red lion IRMA DC Скачать руководство пользователя страница 1

1



USER PROGRAMMABLE INPUT
(RTD alpha = 0.00385 (DIN 43760), alpha = 0.00392, or resistance)



MICROPROCESSOR CONTROLLED



SIMPLE ADJUSTABLE RANGE SETTING (Using Input Signal)



RTD BREAK DETECTION



MOUNTS ON “T” AND “G” STYLE DIN RAILS



3-WAY ELECTRICAL ISOLATION (POWER/INPUT/OUTPUT)



MULTIPLE ANALOG OUTPUTS (0 to 20 mA, 4 to 20 mA, and 0 to 
10 VDC)



WIDE OPERATING TEMPERATURE RANGE (-25°C to 75°C)



LED INDICATION (POWER & MEMORY ERROR)



9 to 32 VDC POWERED

DESCRIPTION

The IRMA accepts an RTD or resistance input and converts it into a voltage 

or current output. The output is linearly proportional to the temperature or 
resistance input. This output is ideal for interfacing to indicators, chart 
recorders, controllers, or other instrumentation equipment. 

The IRMA is DC powered. The DC power input is isolated from the signal 

input and analog output. The unit scales the analog output proportionally to the 
RTD or resistance input signal. The analog output may be configured for one of 
the following: 0 to 20 mA, 4 to 20 mA, or 0 to 10 VDC. Making the signal 
conversion with the IRMA to a current output signal, makes the signal less 
susceptible to noise interference and allows accurate transmission over long 
distances. The 3-Way isolation allows the use of grounded RTD’s which can 
provide additional noise reduction benefits.

The IRMA uses an eight position DIP switch to accomplish the input sensor 

configuration, range selection, and unit calibration. A simple range setting 
technique (Field Calibration) is used so the actual input signal adjusts the output 
for scaling. This technique eliminates the need for potentiometers which are 
vulnerable to changes due to vibration.

The unit is equipped with a universal mounting foot for attachment to 

standard DIN style mounting rails, including top hat rail (T) according to EN 50 
022 - 35 

 7.5 and 35 

 15, and (G) profile according to EN 50 035 - G 32. 

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

manual or on equipment must be observed to ensure personal safety and to 
prevent damage to either the instrument or equipment connected to it. If 
equipment is used in a manner not specified by the manufacturer, the protection 
provided by the equipment may be impaired.

SPECIFICATIONS

1.

 POWER

: 9 to 32 VDC; 1.75 W. 200 mA max. current. The power supply 

must have 400 mA for 200 msec. surge capacity.

2.

 INPUT

: RTD 2, 3, or 4 wire, 100 ohm platinum, alpha = 0.00385

(DIN 43760), alpha = 0.00392, or resistance [selectable via DIP switches].

Excitation

: 0.170 mA nominal

Lead resistance

: Less than 0.5°C with 15 ohms max. per lead

Note: There is no lead compensation for 2 wire input. Field calibration 

should be performed with equivalent series resistance.

3. 

OUTPUT

: All output signals scaled linearly using temperature or resistance 

input. Unit is shipped set for the 4 to 20 mA output. 4 to 20 mA or 0 to 20 
mA selected via internal jumper.

Voltage Output Compliance

:

0 to 10 VDC across min. 1 K

 load (10 mA)

20 mV peak to peak max. ripple (for frequencies up to 120 Hz)

Current Output Compliance

:

0 to 20 mA through max. 600

 load (12 VDC)

4 to 20 mA through max. 600

 load (12 VDC)

15 mV peak to peak max. ripple across 600

 load (for frequencies up to 

120 Hz)

4.

 RTD BREAK DETECTION

: Nominal values shown in the following order: 

(0 to 20 mA, 4 to 20 mA, and 0 to 10 VDC).

Upscale

: 22.9 mA, 22.5 mA, and 11.5 VDC

Downscale

: -0.5 mA, 3.5 mA, and -0.4 VDC

5.

 RESPONSE TIME

: 400 msec. (to within 99% of final value w/step input; 

typically, response is limited to response time of probe.)

6.

 TEMPERATURE EFFECTS

:

Temperature Coefficient

:  

 0.025% of input range per 

C

7.

 DIELECTRIC WITHSTAND VOLTAGE

: 1500 VAC for 1 minute

Working Voltage

: 50 VAC

Power input to Signal input, Power input to Signal output, & Signal input to 
Signal output.

MODEL IRMA DC - 

INTELLIGENT RTD MODULE WITH ANALOG

 

OUTPUT

4.20 REF

1.08

3.12

(27.5)

(106.7)

(79.2)

ERROR

POWER

IRMA

DIP SWITCH SETTINGS:

ON = 1

O

FF = 0

MC2234X

9-32 VDC

ERROR

POWER

VDC+

10

RTD(S)

7

V+

4

I+

1

VDC-

RTD(-)

12

11

9

8

6

5V

-

3

2I

-

78

RANGE

RTD

OHMS

RTD TYPE

385

392

OPEN SEN

DOWN

SENSOR

UP

0

1

SWITCH

4

0

SWITCH

5

SWITCH

1

6

SWITCH

1

0

0

1

2

3

0

0

1

0

1

0

11

392/385

5

O

PEN SEN UP/DN

OHMS/RTD

RANGE

1

4

3

2

OUTPUT CAL

FIELD CAL

BASIC CAL

8

7

6

RTD(+)

RANGE

MADE IN U.S.A.

RED LION CONTROLS

MODEL IRMA

YORK, PA.

 DIMENSIONS  In inches (mm)

CAUTION: Read complete instructions prior 

to installation and operation of the unit.

MODEL NO.

DESCRIPTION

PART NUMBER

IRMA

Intelligent RTD Module

IRMA3035

ORDERING INFORMATION

Bulletin No.  IRMA-E
Drawing No.  LP0437
Released  02/10

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

Содержание IRMA DC

Страница 1: ...er the protection provided by the equipment may be impaired SPECIFICATIONS 1 POWER 9 to 32 VDC 1 75 W 200 mA max current The power supply must have 400 mA for 200 msec surge capacity 2 INPUT RTD 2 3 o...

Страница 2: ...nstallation Listed below are some EMC guidelines for successful installation in an industrial environment 1 Use shielded screened cables for all Signal and Control inputs The shield screen pigtail con...

Страница 3: ...used at a time The unit is factory set for a 4 to 20 mA output The voltage output will track the current output linearly within 2 5 deviation of range endpoints To select 0 to 20 mA output you must o...

Страница 4: ...I VDC RTD S POWER RTD RTD VDC 9 ERROR 7 8 12 10 11 6 3 4 1 5 2 V I 5 1 4 3 2 8 7 6 RANGE RANGE OHMS RTD FIELD CAL BASIC CAL OUTPUT CAL 392 SEN UP DN MODEL IRMA ERROR POWER VDC 10 RTD S 7 V 4 I 1 VDC R...

Страница 5: ...s using a third sense wire Set the RANGE 7 8 TYPE 4 OUTPUT CAL 1 and FIELD CAL 2 switches OFF Set the BASIC CAL switch 3 ON 2 2 Apply operating power and allow a 45 minute warm up period Current goes...

Страница 6: ...ail Installation To install the IRMA on a G style DIN rail angle the module so that the upper groove of the foot catches under the lip of the top rail Push the module toward the rail until it snaps in...

Страница 7: ...7 This Page Intentionally Left Blank...

Страница 8: ...yer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any pers...

Отзывы: