FEATURES AND PROTECTION

INTRODUCTION

This section describes how the regulator functions and explains its operating features. Regulator

 

functions are illustrated in the block diagram of Figure 4-1. 

Before proceeding forward, carefully read and fully understand the warnings, cautions, & safety notice statements in this manual. Failure to do so could 
cause severe injury, death, and/or equipment damage.

DVR® REGULATOR FUNCTION BLOCKS

The following paragraphs describe each of the function blocks, inputs and 
outputs.  Refer to Figure 4-1. 

Generator Voltage
Generator voltage is measured at terminals E1 (A-phase), E2 (B-phase), 
and E3 (C-phase), for ABC rotation, or E1 (C-phase), E2 (B-phase), and 
E3 (A-phase) for CBA rotation. Nominal voltages of up to 600Vac may be 
sensed at these terminals. Voltage applied to these inputs is scaled, condi-
tioned and applied to the controller. 

Line Currents
Generator line currents (IA, IB, IC) are measured via CTs at connectors  
P1 and P2. Current up to 5 Arms may be monitored at these terminals. 
These currents are scaled, conditioned and applied to the controller. Refer 
to 

Section - Specifications

, for connector pin assignments.  

Field Current 
Current through the exciter field winding is measured at terminal F+. Field 
current is scaled, conditioned and applied to the input of the controller.

Contact Input Circuits
Nine contact input circuits powered from an internal 3.3 Vdc supply pro-
vide input control from user-supplied contacts: UP, DOWN, DROOP_OFF,  
EXCITATION_OFF, VAR/PF_OFF, *PS0, *PS1, *DVR_RESET and *VM 
(*2500 only) 

UP
Closing the UP contact across terminals P1-7 (UP) and P1-11 (DG) causes 
the active operating set point to increase. 

DOWN
Closing the DOWN contact across terminals P1-8 (DN) and P1-11 (DG) 
causes the active operating set point to decrease.  

Keeping either contact closed will continue to increase (UP) or decrease 
(DOWN) the operating set point until a limit is reached. The limit is de-
termined by the Maximum External Contact Adjust field of DVRPortal™ 
software. The effect generated by the contacts is displayed in DVRPortal™ 
software on the Set Points Tab as the value “Contact Offset.”

Analog

Input

Power

Input

Stage

Power

Supply

Power 

Amplifier 

Stage

Contact

Inputs

Controller

Fault

Output

Contact

CAN

Port

USB 2.0

Port

HMI

Interface

RTD

Module

Exciter Field

Input 

Power

Generator Sensing

Exciter Field Sensing

Auxiliary Input

Up

Down

Droop Off

ExcitaKon Off

VAR/PF Off

Reset

PS0

PS1

VM

BaOery 

Power

Eight 3-wire 

RTD’s

Shunt Module

Figure 4-1. Simplified Block Design

Содержание Marathon Generator DVR 2400

Страница 1: ...er and input power supplies before installing or servicing voltage regulator Use a voltmeter to verify that power is off before contacting conductors Do not open terminal box or touch unprotected term...

Страница 2: ...s 6 FEATURES AND PROTECTION Introduction 7 Function Blocks 7 Operating Features 9 Regulation Modes 9 Auxiliary Input 10 Load Sharing 11 Generator Soft Start 11 Protection Functions 12 INSTALLATION Gen...

Страница 3: ...ulation True RMS Three phase or single phase generator voltage sensing True RMS current sensing single phase on the 2400 three phase on the 2500 optional CT s required True RMS power metering single p...

Страница 4: ...0 P2 10 DG 2500 PS1 Presets P2 8 PS1 P2 10 DG 2500 FAULT CONTACT OUTPUT Type Form C Carry Current 7 Aac 5 Adc continuous Break Current 7 Aac 0 1 Adc Operating Voltage 240 Vac 30 Vdc maximum Terminals...

Страница 5: ...to P1 4 AU FCR regulation Current Range 4 mA to 20 mA Set Point Range 0 000 Adc to 4 000 Adc Increment 1 mA per 2 0 uA Burden 250 Terminal P1 4 AU P1 5 AU Jumper P1 3 A_L to P1 4 AU Dynamic Under Fre...

Страница 6: ...c standards Emission standard for industrial environments Electromagnetic CompatibilityTests Immunity Electrostatic Discharge ESD IEC 61000 4 2 Radiated RF IEC 61000 4 3 Electrical FastTransient EFT B...

Страница 7: ...currents are scaled conditioned and applied to the controller Refer to Section Specifications for connector pin assignments Field Current Current through the exciter field winding is measured at termi...

Страница 8: ...egulation when the generator is paral leled to utility Opening the VAR PF_OFF contact across terminals P1 10 QPF and P1 11 DG enables VAR or PF control Closing the contact dis ables VAR or PF regulati...

Страница 9: ...DB25 cable Refer to Section Auxiliary Modules for more information about RTD protection configuration Fault Output Contact A fault output contact is provided through terminals P1 12 P1 13 and P1 14 Th...

Страница 10: ...scale factor is disabled in FCR mode Note Any field current reference less than 0 000 Adc will become 0 000 Adc Example The application of a 1 25 Vdc signal will result in a field current of 1 250 Adc...

Страница 11: ...SHARING Note The machine nameplate rated power rated power factor CT Ratio and PT Ratio if applicable MUST be entered to calculate the proper rated reactive power for the droop reference The regulator...

Страница 12: ...0 S A013 F013 Generator Under voltage Yes 5 0 to 50 0 0 0 5 0 Voltage Set point 1 0 to 15 0 S A012 F012 Generator Voltage Imbalance No AVR1 Not Enabled AVR3 Difference of Max Min Line line voltage 20...

Страница 13: ...VAR PF_OFF Inactive AND EXC_OFF active in RUN P state N A N A F003 Table 4 3 CONFIGURABLE ALARMS Alarm Customer Disable Enable Alarm Variable AlarmThreshold Range Reset Hysteresis Threshold Units Time...

Страница 14: ...ulator Field Over Excitation Shutdown The Field Over Excitation protection feature is triggered if the field current exceeds the threshold The fault is triggered if the field current doesn t fall belo...

Страница 15: ...eshold A fault is triggered if the regulator temperature exceeds a factory default shutdown threshold Generator Parallel Start Up Shutdown The Generator Start Up Shutdown protection feature is trigger...

Страница 16: ...urrent is limited to the Field Current Limit value which can be configured through DVRPor tal software The portal displays this alarm condition no HMI indication Power Limiting Alarm The Power Limit p...

Страница 17: ...nsed current is below the alarm threshold the auxiliary bias will be set to zero Non Configurable Protection Alarms Loss of RTD Element Open Alarms The loss of RTD element open alarm is triggered if t...

Страница 18: ...al injury death and or property damage OVERSPEED HAZARD Do not exceed the rated speed of the generator Excessive centrifugal forces could damage the rotating fields and cause parts to be expelled at a...

Страница 19: ...ation Operation and Maintenance Manual SB0056E Revised November 2018 Regal Beloit America Inc 100 East Randolph Street Wausau WI 54402 8003 www regalbeloit com Brands Marathon Generators Figure 5 1 Th...

Страница 20: ...llation Operation and Maintenance Manual SB0056E Revised November 2018 Regal Beloit America Inc 100 East Randolph Street Wausau WI 54402 8003 www regalbeloit com Brands Marathon Generators Figure 5 2...

Страница 21: ...tallation Operation and Maintenance Manual SB0056E Revised November 2018 Regal Beloit America Inc 100 East Randolph Street Wausau WI 54402 8003 www regalbeloit com Brands Marathon Generators Figure 5...

Страница 22: ...ad to the ground bus from each device The DVR voltage regulator connections are dependent on the application The 2400 2500 Connectors The 2400 2500 regulators have five types of interface connectors 1...

Страница 23: ...cables IOGEAR GUE2118 39 feet is recommended for longer dis tances with the DVR2400 2500 voltage regulators The regulator may need to be externally powered for proper communication Refer to the sectio...

Страница 24: ...rminated to chassis as close to the regulator as possible Power Supply Inputs 3 and 4 Power input terminals are labeled 3 and 4 Generator Voltage Sensing Inputs E1 E2 and E3 The generator voltage sens...

Страница 25: ...rands Marathon Generators Sensing Phase CT X1 Terminal CT X2 Terminal 3 Phase DVR 2500 regulator only A P2 1 IA1 P2 2 IA2 B P1 1 IB1 P1 2 IB2 C P2 3 IC1 P2 4 IC2 1 Phase B P1 1 IB1 P1 2 IB2 Table 5 2...

