Inside US: +1 (877) 432-9908
Bulletin No. CTL-D
Outside US: +1 (717) 767-6511
Drawing No. LP0652
www.redlion.net
Revised 2018-06-30
-1-
MODEL
CTL
‐
AVERAGE
RESPONDING
AC
CURRENT
TRANSDUCERS
•
AVERAGE RESPONDING OUTPUT: 0-10 VDC or 4-20 mA
•
JUMPER SELECTABLE RANGES
•
OUTPUT IS MAGNETICALLY ISOLATED FROM THE INPUT
•
SPLIT-CORE AND FIXED-CORE CASES
GENERAL
DESCRIPTION
CTL Series transducers combine a current transformer and a signal
conditioner into a single package. This provides higher accuracy, lower
wiring costs, easier installation and saves valuable panel space.
The CTL Series transducers have jumper selected current input ranges
and industry standard 0-10 VDC or 4-20 mA outputs. The CTL
Series is
designed for application on “linear” or sinusoidal AC loads. Available in a
split-core or solid-core case. Select the CTL
Series for constant speed
loads or On/Off loads.
SAFETY
SUMMARY
All safety regulations, local codes and instructions that appear in this
and corresponding literature, or on equipment, must be observed to
ensure personal safety and to prevent damage to either the instrument or
equipment connected to it. If equipment is used in a manner not specified
by the manufacturer, the protection provided by the equipment may be
impaired.
Do not use this unit to directly command motors, valves, or other
actuators not equipped with safeguards. To do so, can be potentially
harmful to persons or equipment in the event of a fault to the unit.
SPECIFICATIONS
1.
OUTPUT SIGNAL:
2.
OUTPUT LIMIT:
3.
FREQUENCY RANGE:
4.
RESPONSE TIME:
5.
ACCURACY:
6.
POWER SUPPLY:
7.
INPUT RANGES:
(Jumper Selectable)
8.
ISOLATION VOLTAGE
: 3 kV
9.
CASE
: UL 94V-0 Flammability rated thermoplastic
10.
ENVIRONMENTAL
: -4 to 122 °F (-20 to 50 °C)
0-95% RH, non-condensing
11.
TORQUE RATINGS
: 7 in-lbs on Fixed-core models; 9 in-lbs on Split-
core models.
12.
LISTING:
UL Listed: File #E191578.
CAUTION: Risk Of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION:
Risk of electric shock.
PART
NUMBER
RANGE
MAXIMUM
CONTINUOUS
6 SEC
1 SEC
CTL005_ _
2 A
80 A
125 A
250 A
5 A
100 A
125 A
250 A
CTL050_ _
10 A
80 A
125 A
250 A
20 A
110 A
150 A
300 A
50 A
175 A
215 A
400 A
CTL200_ _
100 A
200 A
300 A
600 A
150 A
300 A
450 A
800 A
200 A
400 A
500 A
1000 A
3.50
(88.9)
3.03
(77.0)
0.93
(23.6)
Ø 0.19
(4.8)
2.40
(61.0)
2.18
(55.4)
Ø 0.74
(19)
DIMENSIONS
In
inches
(mm)
FIXED-CORE
C
US LISTED
UL
R
PROC. CONT. EQ.
E191578
0-10 VDC
0-10 VDC
15 VDC
50-60 Hz
100 msec
1.0% FS
Self-powered
4-20 mA
4-20 mA
40 mA
20-100 Hz
300 msec
0.5% FS
24 VDC Norminal, 40 VDC max.
0.85
(21.6)
0.85
(21.6)
3.53
(89.7)
2.40
(61)
3.04
(77.2)
Ø 0.19
(4.8)
2.25
(57.2)
1.19
(30.2)
DIMENSIONS
In
inches
(mm)
SPLIT-CORE