Min 4 Max B 3 Min 2 Max 4 Min 5 Max C 4 Min 3 Max 6 Min 6 Max D 5 Min 4 Max 8 Min 7 Max E 6 Min 5 Max 10 Min 8 Max F 7 Min 6 Max 12 Min 9 Max Restrictor Position Set 0 factory setting ...

Страница 29: ...nt Direct Vent American Metal Products Ameri Vent Direct Vent Security Secure Vent ICC Excel Selkirk Direct Temp AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd Dura Vent and Direct Vent are registered and or proprietary trademarks of Simpson Dura Vent Co Inc Pipe Length Vertical Terminal Storm Collar Flashing Ceiling Firestop Adj Pipe Length Vinyl Siding Standoff...

Страница 30: ...n the Clearances section Horizontal vent must be supported every 3 feet Firestopsarerequiredateachloorlevelandwhenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer to the Vent Restrictor Position section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 1 or Set 2 if required Maximum 40 ft ...

Страница 31: ...rminations Section for minimum and maximum heights Required Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit whichcontainsthefollowing Co linear Flex Adapter Outer Pipe Inner Pipe Adapter 510 994 Rigid Pipe Adaptor 46DVA E45 45o Elbow Alternate Approved Caps 46DVA VC Vertical Termination Cap 46DVA VCH High Wind Cap ...

Страница 32: ...ting with Two 2 90o Elbows For additional vertical venting with 2 x 90o elbows refer to Rigid Pipe Venting Arrangements Section One 90o elbow Two 45o elbows Option V H V V1 With these options maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required A 1 Min 4 Max 2 Min B 2 Min 5 Max 3 Min...

Страница 33: ...d B 2 Max 2 Min 4 Max 5 Min C 3 Max 3 Min 5 Max 7 Min D 4 Max 4 Min 6 Max 9 Min E 5 Max 5 Min 7 Max 11 Min Restrictor Position Set 0 factory setting One 90o elbow Two 45o elbows One 90o elbow Two 45o elbows Option V H H1 V V1 A 2 Min 3 Max 4 Min B 3 Min 4 Max 6 Min C 4 Min 5 Max 7 Min D 5 Min 6 Max 8 Min E 6 Min 7 Max 9 Min F 7 Min 8 Max 10 Min Withtheseoptions max total pipelengthis30feetwithmin ...

Страница 34: ...Max 35 Horizontal Distance Feet Vertical Height feet Vent Restrictor Set 2 Vent Restrictor Vent Restrictor Vent Restrictor Set 2 Set 1 16 Max Vent 8 2 4m Min Horizontal Distance Feet Vertical Height feet 2 51mm max 35 36 1 4 921mm 35 10 7m Max Vent Restrictor Set 2 16 Max Vent Restrictor Set 1 Restrictor Set 1 Restrictor Set 2 35 Horizontal Distance Feet Vertical Height feet 2 51mm max Combined mi...

Страница 35: ... adapter over the existing inner and outer lue collar Fasten to the outer collar only with the 3 supplied screws drilling pilot holes will make this easier 4 Level the ireplace and fasten it to the framing using nails or screws through the top and side nailing strips Diagram 1 Note For best results and optimum performance with each approved venting system it is highly recommended to apply Mill Pac...

Страница 36: ...markings on the cap indicating which way is up This will position the termination cap with proper down slope for draining water Fasten the cap to the outer wall with the 4 supplied screws 6 Pull the centre inner and outer lex liner out enough to slip over the lue collars of the ireplace You may wish to cut the liner shorter to make it more workable Do not bend liner more than 90o The liners must s...

Страница 37: ...cedure Four indenta tions located on the female ends of pipes and ittings are designed to slide straight onto the male ends of adjacent pipes and ittings by orienting the four pipe indentations so they match and slideintothefourentryslotsonthemale ends Diagram1 Pushthepipesections completely together then twist lock one section clockwise approximately one quarter turn until the two sections are fu...

