Maintenance
Reflexomat with Basic controller — 20.06.2017 - Rev. C
English — 51
Tanks with replaceable diaphragm
1. Close the cap valves upstream of the tanks.
2. Record the displayed level value at the controller and empty the tank of water and compressed air.
3. Switch off the main switch and withdraw the mains plug.
4. Open the drain taps at the tanks and drain the condensate.
– If more than 5 litres of water or condensate are discharged, you must check the tank.
•
Check the diaphragm for rupture.
•
Check the tank interior walls for corrosion damage.
CAUTION – Risk of injury caused by escaping pressurised liquid. Injuries can occur during maintenance work if the connections
have been installed incorrectly because condensate under pressure can suddenly escape.
5. Close the tanks' drain taps.
6. Connect the mains plug and switch on the main switch.
7. Open the cap valves of the tanks and secure against unauthorised "closing".
8. Fill water and compressed air into the tanks until the recorded level value is reached.
Maintenance is completed.
Note!
Check the installation location of the tanks for sufficient ventilation if the tank interior wall are damaged by corrosion, see
chapter 6.2 "Preparatory work" on page 18 .
10.3.2
Cleaning the dirt trap
Regularly clean the "ST" dirt trap. The cleaning intervals depend on the local operational conditions.
1. Switch to Stop mode.
– Press
"
Stop
"
on the controller's operator panel.
2. Close the ball valves upstream and downstream of the
"ST" (1) dirt trap.
3. Slowly unscrew the dirt trap insert (2) from the dirt trap in
order for the residual pressure to escape from the pipeline
segment.
4. Pull the mesh from the dirt trap insert and rinse it with clear
water. Use a soft brush for cleaning.
5. Re-insert the mesh into the dirt trap insert, check the gasket
for damage, and screw the dirt trap insert back into the
housing of the "ST" (1) dirt trap.
6. Re-open the ball valves upstream and downstream of the
"ST" (1) dirt trap.
7. Switch to Automatic mode.
– Press "Auto" on the controller's operator panel.
1
"ST" dirt trap
2 Dirt trap insert
Note!
Clean all other installed dirt traps (in the Reflex Fillset, for example).