MODEL

 

CTL

 ‐ 

AVERAGE

 

RESPONDING

 

AC

 

CURRENT

 

TRANSDUCERS

 

AVERAGE RESPONDING OUTPUT: 0-10 VDC or 4-20 mA

JUMPER SELECTABLE RANGES

OUTPUT IS MAGNETICALLY ISOLATED FROM THE INPUT

SPLIT-CORE AND FIXED-CORE CASES

GENERAL

 

DESCRIPTION

CTL Series transducers combine a current transformer and a signal

conditioner into a single package. This provides higher accuracy, lower
wiring costs, easier installation and saves valuable panel space.

The CTL Series transducers have jumper selected current input ranges

and industry standard 0-10 VDC or 4-20 mA outputs. The CTL

Series is

designed for application on “linear” or sinusoidal AC loads. Available in a
split-core or solid-core case. Select the CTL

Series for constant speed

loads or On/Off loads. 

SAFETY

 

SUMMARY

All safety regulations, local codes and instructions that appear in this

and corresponding literature, or on equipment, must be observed to
ensure personal safety and to prevent damage to either the instrument or
equipment connected to it. If equipment is used in a manner not specified
by the manufacturer, the protection provided by the equipment may be
impaired. 

Do not use this unit to directly command motors, valves, or other

actuators not equipped with safeguards. To do so, can be potentially
harmful to persons or equipment in the event of a fault to the unit.

SPECIFICATIONS

1.

OUTPUT SIGNAL:

2.

OUTPUT LIMIT:

3.

FREQUENCY RANGE:

4.

RESPONSE TIME:

5.

ACCURACY:

6.

POWER SUPPLY:

7.

INPUT RANGES:

 (Jumper Selectable)

8.

ISOLATION VOLTAGE

: 3 kV

9.

CASE

: UL 94V-0 Flammability rated thermoplastic

10.

ENVIRONMENTAL

: -4 to 122 °F (-20 to 50 °C)

0-95% RH, non-condensing

11.

TORQUE RATINGS

: 7 in-lbs on Fixed-core models; 9 in-lbs on Split-

core models.

12. 

LISTING:

 UL Listed: File #E191578.

CAUTION: Risk Of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

PART

NUMBER

RANGE

MAXIMUM

CONTINUOUS

6 SEC

1 SEC

CTL005_ _

2 A

80 A

125 A

250 A

5 A

100 A

125 A

250 A

CTL050_ _

10 A

80 A

125 A

250 A

20 A

110 A

150 A

300 A

50 A

175 A

215 A

400 A

CTL200_ _

100 A

200 A

300 A

600 A

150 A

300 A

450 A

800 A

200 A

400 A

500 A

1000 A

3.50

(88.9)

3.03

(77.0)

0.93

(23.6)

Ø 0.19

(4.8)

2.40

(61.0)

2.18

(55.4)

Ø 0.74

(19)

DIMENSIONS

  

In

 

inches

 

(mm)

FIXED-CORE

C

US LISTED

UL

R

PROC. CONT. EQ.

E191578

0-10 VDC

0-10 VDC
15 VDC
50-60 Hz
100 msec
1.0% FS
Self-powered

4-20 mA

4-20 mA
40 mA
20-100 Hz
300 msec
0.5% FS
24 VDC Norminal, 40 VDC max.

0.85

(21.6)

0.85

(21.6)

3.53

(89.7)

2.40
(61)

3.04

(77.2)

Ø 0.19

(4.8)

2.25

(57.2)

1.19

(30.2)

DIMENSIONS

  

In

 

inches

 

(mm)

SPLIT-CORE

Отзывы: