CB40E Gas Fireplace

MANTEL CLEARANCES CB40E (3 SIDED)

Due to the extreme heat this fireplace emits, the 

mantel clearances are critical. 

Combustible mantel 

clearances from top of front facing are shown in the 

diagram on the right.

Note:  Ensure the paint that is used on the mantel 

and the facing is "high quality" or the paint 

may discolour.

MANTEL LEG CLEARANCES

Combustible mantel leg clearances as per diagram:

Combustible Material

2

12

6 4

8

10

Standoff

Wood Stud

(On Edge)

0

14

9”

15-1/16”

10

20

26

Top of

Fireplace

Opening

12" (305mm)

Drywall, wood, wood panel, etc.

2”

To 

Bottom

of 

Fireplace 

Lip

12"

MANTEL LEG

8-1/2"

CB40E (3 sided)

Содержание City Series CB40E Series

Страница 1: ... 4500 ft 42 DMS 53 DMS Minimum Input Altitude 0 4500 ft 0 1372m 15 500 BTU h 4 54 kW 15 500 BTU h 4 54 kW Maximum Input Altitude 0 4500 ft 0 1372m 28 500 BTU h 8 33 kW 28 500 BTU h 8 33 kW Vent Sizing 4 Inner 6 5 8 Outer 4 Inner 6 5 8 Outer 48 7 16 1231mm 25 9 16 648mm 37 3 8 949mm 43 1091mm 33 7 16 849mm 7 1 4 183mm Ø 4 102mm Ø 6 3 4 171mm 11 7 16 291mm 24 1 4 616mm 49 5 8 1261mm 18 11 16 475mm 1...

Страница 2: ...lcove Depth 36 914mm Front of Unit G To Enclosure Ceiling min max 0 3 76mm From top of enclosure H Convection Air outlet 120 sq inches min Top front or side of enclosure I Enclosure Depth min 19 483mm Minimum inside dimensions J Opening Height 15 1 16 383mm Bottom Top of Fireplace Opening K To Ceiling min All 3 sides 1 1 2 To Top of Ceiling L Chase Enclosure min 63 1600mm From base of unit floor H...

Страница 3: ...o ceiling with top opening Low framing with vents in front sides or top Full framing with low vents in front or sides Full framing with vents in front or sides K C I A1 A D L J H B L I C D A1 A J G G H H H B I C G A A1 G D J L H H B I B A D C J G G L H H ...

Страница 4: ...escription CB40E A Framing Height 37 3 8 949mm B Framing Width 48 1 2 1232mm C Framing Depth 19 483mm D Minimum Height to Combustibles 63 1600mm G Vent Centerline Height 56 1 4 1429mm I Gas Connection Opening Height 2 51mm J Gas Connection Height 4 106mm K Gas Connection Inset 13 330mm L Gas Connection Opening Width 3 1 2 89mm Note A combined minimum of 120 square inches of open area is required f...

Страница 5: ...agram on the right Note Ensure the paint that is used on the mantel and the facing is high quality or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Combustible Material 2 12 6 4 8 10 Standoff Wood Stud On Edge 0 14 9 15 1 16 10 20 26 Top of Fireplace Opening 12 305mm Drywall wood wood panel etc 2 To Bottom of Fireplace Lip 12 MANTEL LEG 8 1 2 CB40E ...

Страница 6: ... two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adapter Part 510 994 when using Rigid Pipe Venting Systems Maintain clearances to combustibles as listed in Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the termination is lower than the specif...

Страница 7: ...eet otherwise rigid venting must be used HORIZONTAL VENTING WITH TWO 2 90O ELBOWS One 90o elbow Two 45o elbows Option V H H1 With these options maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required A 1 Min 2 Max B 2 Min 4 Max C 3 Min 5 Max D 4 Min 6 Max E 5 Min 7 Max F 6 Min 8 Max Res...

Страница 8: ... every 3 feet Firestopsarerequiredateachfloorlevelandwhenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer to the Vent Restrictor Position section for details on how to change the vent restrictor from the factory setting of Set 0 through to Set 3 if required NOTE A minimum of 1 305mm vertical off the top of the unit is required b...

Страница 9: ...re required at each floor level and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Vertical Venting with Three 3 90o Elbows One 90o elbow Two 45o elbows V H1 H V1 Option V H H1 V V1 With these options max totalpipelength is 30 feet with min of 10 feet total vertical and max 8 feet total horizontal Please note min 1 foot between ...

Страница 10: ... the bottom edge of the ventilated fireplace chase opening The TV may be recessed into a wall as shown below This can only recess into the chase opening a maximum of 3 1 2 inches and must be a minimum of 12 inches from the fireplace lip to the first stud To achieve a maximum of 3 1 2 recess the wall must be of a maximum of 2 as shown TV RECESSED INTO WALL The TV cannot be any lower than this finis...

Отзывы: