![Reflex Reflexomat RS 150/1 Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/reflex/reflexomat-rs-150-1/reflexomat-rs-150-1_operating-manual_1432679043.webp)
Operation
Reflexomat with Touch controller — 06.07.2016 - Rev. B
English — 43
8.1.3
Stop mode
The Stop mode is intended for the device commissioning.
Except for the display of information, the device is non-functional in Stop mode. Function monitoring is stopped.
The following functions are deactivated:
•
The "CO" compressor is switched off.
•
The solenoid valve in the "PV" overflow line is closed.
•
The solenoid valve in the "WV" make-up line is closed.
1. Press "STOP“.
Reflexomat RS../1
800l
25%
1.4 bar
System
0l
NSP
0l
Notice!
The system returns an alarm if the Stop mode is activated for more than 4 hours.
– If "Floating alarm contact?" in the Customer menu is set to "Yes", the system outputs the alarm to the group alarm
contact.