Technical data
16 — English
Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B
5
Technical data
Note!
The following values apply for all systems:
– Permissible ambient temperature:
– Degree of protection:
– Noise level:
>0 °C – 45 °C
IP 54
55 dB
5.1
Electrical system
Type
Power output
(W)
Power supply
(V / Hz)
Fusing
(A)
Number of RS-485
interfaces
I/O module
Fillcontrol Auto 2P
500
230 / 50
10
2
Optional
Fillcontrol Auto 2PS
500
230 / 50
10
2
Optional
5.2
Dimensions and connections
Type
Weight
(kg)
Height
(mm)
Width
(mm)
Depth
(mm)
Device
connection
System
connection
Overflow
connection
Fillcontrol Auto 2P
47
930
500
560
RP ½
G 1
–
Fillcontrol Auto 2PS
55
1030
500
580
RP ½
G 1
–
5.3
Operation
Type
Make-up capacity
(l/h)
Maximum feed
pressure
(bar)
Maximum delivery
pressure
(bar)
Permissible operating
gauge pressure
(bar)
Operating
temperature
(°C)
Fillcontrol Auto 2P
≤
4200
10
≤
8.5
6
70
Fillcontrol Auto 2PS
≤
4200
10
≤
8.5
6
70