Страница 38: ... twist locked position and sealed 5 Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2 The hole shouldbeofsuicientsizetomeettheminimum requirements for clearance to combustibles of 1 1 2 Slip the lashing under the shingles shingles should overlap half the lashing as per Diagram 3 6 Continue to assemble pipe lengths Note If an ofset is necessary in the attic to a...

Страница 39: ... FLEX VENT KIT 946 755 11 Secure inner lex pipe to pipe adaptor by using Mill Pac over the adaptor Slide the inner pipe over adaptor and secure with 3 screws 12 Repeat Step 11 to secure outer lex Diagram 4 14 Put a bead of caulking on the exterior between the outer pipe and lashing to prevent water from penetrating the chimney system 15 Slide storm collar over pipe length until it reaches the lash...

Страница 40: ...NSION KIT PART 946 756 3 wall straps lex adaptor 4 100mm inner pipe 20ft 6 7 8 175mm outer lex pipe 20ft 10 spring spacers 60 1 4 Ceiling firestop 60 1 4 Ceiling firestop Diagram 1 Diagram 1a Enclosure Ceiling firestop Flashing Termination Cap Storm Collar Roof support Ceiling firestop Enclosure Ceiling firestop Flashing Termination Cap Storm Collar Roof support Ceiling firestop irestop A ceiling ir...

Страница 41: ...tighten HIGH ELEVATION This unit is approved for altitude 0 to 4500 ft CAN1 2 17 M91 GAS LINE INSTALLATION Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN CGA B149 installation code For USA installations follow local codes and or the current National Fuel Gas Code ANSI Z223 1 When using copper or lex connectors use only app...

Страница 42: ... System Configuration 886 GTMF Wire Diagram SureFire Switch 885 AC Adaptor CAUTION Labelallwirespriortodisconnection whenservicingcontrols Wiringerrorscancause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges ...

Страница 43: ...front access panel slide all the way back to the back of the two tabs Installation Access Panel 2 Slide the fan through the front access opening push the fan all the way to the back until the fan base engages with the tabs on the bottom of the unit 5 Connect one of the black wires from the power cord to the black wire included with the fan light blue connector Connect the other end to one spade on...

Страница 44: ...the switch on the Fan Control Module to the ON position ON is to the left The O is the off position FCM COM connector TO REMOVE THE FAN 1 Turn the power off 2 Reverse the above instructions Maintenance The sealed bearings are lubricated there is no need to lu bricate them further Extra lubricant will cause more lint and dust buildup causing the bearings to prematurely fail Regular cleaning and vac...

Страница 45: ...y to the unit 2 Remove the faceplate mesh guard enamel panels if installed and the glass door See the manual for detailed instructions 3 Remove the inner panels reverse of Inner panel Installation in the installation manual 4 Remove the burner tray cover by lifting up and out as shown below Prior to removing burner remove crystals pebbles spa stones and inner panels if installed 5 Loosen 3 screws ...

Страница 46: ... with 2 screws Note the right access panel was removed to allow easier access to the right side screw 15 Secure the ground wire from the fan assembly and the power cord to the ground lug located on the back left near the fan 16 The fan control module supplied with the fan kit secures to the side access panel Remove top screw and loosen 2 bottom screws to remove the side access pane 18 Plug in the ...

Страница 47: ...ctor TO REMOVE THE FAN 1 Turn the power off 2 Reverse the above instructions Maintenance The sealed bearings are lubricated there is no need to lu bricate them further Extra lubricant will cause more lint and dust buildup causing the bearings to prematurely fail Regular cleaning and vacuuming of the fan area will add to the life of the motor IMPORTANT These fans collect a lot of dust from within y...

Страница 48: ...White Black Black Ground Fan Fan Proflame System Configuration 886 GTMF Wire Diagram SureFire Switch 885 CAUTION Labelallwirespriortodisconnection whenservicingcontrols Wiringerrorscancause improper and dangerous operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges WIRING DIAGRAM WITH OPTIONAL FAN ...

