![Reflex Reflexomat RS 150/1 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/reflex/reflexomat-rs-150-1/reflexomat-rs-150-1_operating-manual_1432679007.webp)
Safety
Reflexomat with Touch controller — 06.07.2016 - Rev. B
English — 7
3.2
Personnel requirements
Only specialist personnel or specifically trained personnel may install and operate the equipment.
The electric connections and the wiring of the device must be executed by a specialist in accordance with all applicable national and
local regulations.
3.3
Personal protective equipment
When working at the system, wear the stipulated personal equipment such as hearing and eye protection, safety boots, helmet,
protective clothing, protective gloves.
See the national regulation of your country for personal protective equipment required.
3.4
Intended use
The device is a pressure maintaining station for heating and cooling water systems. It is intended to maintain the water pressure and to
add water within a system. The devices may be used only in systems that are sealed against corrosion and with the following water
types:
•
Non-corrosive
•
Chemically non-aggressive
•
Non-toxic
The ingress of atmospheric oxygen by permeation into the entire heating and cooling water system, make-up water and similar must be
reliably minimised during operation.
3.5
Inadmissible operating conditions
The device is not suitable for the following applications:
•
Mobile system operation.
•
Outdoor operation.
•
For use with mineral oils.
•
For use with flammable media.
•
For use with distilled water.
Note!