Regency FG38 FireGenie Freestanding Gas Stove
INSTALLATION
CLEARANCES TO
COMBUSTIBLES
The clearances listed below are MINIMUM
distances. Measure the clearance to both the
appliance and the chimney connector.
(The far-
thest distance is correct if the two clearances
do not coincide.)
For example, if the appliance
is set as indicated in one of the fi gures but the
connector is too close, move the stove until the
correct clearance to the connector is obtained.
This unit can be installed on a solid combustible
surface like a wood fl oor. This unit can also be
installed directly on carpeting or vinyl when
the bottom pedestal cover plate (provided with
unit) is installed.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
Use the minimum clearances shown in the
diagrams below for all installations.
FG38-NG & FG38-LPG
Reference Dimensions
C Back Wall to Flue Centerline 10-3/4" / 273
mm
D Side Wall to Flue Centerline 20-1/2" / 520
mm
F Side Wall to Flue Centerline 11" / 280 mm
Clearances
A Side Wall to Unit
7-1/2" / 190 mm
B Back Wall to Unit
6" / 155 mm
E Side Wall to Unit
2" / 50 mm
M i n i m u m c e i l i n g
height is 36" / 914
mm from top of unit.
If further reduced clear-
ances are needed, ob-
tain requirements for
construction of a pro-
tected wall from your
local building authori-
ties and their allowable
reductions of the listed
clearances.
DRAFT DIVERTER
This heater has a draft diverter built in. It must
not be altered, obstructed, or blocked in any way,
and the unit must be installed so that the draft
diverter is in the same atmospheric pressure
zone as the combustion air inlet to the burner.
This heater must be properly connected to a
fl ueing system.
WARNING: Operation of this heater when not
connected to a properly installed and main-
tained fl ueing system can result in carbon
monoxide (CO) poisoning and possible death
.
FLUEING
This heater is a fl ued appliance and must be
connected to a chimney/fl ue in accordance with
the installation codes.
Note:
The rear pedestal cover plate must
always be fi tted for safety. Electrical
connections inside.
Flueing Requirements
A100 mm diameter fl ue is required. For cosmetic
or aesthetic purposes 6" outer fl ue can be used
as long as an approved inner fl ue is installed.
Fasten but do not penetrate the inner sleeve
ofthe fl ue when tightening the screw.
The minimum fl ue required is 3.3m from fl oor
level.
Follow all fl ueing manufacturer’s requirements
and local building codes or AS5601-2004.
14)
This unit can be installed on a solid com-
bustible surface like a wood fl oor as well as
on carpeting.
INSTALLATION
CHECKLIST
1)
Check Clearances to Combustibles, page
6.
2)
Install fl ueing, page 6.
3)
Make gas connections, page 7.
4)
If necessary, convert NG to LPG on page
8.
5)
Test Gas Pressure, page 7.
6)
Install log set where indicated on page 9.
7)
Install Front Door, page 11.
8)
Test
for
fl ue spillage (draft test), page 11.
9)
Install Remote Control, page 12.
10)
Final check, page 12.
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi r-
ing correctly and operation fully explained to
customer.
This includes:
1)
Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2)
If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning or that results in
damage is not the responsibility of the manu-
facturer.