Installation
41
Connect Communication
REFUsol 20K...33K-2T
982079 | 05 | 2021-03
En
gl
is
h
D
eu
ts
ch
4.11 Connect Communication
REFUsol 20K...33K-2T
are equipped with an Ethernet
interface as standard.
Device information (yield data, error messages,
alarms, operating status) of the inverter is transmitted
to the REFUlog monitoring portal via Ethernet or
optionally via WiFi.
▷
For a communication connection (Ethernet, RS485
and digital inputs) use a shielded network cable
with an outer diameter of 4.5 mm to 7.5 mm.
▷
To avoid communication interference, lay commu
-
nication cables away from live lines and sources of
interfe-rence.
▷
The length of the communication cable should be
less than 1000 m.
4.11.1Connect RS485 Communication
1. Remove the RS485 and digital input cover on the
inverter.
2. Slightly loosen the union nut of the PG screw con
-
nection.
3. Remove the blind plug from the PG gland and feed
the shielded network cable through the cable gland
and seal.
4. Use a crimping tool to assemble the network cable
with an RJ45 plug. Make sure that the PIN assign
-
ment is correct.
Pin Colour
RS485 function
1
white and orange RS485
B-
, RS485 differential signal-
2
orange
RS485
A-
, RS485 differential
3
white and green RS485
A-
, RS485 differential
4
blue
RS485
A-
, RS485 differential
5
white and blue
RS485
B-
, RS485 differential signal-
6
green
RS485
B-
, RS485 differential signal-
7
white and brown NC
8
brown
NC