Controller
64 — English
Servitec 35-120 with Touch controller — 06.07.2016 - Rev. B
9.5
Messages
The messages indicate impermissible deviations from the unit's normal operating state. They are output either via the RS-485 interface
or via two floating message contacts.
The controller displays the messages with a help text. By selecting the fault memory in the Customer menu, you display the last 24
messages. Message causes can be eliminated by the operator or a specialist workshop. If required, please contact the Reflex Customer
Service.
Note!
Messages identified with "OK" must be confirmed with the "OK" button on the display. The device operation is otherwise
interrupted. The readiness for operation is maintained for all other messages. They are displayed.
Note!
If necessary, you can set the output of messages via a floating contact in the Customer menu.
To reset a fault message, proceed as follows:
1. Touch the display.
Servitec-35
2.1 bar
1 fault message(s)
Make-up degassing
– The current fault messages are displayed.
2. Touch a fault message.
Current messages
02. 1 Insufficient water switch
1 fault message(s)
– The system displays the possible causes for the fault.
3. When the fault is eliminated, confirm the fault with "OK".
Current messages
02.1 Insufficient water
Cause:
–
04.1 Pump
–
Make-up not connected
–
Dirt trap in make-up line clogged
–
Make-up solenoid valve does not open
–
Large gas quantities in the system
Fault has been eliminated and can be acknowledged.
.
2.1 bar
Make-up degassing