Error Messages and Troubleshooting
66
Maintenance
REFUsol 20K...33K-2T
982079 | 05 | 2021-03
7.1 Maintenance
7.1.1 General Warnings
7.1.2 Maintenance Intervals
* Shorter maintenance intervals may be required
(depending on location and environmental conditions).
The maintenance intervals are manufacturer
recommendations and may need to be shortened in extreme
environmental conditions.
DANGER
High voltage
Danger to life due to high voltages in the live
components of the inverter, which can cause fa
-
tal electric shocks.
▸
All work on the product must be carried out
by qualified electricians only.
▸
Always disconnect the inverter before work
-
ing on it and observe the five safety rules (see
chapter 2.9).
▸
Observe the discharge time of 5 minutes.
CAUTION
Hot surfaces
Risk of burns due to hot surfaces.
The product can get hot during operation.
▸
Avoid contact during operation.
▸
Allow the product to cool down sufficiently
before carrying out any work.
Measures to be implemented
Interval
Cleaning the fan grilles (33K-2T only).
12 months*
Check the fans for function and operating
noise.
12 months
Visual inspection of the inverter housing, all
rubber seals and cable glands.
12 months
If necessary, clean the inverter with a dry or
slightly damp cloth.
12 months
Visual inspection and, if necessary, cleaning of
the heat sink.
12 months