Страница 26: ...Contact output normally closed Table 5 3 Connector P1 Terminals Pin Number Terminal Name Name Description 1 IA1 CT A1 Generator Phase A CT terminal 1 2 IA2 CT A2 Generator Phase A CT terminal 2 3 IC1...

Страница 27: ...X_IN AUX_IN and AUX_LOOP This input allows a user to control the regulator with an auxiliary piece of equipment by connecting a voltage source to P1 4 AU and P1 5 AU The regulator can also be configur...

Страница 28: ...rrent sensing Figure 5 8 shows an application where the regulator is connected for three phase voltage sensing and three phase current sensing Figure 5 9 shows an application where the regulator is co...

Страница 29: ...ed to be shorted for Auxiliary 4 20 mA control 5 Normally Open NO Normally Closed NC contact closes opens in a fault condition 6 Genset battery may be connected to keep the 2500 powered on for control...

Страница 30: ...to be shorted for Auxiliary 4 20 mA control 5 Normally Open NO Normally Closed NC contact closes opens in a fault condition 6 Genset battery may be connected to keep the 2500 powered on for control a...

Страница 31: ...ssible in this configuration 4 Analog signal input when Auxiliary is configured for control A_L and AU need to be shorted for Auxiliary 4 20 mA control 5 Normally Open NO Normally Closed NC contact cl...

Страница 32: ...ry is configured for control A_L and AU need to be shorted for Auxiliary 4 20 mA control 5 Normally Open NO Normally Closed NC contact closes opens in a fault condition 6 Genset battery may be connect...

Страница 33: ...6E Revised November 2018 Regal Beloit America Inc 100 East Randolph Street Wausau WI 54402 8003 www regalbeloit com Brands Marathon Generators Figure 5 11 Cross Current Reactive Differential Connectio...

Страница 34: ...shutdown mode indicated by rUn i F011 on the display 5 At this time initial adjustments can be made If adjusting via the HMI see Section Making Settings Changes If adjusting via the DVRPortal communi...

Страница 35: ...ists of four buttons and a four character LED display as illustrated in Figure 6 1 The display indicates status conditions and parameter settings Button function descriptions are given in Table 6 1 Bu...

Страница 36: ...mally and is in stand by mode waiting for the STRT state STRT This display indicates that the regulator is in a Soft Start State RUN V This display indicates that the regulator is operating normally w...

Страница 37: ...point Adc in FCR mode 0 to 100 VAR set point of rated VAR in VAR mode 0 60 to 0 60 PF set point PU in PF mode UFrQ 40 0H to 70 0H Under frequency knee Hz SLoP 1 00U to 5 00U Under frequency slope mult...

Страница 38: ...6 3 If no button is pressed within 60 seconds the display will return to STA TUS mode 3 Press the ENTER button to place the HMI into EDIT mode In EDIT mode the HMI will display the current value of th...

Страница 39: ...provides termination points for up to eight 3 wire 100 Ohm Platinum RTDs The RTD wires are terminated via PCB mounted screwless spring clamp con nectors The RTD module and DVR 2500 regulator are inte...

Страница 40: ...re to the regulator RAM Undo Pressing this button displays the values just prior to the last edit in the currently active tab of the DVRPortal software These values can then be sent to the regulator R...

Страница 41: ...EPROM by pressing the Save to EEPROM button Notes 1 The regulator needs to be in Standby Mode to load configurations 2 When a file is transferred from a computer to the regulator the op erating status...

Страница 42: ...d When the Generator tab is active default the values displayed correspond to the generator output termi nals primaries of potential and current transformers When the Regulator tab is active the value...

Страница 43: ...tes this mode has been selected The apparent power is calculated just as in Normal mode The real and reactive powers are created with the simulated power factor This is intended as a diagnostic mode t...

Страница 44: ...displayed with gray numbers in the panel below the pull down menu Selecting the appropriate frame size chooses appropriate proportional integral and de rivative gain values These gain values are not e...

Страница 45: ...tering of all three phase currents inde pendently This sensing mode should only be selected when using three current transformers This is only available on the 2500 One B Only is used for metering of...

Страница 46: ...the basis for these protections Regulation Set Points 4b This panel contains the editable fields for selecting the regulator set point for the various regulation modes and the frequency characteristic...