Страница 49: ...at the white connector shown below The noted wires will be located near the gas valve Disconnect greenTH wire Green Wires White Connector 3 Connect one thermostat lead to female connector using male spade connector see picture below CAUTION Do not wire Thermostat wires to 120V wire 4 Connect the other thermostat lead to male connector disconnected from Step 1 using a female spade connector see pic...

Страница 50: ...scratch or mark the panel on the pilot shield Final Install 3 Remove installed factory panels Loosen 2 screws do not remove on panel clip securing side panel Slide panel clip down away from screws Remove side panel Handling Instructions Black Enamel Panels Black Enamel panels must be inspected for scratches and dimples prior to installation All claims to be recorded at this time Claims for damage ...

Страница 51: ...5 lb Glass 25 Volcanic Stones 2 lb Beads 30 Ceramic Stones or 2 lb Bead 25 Volcanic Stones NOTE Glass Crystals are not supplied with the unit Must purchase separately see quantities above OPTIONAL PEBBLES GLASS CRYSTAL INSTALLATION FOR FIREBOX BASE AROUND BURNER Firebox Around Burner Packages Unit Glass Crystals Fire Beads Pebbles HZ40E 5 lbs 5 lbs 2 packages 6 x bags pebbles There are 2 optional ...

Страница 52: ...and unwrap them The logs are fragile handle with care never force into position 4 Ensure glass crystals are installed on the burner HZ54E 2lbs HZ40E 1 5lbs 5 HZ54E only Remove existing pilot hood replace with pilot hood provided with log set HZ54E existing Pilot Hood HZ54E new Pilot Hood Top View showing both HZ54E HZ40E cut template out along dotted line 6 Clip on the log guides position approxim...

Страница 53: ...red 15 Place Front Left log piece on firebox floor as shown 16 Place Right Log piece on firebox floor as shown 17 If desired install additional crystals on firebox floor in and around installed logs 18 Install lava embers spread evenly over glass HZ54E shown Left Log 2 positioned to match template profile HZ54E shown Completed Install HZ40E shown Completed Install HZ54E shown Left Cross Log 4 positioned ...

Страница 54: ...door simply hook the top door lange onto the top of the unit and swing the door towards the unit Diagram 1 Note Be careful that the glass gasket does not roll up there must be a gap between the gasket and the door lip to ensure that the door sits securely on the unit See Diagram 2 Diagram 2 Diagram 3 Diagram 1 2 With the door in proper position secure with 3 screws in locations shown in Diagram 3 ...

Страница 55: ... 6 tabs in locations shown below 4 Hook the inner door frame 3 and safety screen assembly 2 over the inner door trim 1 5 Bend the center tab up and secure with a screw to attach the inner door frame safety screen assembly to the inner door trim 6 Attach completed assembly to the glass door on unit 7 Secure the assembly with 1 screw on each side 2 3 Tabs 2 Remove screws from inner side of the inner...

Страница 56: ...er inishing materials are used the faceplate may be adjusted out up to 1 2 HZ40E Important 1 2 gap required between faceplate and inished wall 1 When installing required Safety Screen See Safety Screen instal lation instructions 2 Install brackets onto the back of the faceplate 3 screws for each bracket in locations shown below Hook bracket over these tabs Final Install 1 4 1 2 Use irst notch in b...

Страница 57: ...e the irst mounting slot the one closest to the door frame overlay out of the 3 so that the faceplate and door frame overlay are lush with one another NOTE There are 3 mounting slots available this is to accommodate any inishing that protrudes slightly beyond the faceplate Tab on Faceplate Bracket in Unit Note Inner door frame may be installed by itself or with the outer door frame The outer door ...

Страница 58: ... the glass This condensation is normal and will disappear in a few minutes as the glass heats up DONOTATTEMPTTOCLEANTHEGLASS WHILE IT IS STILL HOT DO NOT BURN THE UNIT WITHOUT THE GLASS DOOR IN PLACE FIRST FIRE NORMAL OPERATING SOUNDS OF GAS APPLIANCES It is possible that you will hear some sounds from your gas appliance This is perfectly normal due to the fact that there are various gauges and ty...

