![Reflex Reflexomat RS 150/1 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/reflex/reflexomat-rs-150-1/reflexomat-rs-150-1_operating-manual_1432679026.webp)
Installation
26 — English
Reflexomat with Touch controller — 06.07.2016 - Rev. B
6.4
Make-up and degassing variants
6.4.1
Function
The filling level is recorded in the primary tank by the "LIS" level sensor and evaluated in the controller. When the water level falls below
the value specified in the controller's customer menu, the external make-up is activated.
6.4.1.1
Make-up without pump
Reflexomat RS with solenoid valve and ball valve.
1
Reflexomat RS
WC Make-up line
2
Solenoid valve “Fillvalve” with ball valve
LIS
Level sensor
3
Reflex Fillset
EC
Expansion line
ST
Dirt trap
Preferably, you should use the Reflex Fillset with integrated system separator when using drinking water for make-up, see chapter 4.6
"Optional equipment and accessories" on page 14 . If you don't use a Reflex Fillset, you must use an "ST" dirt trap with a mesh size
≥
0.25 mm for the make-up.