red lion APOLLO IMR Series Скачать руководство пользователя страница 38

APPENDIX “A” - INSTALLATION & CONNECTIONS

INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the maximum

operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap product.

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

Before installing the IM into the panel, the user should first become familiar

with the unit. It may also be desirable to program the unit for the application.
When programming is complete, all parameters will be saved in non-volatile
memory. The Program Disable (PGM.DIS.) terminal should be connected to
COMM. to prevent accidental or unauthorized programming changes.

-36-

PANEL INSTALLATION

SELECT AC POWER (115/230 VAC)

The AC power to the unit must be selected for either 115 VAC or 230 VAC.

The selector switch is located through an access slot on the side of the case (See
figure above or label on case). The unit is shipped from the factory with the
switch in the 230 VAC position.

Caution: Make sure the AC selector switch is set to the appropriate

position before applying power to the unit. Damage to the unit

may occur if the AC selector switch is set incorrectly.

The unit meets NEMA 4/IP65 requirements for indoor use, when properly

installed. The units are intended to be mounted into an enclosed panel with a
gasket to provide a water-tight seal. Two mounting clips and screws are
provided for easy installation. Consideration should be given to the thickness
of the panel. A panel which is too thin may distort and not provide a
water-tight seal. Recommended minimum panel thickness is 1/8".)

After the panel cut-out has been completed and deburred, carefully slide the

gasket over the rear of the unit to the back of the
bezel. Insert the unit into the panel. As depicted
in the drawing, install the screws into the narrow
end of the mounting clips. Thread the screws
into the clips until the pointed end just protrudes
through the other side. Install each of the
mounting clips by inserting the wide lip of the
clips into the wide end of the hole, located on
either side of the case. Then snap the clip onto
the case. Tighten the screws evenly to apply
uniform compression, thus providing a
water-tight seal.

Caution: Only minimum pressure is required to seal panel. Do NOT

overtighten screws.

Содержание APOLLO IMR Series

Страница 1: ...THE APOLLO INTELLIGENT METER SERIES MODEL IMR INSTRUCTION MANUAL IMRCVR L QXD 10 6 2005 9 02 AM Page 1...

Страница 2: ...erent indication and control requirements The Intelligent RTD Meter which you have purchased has the same high quality workmanship and advanced technological capabilities that have made Red Lion Contr...

Страница 3: ...am Integrator Totalizer 13 Module 6 Program Alarm Setpoint 14 Module 7 Program Serial Communications 16 Module 8 Program Re Transmitted Analog Output 17 Module 9 Service Operations 18 Operating the IM...

Страница 4: ...TTED ANALOG OUTPUT Optional 34 Analog Output Calibration 35 APPENDIX A INSTALLATION CONNECTIONS 36 Installation Environment 36 Panel Installation 36 Select AC Power 115 230 VAC 36 EMC Installation Gui...

Страница 5: ...to directly command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipment in the event of a fault to the unit DEFINITION OF TERMS I...

Страница 6: ...rammable to operate in a wide variety of modes to suit many control or alarmapplications Optional 20 mA loop bi directional serial communications provides computer and printer interfacing to extend th...

Страница 7: ...PPLY 1 5WC PGM DIS 0 i I J C ii l J SIGNAL SIGNAL COMM SI SI v SO 20mA SRC 5WC 5WC 12VDC 15VDC PROGRAM DISABLE El CON PROCESS CIRCUITRY E2 CON SERIAL IN SERIAL OUT ANALOG OUT DISPLAY 8 8 8 8 8 8 5WC N...

Страница 8: ...eled P momentarily Briefly the display will show Pro alternately flashing with 0 This is the indicator s programming mode The programming mode is divided into sections numbered 0 9 each of which can b...

Страница 9: ...in TBA 8 The functions of the remote E1 and E2 pins are the same and include display hold peak valley modes totalizer reset alarm reset temperature offset reading synchronization or print request DISP...

Страница 10: ...button dECNPt 0 0 0 If the totalizer option is installed the offset and slope can be programmed for various temperature probe differences Reference offset and slope display temperature section for mor...

Страница 11: ...hysteresis value then this step will default to NO and will not be displayed for selection ENtHYS yES or NO Note This sequence may be locked out due to other programmed sequences Note This function o...