Страница 47: ...ted as Dynamic Slope 2500 only the UF Slope setpoint field will be locked as this register dynamically updates with the applied AUX voltage Aux Control Scale Factor is used when the auxiliary input po...

Страница 48: ...age related to that protection feature Refer to Section 4 for detailed description of these protections Enable Disable 5b The panel contains enable disable options for all protections Most of these ca...

Страница 49: ...nt of time taken to ramp to the desired voltage at the generator output terminals in AVR1 and AVR3 regulation modes Refer to Section Features and Protection for a detailed description of the Generator...

Страница 50: ...gulator is stand by mode b Connect to regulator through the DVRPortal software c Set Preset Edit Mode to Enable d Select the preset that you would like to edit 6b e Navigate through various tabs and m...

Страница 51: ...h the regulator will initiate voltage soft start The HMI and DVR regulator will show START as a status indicator during the soft start Run Cut Out Hysteresis This is the speed at which the regulator s...

Страница 52: ...priority Electronic Control Unit that the DVR regulator will respond to Note The ECU addresses can all be assigned to the same control unit They should only be different if the regulator needs to comm...

Страница 53: ...ersion and settings version It also contains editable fields for custom tags Serial Number is the serial number of the regulator Software Version is the version of regulator firmware Settings Version...

Страница 54: ...ulator does not malfunction as reading events is memory intensive Save all Events button lets you export events data from the portal to a CSV file This allows users to share event log data The check b...

Страница 55: ...y death and or property damage DO NOT DISASSEMBLE Only qualified personnel who know local national international and or other applicable codes rules or regulations and sound practices should install o...

Страница 56: ...operating in under frequency region Verify the regulator under frequency knee is set to correct value and change if necessary Verify correct generator speed Is the regulator regulation mode correct V...

Страница 57: ...ecessary Is Aux Input influencing set point Monitor Aux Input Offset Turn off Aux Input if not needed yes check check check check check TROUBLESHOOTING FLOWCHART GENERATOR VOLTAGE NOT STABLE Is Aux In...

Страница 58: ...th known kW Correct as necessary check Is Under Excitation threshold too low Check Under Excitation threshold and adjust as necessary check A006 ALARM Check address priority and timing parameters and...

Страница 59: ...ULT Are Aux Input UP DOWN Droop and or CAN influencing set point Monitor effect of Aux Input UP DOWN Droop and CAN Offsets on Total Set Point Adjust settings as needed check Is Under Voltage threshold...

Страница 60: ...io and adjust as necessary Is PT if used ratio correct check Is Droop function enabled Check CT polarity Correct if necessary yes Check physical markings on CTs or compare DVRPortalTM software power m...

Страница 61: ...r load balanced Check line currents for balance with DVRPortalTM software Redistribute load if possible check have matching Check PT nameplates check Inspect exciter per generator manual Is generator...

Страница 62: ...er Excitation A009 Unused A010 Unused A011 Loss of Auxiliary Current Sensing A012 Generator Under Voltage A013 Generator Over Voltage A014 Generator Reverse Power Flow A015 Generator Under Frequency A...

Страница 63: ...inal Description GND Protective earth ground 4 PMG terminal 1 Fused 3 PMG terminal 2 Fused E1 Generator armature Phase A E2 Generator armature Phase B E3 Generator armature Phase C UNUSED UNUSED F Exc...

Страница 64: ...disable contact input active closed 10 QPF VAR PF mode disable active closed 11 DG Digital ground 12 NO Contact output normally open 13 COM Contact output common 14 NC Contact output normally closed...

Страница 65: ...LOP 8 Press SELECT The word PR will appear in the display Press ENTER Use the UP and DOWN arrows to select the nameplate Power Rating in kW and then press ENTER The entered value will flash 3 times to...

Страница 66: ...T Current Transformer DC Direct Current ECU Electronic Control Unit EEPROM Electrically Erasable Programmable Read Only Memory FCR Field Current Regulation g Gram G Unit of gravitational acceleration...

Страница 67: ...500 Digital Voltage Regulator Installation Operation and Maintenance Manual SB0056E Revised November 2018 Regal Beloit America Inc 100 East Randolph Street Wausau WI 54402 8003 www regalbeloit com Bra...

Страница 68: ...cope of the technical and application information included in this publication is necessarily limited Unusual operating environments and conditions lubrication requirements loading supports and other...

Отзывы: