Messages
Messages with ER codes are displayed at the controller.
•
Use the arrow keys at the controller operating panel to select the messages.
•
By selecting the "Fault memory" main menu in the Customer menu, you display the last 20 alarms.
•
Alarm causes can be eliminated by the operator or a specialist workshop.
•
If required, please contact the Reflex Customer Service.
Note!
Clearing of the cause must be confirmed by pressing the “Ack” button on the operator panel. All other alarms are
automatically reset as soon as the cause has been eliminated.
Note!
Floating contacts, setting in the Customer menu, see chapter 7.5 "Parametrising the controller in the Customer menu" on
page 31 .
ER Code
Alarm
Floating
contact
Cause
Remedy
Alarm reset
01
Minimum pressure
Yes
•
Set value not reached
•
Water loss in the system
•
Pump fault
•
Expansion tank defective
•
Check set value in the
Customer or Service
menu
•
Check water level
•
Check pump
•
Check expansion tank
-
02.1
Insufficient water
-
Insufficient water switch has
actuated for too long
•
Open the degassing line
•
Clean the dirt trap
•
Replace the degassing
valve
Quit
02.2
Insufficient water
-
Insufficient water switch
triggered
•
Check the supply line
from the fresh-water
system to the system
separator tank
•
Check the function of
the float valve in the
system separator tank
Quit
04.1
04.2
Pump1
Pump2
Yes
Pumps disabled
•
Pumps jammed
•
Pump motor defective
•
Pump motor protector
(Klixon) tripped
•
Fuse defective
•
Rotate the pumps with
screwdriver
•
Replace the pump
motor
•
Electrically test the
pump motor
•
Replace the 10 A fuse
Quit
06
Makeup time
-
•
Set value exceeded
•
Water loss in the system
•
Makeup line not connected
•
Makeup rate insufficient
•
Makeup hysteresis too low
•
Check set value in the
Customer or Service
menu
•
Check water level
•
Connect makeup line
Quit