Controller
Variomat 1 — 06.07.2016 – Rev. B
English — 51
9.2.2
Default settings
The device controller is shipped with the following default settings. Use the Customer menu to adjust these values to local conditions. In
specific cases, it is possible to further adjust the values in the Service menu.
Customer menu
Parameter
Setting
Remarks
Language
EN
Display language.
Minimum operating pressure "P
0
"
1.8 bar
see chapter 7.2 "Determining the P
pressure for the controller" on page 36 .
Next maintenance
12 months
Time left to the next due maintenance.
Floating alarm contact
All
see chapter 9.3 "Messages" on page 52 .
Make-up
Maximum make-up quantity
0 Litres
Only if make-up has been selected in the customer menu
with “With water meter Yes”.
Maximum make-up time
20 minutes
Maximum make-up cycles
3 cycles within 2 hours
Degassing
Degassing programme
Continuous degassing
Continuous degassing time
12 hours
Default setting
Softening (Only if "With softening Yes")
Lock make-up
No
In the case of soft water residual capacity = 0
Hardness reduction
8°dH
= Target – Actual
Maximum make-up quantity
0 Litres
Soft water capacity
0 Litres
Cartridge replacement
18 months
Replace cartridge.