Страница 59: ...st approximately 60 seconds If there is no lame ignition rectiication the board will stop sparking for approximately 35 seconds After wait time the board will start second try for ignition by sparking for approximately 60 seconds If there is still no positive ignition the board will go into lock out The system will need to be reset as follows a Turn the system of using ON OFF switch or press ON OF...

Страница 60: ...rvice agency or gas supplier AVERTISSEMENT Quiconque ne respecte pas à la lettre les instructions dans la présente notice risquede déclencher un incendie ou une explosion entraînant des dommages des blessures ou la mort Une installation d ajustement de modification de service ou d entretien peut provoquer des blessures ou des dommages matériels Reportez vous au manuel du propriétaire de l informat...

Страница 61: ... damaged or broken glass WARNING Do not operate the appliance with the glass panels removed cracked or broken Replacement of the glass panels should be done by a licensed or qualiied service person GLASS DOOR Your Regency ireplace is supplied with high temperature 5mm Ceramic glass If your glass requires cleaning we recommend using an approved glass cleaner available at all authorized dealers Do n...

Страница 62: ...e faceplate or door frame see instruction in this manual 5 Remove the inner panels reverse of Inner panel Installation in this manual 6 Remove the burner tray cover by lifting up and out as shown below Prior to removing burner remove crystals pebbles spa stones and inner panels if installed 7 Remove 3 screws on the burner to release it locations shown below 8 Remove the burner by sliding it to the...

Страница 63: ... 007 Pilot Assembly IPI LP 8 258 574E P Valve Assembly HZ40E NG SIT 258 576E P Valve Assembly HZ40E LP SIT 9 910 157 P Replacement Fan Dual Blower 10 258 013 Safety screen Part Description 911 032 10 ft wiring harness 910 572 Wall switch receiver 910 576 Receiver wall plate white 911 037 Flame Sensor 911 038 Flame electrode 910 100 Pilot oriice NG 910 101 Pilot oriice LP 911 039 Pilot Hood 2 way 9...

Страница 64: ...Description 946 775 BlackRelectiveCrystals 946 776 Copper Crystals 946 777 Starire Crystals 946 672 Natural River Pebbles 946 674 Ceramic Spa Stones 946 710 Volcanic Stones Slate Grey 946 711 Volcanic Stones Ivory Tan 1 pound bag of glass crystals Part Description 946 675 Black Relective Crystals 946 676 Copper Crystals 946 677 Starire Crystals 258 900 Steel Stud Framing Kit 5 pound bag of irebead...

Страница 65: ...Regency Horizon HZ40E 10 Gas Fireplace 65 65 notes ...

Страница 66: ... Blowers Blower Control Module Battery Pack Remote Control Systems 2 Enamel Panels 1 Venting Venting Components 1 All Stainless steel surrounds 1 All Firebox Media Crystals Firebeads Volcanic Ceramic Spa Stones 1 All hardware 1 Mesh Glass Safety Barriers 1 Accent Light Bulbs 1 Glass Crazing 1 Conditions Warranty protects against defect in manufacture or FPI factory assembled components only unless...

Страница 67: ...ot limited to cap size or type operator error abuse misuse use of improper fuels lack of regular maintenance and upkeep acts of God weather related problems from hurricanes tornados earthquakes floods lightning strikes bolts or acts of terrorism or war which result in malfunction of the appliance are not covered under the terms of this Limited Lifetime Warranty FPI has no obligation to enhance or ...

Страница 68: ...heir local provincial or naional legal codes for addiional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the authorized selling dealer to obtain warranty service In the event the authorized selling dealer is unable to provide warranty service please contact FPI by mail at the address listed below Please include a brief descripion of the prob...

Страница 69: ...low in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Product Model required Dealer Details Dealer Name required Dealer Address Dealer Phone Installer Date Installed mm dd yyyy Your Contact Details required Name Address Phone Email For purchase...

Страница 70: ......

Страница 71: ......

Страница 72: ...Dealer Name Address ______________________________________________ ___________________________________________________________________ Installer ___________________________________________________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No _________________________________________________...

Отзывы: