Regency FG38 FireGenie Freestanding Gas Stove
7
INSTALLATION
GAS CONNECTION
The gas line should be rigid pipe. Copper may
also be used if approved by AS5601-2004.
The gas connection at the valve is 1/2 male.
For minimum and maximum supply pressure
see the System Data Table.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1)
Make sure the valve is in the "OFF" position.
2)
Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure tap(s), turning counterclockwise
with a 1/8" wide fl at screwdriver.
3)
Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4)
Seal and or check the pilot outlet (# 8)
5)
The pressure check should be carried out
with the unit burning and the setting should
be within the limits specifi ed on the safety
label.
6)
When fi nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" fl at
screwdriver.
Screw should be snug, but do
not over tighten.
S.I.T. Valve Description
1)
On-Off Solenoid Valve EV1
2)
On-Off Solenoid Valve EV2
3)
Inlet Pressure Test Point
4)
Outlet Pressure Test Point
5)
Connection for Pressure Regulator /
Combustion Chamber Compensation
6)
Pressure Regulator for Minimum and
Maximum Outlet Pressure
7)
Gas Outlet Pressure Electric Modulator
8)
Pilot Outlet
9)
Main Gas Outlet
10)
Side Outlet
11)
Main Gas Inlet
FG38-NG: For 0 to 610 meters altitude
FG38-LPG: For 0 to 610 meters altitude
Burner Inlet Orifi ce Sizes:
NG
LPG
Burner
#33
#52
Max. Input
NG
38
mj
LPG
31
mj
Min. Input
NG
20.8
mj
LPG
16.1
mj
Supply Pressure
NG
1.13
kPa
LPG
2.75
kPa
Manifold Pressure
NG
0.87
kPa
LPG
2.65
kPa
Electrical: 240 V. 50Hz.
Circulation: High/Off/LO speed fan, 150/89
CFM.
Log Set: Ceramic fi ber, 7 per set.
Aeration Setting
NG 15
mm
LPG 6.4 mm
Flue Restrictor Setting
NG Full
Open
LPG Full
Open
System Data
FG38
EV1
EV2
R.Q.
ADJ.
P.OUT
MD
4
3
2
1
Pin
11
8
9
10
1
2
3
4
6
7
5