UMP Replacement Instructions

Warnings and Instructions

2

In addition to the specified torque values noted in this manual, when properly tightened, all flanged fittings should 
have metal-to-metal contact.

The Red Jacket Submersible Turbine Pump’s A-weighted emission sound pressure level at work stations (inside 
the sump pit or on forecourt while refueling) does not exceed 70 dB.

Warnings and Instructions

This section introduces the hazards and safety precautions associated with installing, 
inspecting, maintaining or servicing this product. Before performing any task on this 
product, read this safety information and the applicable sections in this manual, where 
additional hazards and safety precautions for your task will be found. Fire, explosion, 
electrical shock or pressure release could occur and cause damage to property, 
environment, resulting in serious injury or death, if these safe service procedures are 
not followed.

PRELIMINARY PRECAUTIONS

You are working in a potentially dangerous environment of flammable fuels, vapors, and high 
voltage or pressures. Only trained or authorized individuals knowledgeable in the related 
procedures should install, inspect, maintain or service this equipment. 

Read the Manual

Read, understand and follow this manual and any other labels or related materials supplied with this equipment. If 
you do not understand a procedure, call 1-800-323-1719 to locate a qualified technician. It is imperative to your 
safety and the safety of others to understand the procedures before beginning work. 

Make sure your 

employees and any service contractors read and follow the instructions. 

Follow the Regulations

Applicable information is available in National Fire Protection Association (NFPA) 30A; 

Code for Motor Field 

Dispensing Facilities and Repair Garages

, NFPA 70; 

National Electrical Code

 (NEC), Occupational Safety and 

Hazard Association (OSHA) regulations and federal, state, and local codes. All these regulations must be 
followed. Failure to install, inspect, maintain or service this equipment in accordance with these codes, regulations 
and standards may lead to legal citations with penalties or affect the safe use and operation of the equipment.

WARNING

This product operates in the highly combustible atmosphere of a gasoline storage tank.

FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS 
COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY 
OR DEATH.

1. All installation work must comply with the latest issue of the National Electrical Code 

(NFPA 70), the Code for Motor Fuel Dispensing Facilities and Repair Garages (NFPA 
30A), and any European, national, state, and local code requirements that apply.

2. Turn off, tag, and lockout power to the STP before connecting or servicing the STP.

3. Before installing pipe threads apply an adequate amount of fresh, UL classified for 

petroleum, non-setting thread sealant. For E85AG applications, Loctite 564 is 
recommended for all field serviceable pipe threads.

4. When servicing unit, use non-sparking tools and use caution when removing or 

installing equipment to avoid generating a spark.

5. To protect yourself and others from serious injury, death, or substantial property 

damage, carefully read and follow all warnings and instructions in this manual. 

OFF

WARNING

WARNING

Содержание Quick-Set AGUMP150S1

Страница 1: ...Manual No 577014 053 Revision D Replacement Instructions Red Jacket UMP Red Jacket Quick Set Submersible Pump...

Страница 2: ...f any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Fax Bill of Lading to V R Customer Service at 800 234 5...

Страница 3: ...gure 7 UMP Bolts And Gasket 13 Figure 8 Verifying Pigtail s Female Connector Is Seated Properly In Discharge Head 14 Tables Table 1 Maximum Specific Gravity And Maximum Viscosity 4 Table 2 Electrical...

Страница 4: ...Turn Off power to the device and associ ated accessories when servicing the unit WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION indicates...

Страница 5: ...re your employees and any service contractors read and follow the instructions Follow the Regulations Applicable information is available in National Fire Protection Association NFPA 30A Code for Moto...

Страница 6: ...er s station WILL NOT shut off electrical power to the pump dispenser This means that even if you press a button on the console labeled EMERGENCY STOP ALL STOP PUMP STOP or something similar fuel may...

Страница 7: ...ted for the following fuel compatibility 100 Diesel 100 Gasoline Gasoline and up to 10 Ethanol 15 Methanol 20 MTBE 20 ETBE 20 TAME All models of The Red Jacket with the AG prefix are UL Listed for the...

Страница 8: ...144 224 5 17 5 AGUMP75S1 UMP75U1 3 4 60 1 200 250 6 5 25 2 9 3 6 14 9 18 2 17 7 21 9 410164 001 17 5 AGUMP150S1 UMP150U1 1 1 2 60 1 200 250 10 5 37 2 0 2 5 11 6 14 2 13 5 16 8 410164 002 25 X3AGUMP15...

Страница 9: ...1 1 2 60 1 200 250 10 5 33 2 8 3 4 6 8 8 2 9 4 11 3 410164 002 25 AGUMP200S1 3 AGUMPL200S1 3 UMP200U1 3 UMPL200U1 3 2 60 1 200 250 11 4 44 1 9 2 3 3 4 4 1 5 1 6 2 410164 003 40 AGUMP75S3 3 UMP75U3 3 3...

Страница 10: ...8 505 30 5 13 9 UMP75U17 3 AGUMP75U17 3 3 4 19 1 4 489 19 483 28 12 7 UMP150U1 AGUMP150S1 1 1 2 20 1 2 519 20 5 8 524 34 15 5 X3P150U1 X3AGUMP150S1 1 1 2 21 1 4 540 21 1 2 546 35 15 8 UMP150U3 3 AGUMP...

Страница 11: ...d down line from the pump close it 2 Remove the two extractable lock down nuts and discard them see Figure 2 The springs on the lock down studs between the extractable s flange and the manifold will p...

Страница 12: ...inding occurs during removal stop and determine the cause of the binding and correct the situation before proceeding with removal For all models with the RA suffix take care not to damage the powder c...

Страница 13: ...UMP retaining bolts Use hand force to push the UMP onto the discharge head If the UMP does not seat snug against the discharge head remove the UMP and correct the problem Fasteners are not metric use...

Страница 14: ...nd in the kit Apply anti seize also found in the kit to the lock down studs prior to nut and washer installation 15 Turn the air purge screw 2 3 turns counterclockwise see Figure 2 The air purge screw...

Страница 15: ...ssure to flow into the tank or back out Functional Element screw Confirm that the packer wiring compartment cover plug with lifting eyebolt is properly torqued at 50 ft lbs 70 N m Confirm that the lif...

Страница 16: ...indexing tab of the pigtail is seated in the notch of the discharge head Figure 7 UMP Bolts And Gasket 11 Pull the pigtail connector in the discharge head out far enough to see the o ring in the sidew...

Страница 17: ...nt 15 Replace the packer o ring and discharge Quad seal after lubricating them with petroleum based jelly 16 Reinstall the extractable portion into the tank aligning the positioning dowels of the mani...

Страница 18: ...ressure at line test port 50 psi 345 kPa maximum Excessive pressure above normal test pressure of 50 55 psi 345 380 kPa may damage check valve seat and other system components 4 After completion of li...

Страница 19: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: