Manual
– TopCon TC.LAE
Appendix
53 / 56
2016-06-08
9.3.2.
Weight
Device variants
Device total weight
Standard device
1
~25 kg
Tab. 15
Information on the device weight.
1
Full filled with coolant glycol ethylene 30%
9.3.3.
Liquid cooling
– interface
For further information about the Liquid cooling interfaces,
refer to chapter 5.2, page 22.
9.4. Technical data
– electrical
For further information on the technical data, see device data sheet.
9.4.1.
Cross-section
– Cable connections AC line
Terminal connection via cable ferrules
Regatron recommends attaching cable ferrules at the connection cables
for the plugs at the interface AC line.
1
2
3
a
d
Fig. 33
Cable connections
– AC line.
Cable types:
-1-
Flexible,
-2-
Rigid,
-3-
Ferrule
Pay attention to the cross-section of the line A:
π * d
2
/ 4.
The mechanical specifications about cross-section and the required
stripping length for the according connector types can be found in the
following tables.
AC line X10
Cross-section A
Stripping
length a
[mm]
Tightening
tourge
1
[Nm]
[mm
2
]
[AWG/kcmil]
1
Flexible
0.20 … 4
24 … 10
7
0.5 … 0.6
2
Rigid
0.20 … 4
3
Ferrule
0.25 … 4
Tabelle 16
Cable connections AC line
– Mechanical specifications.
1
Recommend torque at the cable connection via mounting screws.
2
1 kcmil
≙
0,5067 mm²