background image

  

AVERAGE RESPONDING OUTPUT: 0-10 VDC or 4-20 mA

  

JUMPER SELECTABLE RANGES

  

OUTPUT IS MAGNETICALLY ISOLATED FROM THE INPUT

  

SPLIT-CORE AND FIXED-CORE CASES

GENERAL DESCRIPTION

CTL Series transducers combine a current transformer and a signal conditioner 

into a single package. This provides higher accuracy, lower wiring costs, easier 

installation and saves valuable panel space.

The CTL Series transducers have jumper selected current input ranges and 

industry standard 0-10 VDC or 4-20 mA outputs. The CTL Series is designed for 

application on “linear” or sinusoidal AC loads. Available in a split-core or solid-

core case. Select the CTL Series for constant speed loads or On/Off loads. 

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

literature or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired.

Do not use this unit to directly command motors, valves, or other actuators 

not equipped with safeguards. To do so, can be potentially harmful to persons or 

equipment in the event of a fault to the unit.

SPECIFICATIONS

7. 

INPUT RANGES

: (Jumper Selectable)

8. 

ISOLATION VOLTAGE

: 3 kV

9. 

CASE

: UL 94V-0 Flammability rated thermoplastic

10. 

ENVIRONMENTAL

: -4 to 122 °F (-20 to 50 °C)

0-95% RH, non-condensing

11. 

TORQUE RATINGS

: 7 in-lbs on Fixed-core models; 9 in-lbs on Split-core 

models.

12. 

LISTING

: UL 508 Industrial Control Equipment, CSA C22.2 No. 14-M95, 

and CE Certified.

MODEL CTL - AVERAGE RESPONDING AC CURRENT TRANSDUCERS

CAUTION: Read complete 

instructions prior to installation 

and operation of the unit.

CAUTION: Risk of electric shock.

Bulletin No.  CTL-C
Drawing No.  LP0652
Released  03/14

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

C

US LISTED

UL

R

IND. CONT. EQ.

5T44

PART 

NUMBER

RANGE

MAXIMUM

6 sec

Continuous

1 sec

CTL050_ _

CTL005_ _

2 A

125 A

80 A

250 A

5 A

125 A

100 A

250 A

50 A

20 A

10 A

215 A

150 A

125 A

175 A

110 A

80 A

400 A

300 A

250 A

CTL200_ _

100 A

300 A

200 A

600 A

150 A

450 A

300 A

800 A

200 A

500 A

400 A

1000 A

0.85

(21.6)

0.85

(21.6)

3.53

(89.7)

2.40

(61)

3.04

(77.2)

Ø 0.19

(4.8)

2.25

(57.2)

1.19

(30.2)

DIMENSIONS  In inches (mm)

3.50

(88.9)

3.03

(77.0)

0.93

(23.6)

Ø 0.19

(4.8)

2.40

(61.0)

2.18

(55.4)

Ø 0.74

(19)

DIMENSIONS  In inches (mm)

0-10 VDC

4-20 mA

1. 

OUTPUT SIGNAL:

0-10 VDC

4-20 mA

2. 

OUTPUT LIMIT:

15 VDC

40 mA

3. 

FREQUENCY RANGE:

50-60 Hz

20-100 Hz

4. 

RESPONSE TIME:

100 msec

300 msec

6. 

POWER SUPPLY

:

5. 

ACCURACY:

Self-powered

1.0% FS

0.5% FS

SPLIT-CORE

FIXED-CORE

24 VDC Nominal, 40 VDC max.