I N S T A L L A T I O N   I N S T R U C T I O N S

RSH-50

Surge Protective Device (SPD) for Single-Phase System

120/240 VAC Type 1

Installation

1) To assure proper installation, measure the voltage on each 

phase and ensure the correct device is installed. 

2) Turn off power to the circuit where surge protector is to be 

installed.

3) Mount device to keep conductor length as short as 

possible. Cut wires to length and connect to circuit per 

wiring diagram below avoiding sharp bends or looping.

4) Reinstall covers, restore power and confirm diagnostic 

LED is illuminated.

Device Ratings

Normal Voltage

Per Leg

Max. Operating Voltage 

(MCOV) Per Leg

Max. Discharge 

Current (IMAX)

120 VAC

150 VAC

50kA

240 VAC DIAGRAM 

Split-Phase System: 1 Ph, 2W + G

240 VAC 2-POLE DISCONNECT 

UL Type 1 SPD

5ME8

Para instrucciones en español visite 

www.rectorseal.com 

Technical Support Call 1-800-648-6802

 

All surge protection devices require a good ground connection for effective operation

Black

Black

Green

Ground

120 VAC DIAGRAM 

Single-Phase System: 1 Ph, 2W + G 

240 VAC

120 VAC

120 VAC

Diagnostic Operations

LED ON

 =

System protected

LED OFF

 =

Replaced Device

BLACK
GREEN

BLACK

BLACK
GREEN

BLACK

120 VAC

Diagnostic Operations

LED ON

 =

System protected

LED OFF

 =

Replaced Device

BLACK
GREEN

BLACK

120 VAC

Diagnostic Operations

LED ON

 =

System protected

LED OFF

 =

Replaced Device