![REFUSOL 20K-2T Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/refusol/20k-2t/20k-2t_operating-manual_1432921014.webp)
Technical Description
14
Connection Requirements
REFUsol 20K...33K-2T
982079 | 05 | 2021-03
3.3 Connection Requirements
The following points are to be considered when
planning the infrastructure:
∘
The
REFUsol 20K...33K-2T
can feed into the low-volt
-
age grid and the medium-voltage grid.
∘
The power supply line must be equipped with an ap
-
propriate AC disconnecting device.
∘
The
REFUsol 20K...33K-2T
is not equipped with inter
-
nal potential isolation.
∘
If connected with the medium-voltage-grid, it must
be operated with electrically isolating transform
-
ers.
∘
The transfomer must be selected according to the
specific site of use and the relevant regulations
must be taken into account: Hazardous substances
ordinance, ordinance on installations for handling
substances hazardous to water, chemicals prohibi
-
tion ordinance, technical instructions for noise pro
-
tection, and regional building regulations.
∘
The
REFUsol 20K...33K-2T
has 2 independent MPP
trackers. All PV modules connected to the same
MPPT should be of the same type and have the same
orientation.
∘
When planning the system, selecting operating
equipment, installation, commissioning and com
-
Additional required
equipment
at low voltage
network
at medium
voltage net
-
work
DC load break switch integrated
1)
1)
Local regulation might require an additional DC switch at a external DC
combiner box.
integrated
1)
AC load break switch necessary
necessary
Central grid protec
-
tion device with sec
-
tion switch
(VDE-AR-N 4105,
VDE-AR-N 4110)
necessary
necessary
LV-/MV-Transformer not necessary
necessary
Specification of medium voltage transformer
Mains transformer according to EN 50588-1
Switching group
Dyn5 or Dyn11
Содержание 20K-2T