Operation
Variomat 1 — 06.07.2016 – Rev. B
English — 47
8
Operation
8.1
Automatic mode
After successful commissioning, start the Automatic mode from the device. The Automatic mode is suitable for continuous device
operation and the controller monitors the following functions:
•
Maintain pressure
•
Compensate expansion volume
•
Degas
•
Automatic make-up
Press "Auto" on the controller operator panel to start the Automatic mode. The "PU" pump and the "PV1" motor ball valve of the
overflow line are regulated by the controller so that the pressure remains constant at a regulation range of ± 0.2 bar. Faults are displayed
and evaluated. The "PV1" motor ball valve of the overflow line remains open during the adjustable degassing time as long as the pump
runs. In the de-pressurised "VG" primary tank, the system water is expanded and degassed. For Automatic mode, you can set various
degassing programmes in the Customer menu, see chapter 7.6 "Parametrising the controller in the Customer menu" on page 42 . The
controller display supplies the necessary information.
Continuous degassing
Select this programme after commissioning and repairs of the connected system.
– The device will continuously degas for a set period of time. Free and dissolved
gases are quickly removed.
Start/setting:
– Automatic start after execution of the start routine during commissioning.
– Activated from the Customer menu.
•
The degassing time can be set in the Customer menu, dependent on the actual
system.
– The default setting is 12 hours. After expiry of the set time, the device
automatically switches to interval degassing.
30 %
2.5 bar
Continuous degassing
Interval degassing
Select this programme for continuous operation. As the default setting, it is set in the
Customer menu see chapter 7.6 "Parametrising the controller in the Customer menu" on
page 42 .
Degassing is continuous during an interval. An idling time follows an interval. The interval
degassing mode can be limited to an adjustable time period. Set the time in the Service
menu, see chapter 9.2.1 "Service menu" on page 50.
Start/setting:
•
Automatic activation upon expiry of continuous degassing.
•
Degassing interval
– The default setting is 90 seconds.
•
Idling time
– The default setting is 120 minutes
•
Start/End
– 8:00 to 18:00 o'clock.
30 %
2.5 bar
Interval degassing