Installation
38
Connect AC Cable
REFUsol 20K...33K-2T
982079 | 05 | 2021-03
4. If necessary, protect the potential equalisation con
-
nection against corrosion.
4.9 Connect AC Cable
Tab. 5:
AC fuse and minimum cross-sections of the AC
cables
* The conductor cross-sections shown in the table are minimum re
-
quirements. For longer cable lengths, the conductor cross-sections
must be designed accordingly.
1. Remove the AC cover with a Phillips screwdriver.
2. Loosen the union nut and remove the blind plug of
the cable gland.
3. Strip the conductors of the AC cable according to
the following illustration.
4. Attach the union nut to the PG cable gland.
5. Feed AC cable through PG cable gland and AC cover.
6. Insert the conductor into the M6 crimping cable lug
and crimp it with a crimping tool.
Type
REFUsol 20K-2T
REFUsol 33K-2T
Conductor cross
section*
≥ 10 mm²
≥ 16 mm²
Fuse
40 A
63 A
55 mm (PE)
12
12
45 mm
(L1, L2, L3, N)