44
o
perator
i
nterface
i
nStallation
MOUNTING INSTRUCTIONS
This operator interface is primarily designed for
through-panel mounting. Four VESA mount tapped
screw-holes (M4 x 0.7, 5 mm deep) are present on the rear
of the panel to allow for stand or wall mounting. Care
should be taken to remove any loose material from the
mounting cut-out to prevent that material from falling into
the operator interface during installation. A gasket is
provided to enable sealing to NEMA 4X/IP66
specification. Install the mounting clips provided and
tighten to 6.0 pound-force inch (96 ounce-force inch)
(0.68 Nm) evenly for uniform gasket compression.
Provisions should be made to prohibit the product from
being exposed to UV radiation while in use. Care should
be taken not to rub or buff the touchscreen surface in a
way that might cause the accumulation of static charges.
FOOT MAY BE REMOVED
FOR THICKER PANEL
INSTALLATIONS
4.869
(123.7)
7.060 (179.3)
4X R.10 (2.5)
MAX.
All tolerances ±.059" (±1.5 mm)
PANEL CUT-OUT
2.95 (75)
1.48 (37.5)
2.95
(75)
1.73
(44)
VESA MOUNT (MIS-D 75) DIMENSIONS
G07
5.832
(148.1)
9.423 (239.3)
4X R.10 (2.5)
MAX.
All tolerances ±.059" (±1.5 mm)
PANEL CUT-OUT
1.77
(45)
2.95
(75)
2.95 (75)
1.48 (37.5)
VESA MOUNT (MIS-D 75) DIMENSIONS
G09
For hazardous location installation, this device must be
mounted in a suitable ATEX/IECEx certified end-enclosure
with a minimum ingress protection rating of at least IP66
as defined in EN/IEC 60529 and used in an environment
of not more than Pollution Degree 2 per EN 60664-1. Must be wired
using Division 2 wiring methods as specified in article 501-4 (b),
502-4 (b), and 503-3 (b) of the National Electrical Code, NFPA 70 for
installation within the United States, or as specified in section 19-152
of Canadian Electrical Code for installation in Canada.