The table below explains the meaning and possibility of changes in the individual settings
windows.
Sub menu
Parameter
Description
Date&Time
Date format setting
There are three possible selection formats
(A) year / month / day, (b) month / day / year,
(C) day / month / year
Time setting
Setting date and time
Language
Current language
Language in current use
Language selection
English or chinese
COMM.
Device Address
Set device address
RS232 Protocol Selection
SNT, ModBus, YD/T or Dwin
(
for service
)
Baudrate
Set the read speed for the communication protocol
Modbus Mode
ASCII or RTU
Modbus parity
Parity setting for Modbus
USER
Output voltage Adjustment
Setting the voltage value
Bypass Voltage Up Limited
To 10%
,
+15%
,
+20%
,
+25%
Bypass Voltage Down Limited
To choose:-10%
,
-15%
,
-20%
,
-30%
,
-40%
Bypass Frequency Limited
To choose
:
+/-1Hz
,
+/-3Hz
,
+/-5Hz
Dust Filter Maintenance Period
Set the date of the replacement of the pollen filter
BATTERY
Battery Number
Setting the amount of battery (12V)
Battery Capacity
Setting the battery capacity (Ah)
Float Charge Voltage/Cell
Set the charging voltage in float mode for the
battery cell (2V)
Boost Charge Voltage/Cell
Charging voltage setting in boost mode for battery
cell (2V)
EOD(End of charge)
Voltage/Cell,@0.6C Current
Setting the battery disconnect voltage when
discharging 0.6xC
EOD (End of charge)
Voltage/Cell,@0.15C Current
Set the voltage of disconnecting the battery when
discharged with 0.15xC
Charge Current Percent Limit
Set the percentage of battery charger
performance
Battery Temperature
Compensate
Set the temperature correction factor of the
charging voltage
Boost Charge Time Limit
Setting the charging time in boost mode
Auto Boost Period
Setting the auto boost load duration
Auto Maintenance Discharge
Period
Set the period of automatic battery tests