Страница 12: ...yES or NO ENTER OFFSET VALUE If YES was selected for the previous step this selects whether the offset value can be entered from the panel If NO was selected then this step defaults to NO and will not...

Страница 13: ...activated the value of the actual temperature being displayed is placed in the location of the display offset value To bring the unit into the normal temperature display mode reset the offset value to...

Страница 14: ...set A negative going edge tares zeros the input signal Prior to the offset operation the input signal is saved and held display hold as long as the remote input pin is low On the positive edge the inp...

Страница 15: ...hanges can be made synchronous to the display by programming E1 or optional E2 CON pin for function 13 Instrument reading synchronization A multiplying scale factor may be used to span the standard ti...

Страница 16: ...emote input E1 CON or optional E2 CON or through the front panel Latched alarms are usually used when an operator is required to take some action for the alarm condition LAtC 1 yES or NO ALARM 1 ASSIG...

Страница 17: ...or alarm 2 may be programmed from 1 to 9 999 for the input and 1 to 999999 for the totalizer option The value is either added to or subtracted from the alarm value depending on whether the alarm is hi...

Страница 18: ...cede the digits that are printed ex 000127 positive overflow 00127 negative overflow If the temperature exceeds the range of the unit or the sensor opens the print out will show OPEN and for the negat...

Страница 19: ...y programming the high display value for the AN LO programming step and the low display value for the AN HI step Note DO NOT ADJUST THE ANALOG OUTPUT POTS ON THE BACK OF THE UNIT Fine offset and span...

Страница 20: ...at the resistor as shown in the drawing to the right Shorting terminals may lead to incorrect calibration Connect a precision 300W resistor across Terminals 6 and 7 Allow to stabilize for 20 seconds...

Страница 21: ...alarms and hysteresis values can be modified in the same manner as in the regular programming mode The new alarm and hysteresis values will take effect when P is pressed The other operations in the q...

Страница 22: ...dSP AL yES ENt AL yES dSPHYS yES ENtHYS yES rSt AL yES dSPbUF yES rStbUF yES SELdSP yES rSttOt yES dSPOFF yES ENtOFF yES Pro 4 FILter 1 E1 CON 4 Display Hold E2 CON 4 Display Hold Pro 5 dECPNt 0 tbASE...

Страница 23: ...ERIAL Provide hardcopy printout of total input and peak valley when operator actuates print request Baud rate 300 ANALOG RE TRANSMISSION Record temperature profile 4 mA at 100 F and 20 mA at 400 F Pro...

Страница 24: ...rder to assure that personnel inform maintenance of a possible problem Key switches are installed to lock out the front panel from unauthorized personnel and to provide the means to reset the latched...

Страница 25: ...00 400 and finally 500 degrees Using the controlled relay outputs of three IMRs the various temperatures of the bands are controlled precisely After the material is injected into the mold the mold tem...

Страница 26: ...e other features of the integrator totalizer option are peak and valley detection The indicator will record the lowest reading valley and the highest reading peak automatically for later recall This i...

Страница 27: ...tions The following programming steps are performed BASIC SET UP Pro 1 rtdtyP 385 SCALE F dECPNt 0 0 INTEGRATOR TOTALIZER SET UP With an average temperature input which gives a display of 110 0 at the...

Страница 28: ...can be calculated by the following formula Av I V S F x T T I V Integrator Totalizer Value S F Programmable Scale Factor T T Total Time From the beginning of the shift For example 6 hours and 37 minut...

Страница 29: ...where a pre warning control activates before a second alarm shuts off the process When tracking is programmed changing the shut off trip value Alarm 2 automatically changes Alarm 1 so that the offset...

Страница 30: ...ting the unit with a printer the receive loop of the indicator must have current flowing into it before transmission can take place COMMUNICATION FORMAT Data is sent by switching current on and off in...

Страница 31: ...mand is not required This is done where only one indicator is in the loop The command string is constructed in a specific logical sequence The indicator will reject command strings that do not conform...

Страница 32: ...E COMMAND STRING TRANSMITTED AT SELECTED BAUD RATE t 80msec MAXIMUM IM PROCESSES COMMAND BOmsec MAXIMUM IM BEGINS PROCESSING AFJER IS RECEIVED MODE IM TRANSMITS DATA STRING AT SELECTED BAUD RATE corno...

Страница 33: ...asons extra characters are added onto the end of the above character string These characters could be and are used for control or signaling purposes These characters are CR sent after single line tran...

Страница 34: ...lected in Program Module 7 Reference Programming Module 7 for more details In order for a print request function to occur E1 CON TBA 4 or E2 CON TBA 8 pin must be programmed for print request Note In...

Страница 35: ...le 7 A baud rate of 1200 is selected An application program is written which sends and retrieves data from the IMRs Note On all IM indicators the SO and the 20 mA SRC are connected internally Therefor...

Страница 36: ...o and a 20 mA or 10 VDC output AN HI The analog output then follows the assigned value and as such will update every measurement cycle Nonstandard current or voltage ranges can be supported by calcula...

Страница 37: ...See Appendix B for max input voltage Adjust the span potentiometer left side so that 20 00 mA is flowing Repeat the zero and span adjustments until both are accurate Analog output calibration is comp...

Страница 38: ...position Caution Make sure the AC selector switch is set to the appropriate position before applying power to the unit Damage to the unit may occur if the AC selector switch is set incorrectly The un...

Страница 39: ...ency is above 1 MHz c Connect the shield to common of the unit and leave the other end of the shield unconnected and insulated from earth ground 3 Never run Signal or Control cables in the same condui...

Страница 40: ...ocation on the PC board Wire each terminal block in this manner POWER WIRING Primary AC power is connected to terminal 1 and 2 marked VAC 50 60 Hz located on the left hand side of the bottom terminal...

Страница 41: ...BA 5 excitation The excitation and sense leads are generally the same color because they are functionally the same and may be interchanged at the instrument Four wire sensors have an additional sense...

Страница 42: ...ield Integration Totalization Disabled Analog Output 20 mA 6 RESOLUTION 0 1 or 1 degree 7 ACCURACY 0 3 C 23 C and 20 min Warm up 8 RANGE 0 1 res 99 9 to 850 0 C 99 9 to 999 9 F 1 res 200 to 850 C 328...

Страница 43: ...wered source would be capable of operating between 18 and 22 units in a loop 18 ALARMS Optional Solid State Two isolated sinking open collector NPN transistors acting in parallel with relays Imax 100...

Страница 44: ...0 V m 900 Mhz 5 MHz 200 Hz 50 duty cycle Emissions to EN 50081 2 RF interference EN 55011 Enclosure class A Power mains class A Notes 1 Metal bezel of unit connected with ground lead from rear bezel s...

Страница 45: ...er IN DISPLAY 1 Input display out of range 1a Check unit scaling b Check for electrical disturbance 2 Loss of data set ups 2a Check data set ups b Check for electrical disturbance c Disconnect and rec...

Страница 46: ...ble display alarms ENt AL Enable enter alarms dSPHYS Enable display hysteresis ENtHYS Enable enter hysteresis rSt AL Enable reset latched alarms dSPbUF Enable display of peak valley readings rStbUF En...

Страница 47: ...ber 0 99 Print Enter print function or P command function through Serial Option 0 temp 1 temp peak valley and offset 2 temp and alarms 3 temp peak valley alarms hysteresis and offset 4 total 5 temp an...

Страница 48: ...S 115 230 VAC IMR Intelligent Meter for RTD Inputs NO NO NO NO IMR00160 NO YES NO NO IMR00162 YES NO NO NO IMR02160 YES NO YES NO IMR02161 YES YES NO NO IMR02162 YES NO NO 4 to 20 mA IMR02163 YES YES...

Страница 49: ...47 This page is intentionally left blank...

Страница 50: ...48 This page is intentionally left blank...

Страница 51: ...nst damages claims and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profi...

Страница 52: ...764 0839 Red Lion Controls AP 31 Kaki Bukit Road 3 06 04 05 TechLink Singapore 417818 Tel 65 6744 6613 Fax 65 6743 3360 Red Lion Controls BV Basicweg 11b NL 3821 BR Amersfoort Tel 31 0 334 723 225 Fax...

Отзывы: