Troubleshooting
51
Error List
REFUsol 100K
982059/02
2020-11
En
gl
is
h
D
eu
ts
ch
11 Troubleshooting
11.1 Error List
Error Code Message
Description
Instructions
11005
Isolation Error
An insulation fault was detected during the
self-test before grid connection.
▸
Check measured value and limit value in
REFUset.
▸
Check the installation of the inverter.
▸
Check PE connection.
▸
Check for faulty cables (e.g. damaged insu
-
lation).
▸
Check solar generator installation.
70004
Safety Relay Broken
The self-test of the safety relays could not be
completed successfully.
▸
Open and close the DC switch.
▸
If this error occurs more than once, contact
REFU Service.
70005
Relay Test Bad Comm1
The self-test of the safety relays detected a
communication problem.
70006
Relay Test Bad Comm2
70007
Relay Test Bad Comm3
70008
Relay Test Bad Comm4